Holdowns
Holdowns
MiTek
®
Product Catalog
HPA / PA / PAI Purlin Anchors
HPA series – For installation into poured concrete walls,
foundations, or masonry. The HPA is the heavy-duty version
of the PA anchor.
PA series – For installation into poured concrete or concrete
block walls and foundations.
PAI series – For wood I-Joist applications. An expanded 3"
on-center nail spacing reduces splitting along I-Joist ange.
Materials: HPA – 10 gauge; PA / PAI – 12 gauge
Finish: G90 galvanizing
Options: See chart for Corrosion Finish Options
Codes: IBC 1620.2.1
Installation:
• Use all specied fasteners. See Product Notes, page 18.
• Minimum concrete strength is 2,500 psi.
The allowable loads for bolts are based on parallel to grain
loading with a 3" minimum member thickness, except the
HPA which requires a 3-12" thick wood member. Reduce
load per code requirements when minimum member
thickness is not achieved.
Minimum concrete end/edge distance is 4" for PA / PAI series,
and 6" for HPA series.
• Minimum CMU end/edge distance is 20".
Designer may specify alternate fastening schedules. Refer
to Nail Specication Table on page 23 for nail shear values.
Load values shall not exceed published allowable loads.
No anchor bolts are needed for achieving efcient stress
transfer from framing to concrete walls or foundations.
Typical PA holdown
installation
Typical PA
purlin installation
Typical PAI
I-Joist purlin face installation
Ledger
#4 rebar
min
4"
PA / HPA
L
2-1/16"
1-1/2"
4-1/2"
PAI
L
2-1/16"
Continued on next page