User`s manual

56
Duct Connected -Low/Middle Static Pressure-
FDUM
Model No.
FDUM22KXE6D
FDUM28KXE6D
FDUM36KXE6D
FDUM45KXE6D
FDUM56KXE6D
FDUM71KXE6D
FDUM90KXE6D
FDUM112KXE6D
FDUM140KXE6D
Dimensions
All measurements in mm.
FDUM22KXE6D
Hi:35 Me:32 Lo:29
Hi:34 Me:31 Lo:28
Hi:33 Me:31 Lo:28 Hi:35 Me:32 Lo:29
Hi:10 Me:9 Lo:8
Hi:36 Me:33 Lo:30
33 5934 40
2.2
2.5
2.8
3.2
3.6
4.0
4.5
5.0
5.6
6.3
7.1
8.0
9.0
10.0
11.2
12.5
14.0
16.0
FDUM22KXE6D FDUM28KXE6D FDUM36KXE6D FDUM45KXE6D FDUM56KXE6D FDUM71KXE6D FDUM90KXE6D
FDUM112KXE6D FDUM140KXE6D
Hi:12 Me:11 Lo:10
Hi:37 Me:35 Lo:32 Hi:38 Me:36 Lo:33
Hi:20 Me:18 Lo:15
Hi:16 Me:15 Lo:14 Hi:28 Me:25 Lo:22 Hi:28 Me:25 Lo:22
Hi:13 Me:12 Lo:11
1 Phase 220-240V, 50Hz
kW
kW
kW
dB(A)
mm
kg
CMM
Pa
mm(in)
Item
Nominal cooling capacity
Nominal heating capacity
Power source
Power
consumption
Sound pressure level
Exterior dimensions
H x W x D
Net weight
Air flow
External
Static pressure
Outside air intake
Air filter, Q’ty
Remote control(option)
Installation data
Refrigerant piping size
299 x 750 x 635 350 x 1370 x 635299 x 950 x 635
Possible
Procure locally
wired:RC-E4, RCH-E3 wireless:RCN-KIT3-E
Liquid line:ø6.35(1/4")
Gas line:ø12.7(1/2")
Liquid line:ø9.52(3/8")
Gas line:ø15.88(5/8")
Liquid line:ø6.35(1/4")
Gas line:ø9.52(3/8")
Model
85
(at 34CMM)
90
(at 28CMM)
85
(at 18CMM)
85
(at 20CMM)
85(at 14CMM)85(at 12CMM)
85
(at 10CMM)
Cooling
Heating
0.10-0.12
0.10-0.12
0.18-0.21
0.18-0.21
0.13-0.15
0.13-0.15
0.17-0.19
0.17-0.19
0.31-0.35
0.31-0.35
0.27-0.31
0.27-0.31
0.16-0.18
0.16-0.18
LOW NOISE
Specifications
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB. External static
pressure of indoor unit is 60Pa.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Filter kit
UM-FL1E : for 22~56
UM-FL2E : for 71, 90
UM-FL3E : for 112, 140
(option)
RC-E4
(option)
Wired remote control
RCH-E3
(option)
Wireless remote control
RCN-KIT3-E
(option)
*
Filter pressure loss:5pa
Powerful-Hi can be selected. Sound pressure level: FDUM22/28/36 35dB(A), FDUM45/56 36dB(A), FDUM71/90 38dB(A), FDUM112/140 41dB(A). Air flow: FDUM22 12CMM, FDUM28/36/45/56 14CMM, FDUM71 18CMM, FDUM90
23 CMM, FDUM112/140 34CMM.