User`s manual

82
Coming soon
FDCH335KXE6-K
FDCH400KXE6
FDCH450KXE6
FDCH504~680KXE6
14~48hp (40.0~136.0kW)
Production by order
FDCH335KXE6-K & FDCH560KXE6-K are only used for combining with other models.
Model No.
FDCH335KXE6-K
FDCH400KXE6
FDCH450KXE6
FDCH504KXE6
FDCH560KXE6
FDCH560KXE6-K
FDCH615KXE6
FDCH680KXE6
Nominal Cooling Capacity
33.5 kW
40.0 kW
45.0 kW
50.4 kW
56.0 kW
56.0 kW
61.5 kW
68.0 kW
Model No.
FDCH735KXE6 (FDCH335-K+FDCH400)
FDCH800KXE6 (FDCH400x2)
FDCH850KXE6 (FDCH400+FDCH450)
FDCH900KXE6 (FDCH450x2)
FDCH960KXE6 (FDCH450+FDCH504)
FDCH1010KXE6 (FDCH504x2)
FDCH1065KXE6 (FDCH504+FDCH560)
FDCH1130KXE6 (FDCH560x2)
FDCH1180KXE6 (FDCH560-K+FDCH615)
FDCH1235KXE6 (FDCH615x2)
FDCH1300KXE6 (FDCH615+FDCH680)
FDCH1360KXE6 (FDCH680x2)
Nominal Cooling Capacity
73.5 kW
80.0 kW
85.0 kW
90.0 kW
96.0 kW
101.0 kW
106.5 kW
113.0 kW
118.0 kW
123.5 kW
130.0 kW
136.0 kW
Outdoor units
High Head series ( 00m)
Maximum allowable height difference between the outdoor and
the indoor unit located at the lowest height position has been
increased from 50m to 00m.
(When the outdoor unit is located at higher position than the
indoor unit)
Total length:
000m
Outdoor
unit
Height
difference
Max height
difference
between
indoor units:
Indoor unit
Indoor unit
Indoor unit
Max height difference:
0.4m
Furthest indoor unit : 160m
Max: 10m
Max: 5m
To the
first branch:
max 130m
From the first
branch to the
furthest
indoor unit:
*
1
*
2
The difference between the longest and shortest indoor unit piping from
the first branch must be within 40m.
In case of less than 50m, the standard models are applied.
*
1
*
2
-00°C : not fixed
00m, 000m : not fixed
00m : not fixed
Range of operation
50
40
30
20
10
0
-10
-20
Heating
Cooling
+43
°
C
-5
°
C
+15.5
°
C
-00
°
C