User`s manual

36
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
Specifications
Model No.
FDC735KXRE6 (FDC335-K+FDC400)
FDC800KXRE6 (FDC400x2)
FDC850KXRE6 (FDC400+FDC450)
FDC900KXRE6 (FDC450x2)
Nominal Cooling Capacity
73.5kW
80.0kW
85.0kW
90.0kW
Heat
recovery 3-pipe combination systems 26, 28, 30, 32hp
(73.5kW – 90.0kW)
Item
Combination (FDC)
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Refrigerant piping size
Capacity connection
Number of connectable indoor units
Cooling
Heating
Starting current
Power
consumption
Operating
current
HxWxD
R410A
Liquid line
Suction Gas line
Discharge Gas line
Cooling
Heating
Cooling
Heating
kW
A
kW
A
mm
kg
kg
in (mm)
%
FDC735KXRE6 FDC800KXRE6 FDC850KXRE6 FDC900KXRE6
Range of operation
Outdoor unit
Total length: 1000m
To the
first branch:
max 130m
From the first
branch to the
furthest indoor
unit: 90m
Height difference
50m
(outdoor unit above)
40m
(outdoor unit below)
Furthest
indoor unit: 160m
Max height
difference
between
indoor units:
18m
Indoor unit
Indoor unit
Indoor unit
335KXRE6-K
400KXRE6
26HP
73.5
82.5
21.08
21.3
34.4-31.5
35.4-32.4
ø25.4(1”)[ø28.58(1 1/8”)]
53
400KXRE6
400KXRE6
28HP
80.0
90.0
23.22
23.86
38.0-34.8
39.8-36.4
58
400KXRE6
450KXRE6
30HP
85.0
95.0
25.10
25.25
40.6-37.2
41.9-38.3
ø28.58(1 1/8”)
61
450KXRE6
450KXRE6
32HP
90.0
100.0
26.98
26.64
43.2-39.6
44.0-40.2
65
for simultaneous heating and cooling
The KXR6 heat recovery systems offer high performance VRF for almost
every type of building, with the capacity for simultaneous heating and
cooling operations of individual indoor units. Energy efficiency is
maximised by employing DC inverter compressors ONLY, and distributing
surplus heat from cooling operations to areas where it is required (and
vice versa) resulting in COP (in cooling) from 3.3 to 3.5.
Connect from 50% up to 160% capacity indoor units.
Industry leading total piping length up to 1000m and a maximum pipe run
of 160m.
50
40
30
20
10
0
-10
-20
Heating
Cooling
+43
°
C
-15
°
C
+15.5
°
C
-20
°
C
3 Phase 380-415V, 50Hz
16
1690x2700x720
674
33
ø15.88(5/8”)
ø31.75(1 1/4”)[ø34.92(1 3/8”)]
50~160
Uniform footprint of all
models (from 8hp~24hp)
allows continuous side-by-
side installation
Outdoor units