52
Ceiling Cassette -1way Compact-
FDTQ
Model No.
FDTQ22KXE6D
FDTQ28KXE6D
FDTQ36KXE6D
Condensate drain pump
included as standard
or less Max.Drain up
295~325
63
600
210
Optional wide panel shown for solid ceiling
Direct blow panel Duct panel
Direct blow panel Duct panel
Direct blow panel Duct panel
Hi:41 Me:38 Lo:33
Hi:7 Me:6 Lo:5
2.2
2.5
2.8
3.2
3.6
4.0
1 Phase 220-240V, 50Hz
kW
kW
kW
dB(A)
mm
kg
CMM
mm(in)
Item
Panel Name
Panel mode (Option)
Nominal cooling capacity
Nominal heating capacity
Power source
Power
consumption
Sound pressure level
Exterior dimensions
H x W x D
Net weight
Air flow
Outside air intake
Air filter, Q’ty
Remote control(option)
Installation data
Refrigerant piping size
35x625x650 35x780x650
Possible
Pocket Plastic net x1 (Washable)
wired:RC-E4, RCH-E3 wireless:RCN-KIT3-E
Liquid line:ø6.35(1/4")
Gas line:ø12.7(1/2")
Liquid line:ø6.35(1/4")
Gas line:ø9.52(3/8")
Model
FDTQ22KXE6D FDTQ28KXE6D FDTQ36KXE6D
TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER
Unit:23 Panel:2.5 Unit:23 Panel:3
Hi:41 Me:38 Lo:33
Hi:7 Me:6 Lo:5
35x625x650 35x780x650
Unit:23 Panel:2.5 Unit:23 Panel:3
Hi:41 Me:38 Lo:33
Hi:7 Me:6 Lo:5
35x625x650 35x780x650
Unit:23 Panel:2.5 Unit:23 Panel:3
Hi:41 Me:38 Lo:33
Hi:7 Me:6 Lo:5
35x625x650 35x780x650
Unit:23 Panel:2.5 Unit:23 Panel:3
Hi:41 Me:38 Lo:33
Hi:7 Me:6 Lo:5
35x625x650 35x780x650
Unit:23 Panel:2.5 Unit:23 Panel:3
Hi:41 Me:38 Lo:33
Hi:7 Me:6 Lo:5
35x625x650 35x780x650
Unit:23 Panel:2.5 Unit:23 Panel:3
Unit
Panel
Ultra slim design at just 250mm above the ceiling
Fresh air
opening
for ducting
(Knock out)
35
250
285
Cooling
Heating
0.05-0.07
0.05-0.07
0.05-0.07
0.05-0.07
0.05-0.07
0.05-0.07
Holes for
tapping screws
Fits into standard
600 x 600 ceiling
•
Comfortable effective cooling for small rooms,
with low fan speed air flow at just 5.4m
3
/min.
250x570x570 250x570x570 250x570x570
Specifications
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
RC-E4
(option)
Wired remote control
RCH-E3
(option)
Wireless remote control
RCN-KIT3-E
(option)
Powerful-Hi can be selected. Sound pressure level: FDTQ22/38/36 45dB(A). Air flow: FDTQ22/38/36 8CMM.