User`s manual

10
Long Pipe Length
Piping length has extended max height difference between indoor
units from 4m to 18m and enables us to put indoor unit on extra
three floors.
8~12HP(KX6) 14~48HP(KX6), 8~48HP(KXR6)
As a result of the adoption of thinner refrigerant piping and refrigerant
volume reductions, the industry's longest 160 m actual piping length or
1000m total piping length is realized.
Outdoor unit
Height difference
50m
(outdoor unit above)
40m
(outdoor unit below)
Max height
difference
between
indoor units:
15m
Indoor unit
Indoor unit
Indoor unit
Max: 0.4m
Furthest
indoor unit:
160m
Max: 10m
Max: 5m
To the
first branch:
max 130m
From the first branch
to the furthest
indoor unit: 40m
Total length:
510 1000m
*
*
The difference in length from the first branch must be within 40m.
-core
1350mm 1350mm
1350mm
m
(1)Divide up the refrigerant system into independent refrigeration circuit systems in case required additional refrigerant on site is 50kg or more for
14~24HP and 100kg or more for 26~48HP.
(2)In case indoor unit connection capacity is 130% or more or total piping length is 510m or more, additional charge of refrigerant and oil on site
is required. Refer to our Installation Manual for details.
KX6(14~48HP) is portable and the uniform reduced footprint
allows neat, continuous installation.
Easy Transportation & Installation
Due to realization of significant reduction in size and foot print which is one of
the smallest in the industry, transportation in an elevator made for six persons
(Width:1400mm, Depth:850, Open area:800mm) is possible, eliminating cost
of a crane and reducing labor.
1,400
850
800
H1,675
x
W1,080
x
D480
8~12HP (KX6)
Transportation in an
elevator made for six
persons
Easy
transportation
Outdoor unit
Total length: 510m
To the
first branch:
max 130m
From the first
branch to the
furthest indoor
unit: 40m
Height difference
50m
(outdoor unit above)
40m
(outdoor unit below)
Furthest
indoor unit:
160m
Max height
difference
between
indoor units:
4
m
Indoor unit
Indoor unit
Indoor unit