Easy Service
Blower
compartment
Mechanical
compartment
Quick and easy access to service parts by separation of
compartments.
Check Operation (8~48HP)
Closing of Service valve, crossing connection of refrigerant
piping and electrical wiring, proper operation of EEV (Electrical
Expansion Valve) can be checked automatically in cooling
operation. This check operation can be done at 0~43°C outdoor
temperature and 10~32°C indoor temperature by use of
outdoor unit dip switch. The check should be done in one
refrigerant system. It takes 15~30 minutes and avoids frequent
failure by preventing careless mistakes during installation.
Applying nonpolar 2-core in new remote control line, it is very
convenient for installation including renewal case.
previous New
-core
-core-core
New remote control for all indoor units
The wiring must be a 2-core shielded cable size 0.75mm
2
to
1.25mm
2
.
The max length of 2-core can be 1500m from 1000m of
previous models.
Max length of electrical wiring
previous New
m
mm
Wide Range of Operation
For the capacities under low temperature conditions, refer to technical manual.
Heating
NEW
previous
previous
Cooling
NEW
+43°C
+15.5°C
-15°C
-20°C
50403020100-10-20
KX6,KXR6 series permits a system design considering a heating range operation under a low temperature condition up to -20°C from -15°C of
previous model and a cooling range operation under -15°C from -5°C of that.
-15°C
-5°C