Heat pump systems 14, 16hp (40.0kW~45.0kW)
50
40
30
20
10
0
-10
-20
Heating
Cooling
+43
°
C
-15
°
C
+15.5
°
C
-20
°
C
Range of operation
Specifications
Item
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Sound pressure level
Refrigerant piping size
Capacity connection
Number of connectable indoor units
Cooling
Heating
Starting current
Power
consumption
Running
current
HxWxD
R410A
Cooling/Heating
Liquid line
Gas line
Cooling
Heating
Cooling
Heating
kW
A
kW
A
mm
kg
kg
dB(A)
mm(in)
%
14HP
40.0
45.0
11.27
11.73
18.4-16.9
19.6-17.9
59.5/60
ø25.4(1") [ø28.58(1 1/8")]
36
FDC400KXE6
16HP
45.0
50.0
12.97
13.10
21.1-19.3
21.7-19.9
62.5/62.5
ø28.58(1 1/8")
40
FDC450KXE6
ø12.7(1/2")
50~200
1690x1350x720
317
11.5
8
3 Phase 380-415V, 50Hz
Model No.
FDC400KXE6
FDC450KXE6
Nominal Cooling Capacity
40.0kW
45.0kW
The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal
for open plan areas.
Connect up to 40 indoor units/up to 200% capacity.
High efficiency with COP (in cooling) up to 3.6.
KX6 employs DC inverter compressors ONLY.
Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.
Uniform footprint of models (14,16hp)
allows continuous side-by-side installation
Outdoor unit
Total length: 1000m
To the
first branch:
max 130m
From the first
branch to the
furthest indoor
unit: 90m
Height difference
50m
(outdoor unit above)
40m
(outdoor unit below)
Furthest
indoor unit: 160m
Max height
difference
between
indoor units:
18m
Indoor unit
Indoor unit
Indoor unit
Model
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
Outdoor units
IntakeIntake