User`s manual

83
Specifications
Item
Combination (FDCH)
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Refrigerant piping size
Capacity connection
Number of connectable indoor units
Cooling
Heating
Starting current
Power consumption
Running current
HxWxD
R410A
Liquid line
Gas line
Cooling
Heating
Cooling
Heating
kW
kW
A
kW
kW
A
A
mm
kg
kg
mm(in)
%
FDCH735KXE6 FDCH800KXE6 FDCH850KXE6 FDCH900KXE6
3 Phase 380-415V, 50Hz
16
1690x2700x720
319x2
11.5x2
ø19.05(3/4")
ø31.8(1 1/4") [ø34.92(1 3/8")]
not fixed
335KXE6-K
400KXE6
26HP
73.5
82.5
20.21
20.66
32.9-30.2
34.4-31.4
53
400KXE6
400KXE6
28HP
80.0
90.0
22.54
23.46
36.8-33.8
39.2-35.8
58
400KXE6
450KXE6
30HP
85.0
95.0
24.24
24.83
39.5-36.2
41.3-37.8
61
450KXE6
450KXE6
32HP
90.0
100.0
25.94
26.20
42.2-38.6
43.4-39.8
65
Model
Item
Combination (FDCH)
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Refrigerant piping size
Capacity connection
Number of connectable indoor units
Cooling
Heating
Starting current
Power consumption
Running current
HxWxD
R410A
Liquid line
Gas line
Cooling
Heating
Cooling
Heating
kW
kW
A
kW
kW
A
A
mm
kg
kg
mm(in)
%
FDCH1180KXE6
560KXE6-K
615KXE6
42HP
118.0
132.0
37.16
35.27
60.5-55.4
58.7-53.8
69
FDCH1235KXE6
615KXE6
615KXE6
44HP
123.5
138.0
40.74
36.96
66.2-60.6
61.4-56.2
72
FDCH1300KXE6
615KXE6
680KXE6
46HP
130.0
142.0
45.35
37.56
73.4-67.2
62.3-57.1
76
FDCH1360KXE6
680KXE6
680KXE6
48HP
136.0
146.0
49.96
38.16
80.6-73.8
63.2-58.0
80
Model
3 Phase 380-415V, 50Hz
16
2048x2700x720
357x2
11.5x2
ø22.22(7/8")
ø38.1(1 1/2")
not fixed
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
Item
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Sound pressure level
Refrigerant piping size
Capacity connection
Number of connectable indoor units
Cooling
Heating
Starting current
Power consumption
Running current
HxWxD
R410A
Cooling / Heating
Liquid line
Gas line
Cooling
Heating
Cooling
Heating
kW
kW
A
kW
kW
A
A
mm
kg
kg
dB(A)
mm(in)
%
14HP
40.0
45.0
11.27
11.73
18.4-16.9
19.6-17.9
59.5 / 59.5
ø25.4(1") [ø28.58(1 1/8")]
36
FDCH400KXE6
16HP
45.0
50.0
12.97
13.10
21.1-19.3
21.7-19.9
62.5 / 62.5
ø28.58(1 1/8")
40
FDCH450KXE6
ø12.7(1/2") ø15.88(5/8")
ø28.58(1 1/8")
1690x1350x720
319
Model
3 Phase 380-415V, 50Hz
8
343
11.5
2048x1350x720
18HP
50.4
56.5
14.73
15.12
24.1-22.0
25.2-23.1
61.5 / 61.5
36
FDCH504KXE6 FDCH560KXE6
20HP
56.0
63.0
16.79
16.79
27.4-25.1
28.0-25.7
63.0 / 63.0
40
357
FDCH615KXE6
22HP
61.5
69.0
20.37
18.48
33.1-30.3
30.7-28.1
64.5 / 64.5
44
FDCH680KXE6
24HP
68.0
73.0
24.98
19.08
40.3-36.9
31.6-29.0
65.0 / 65.0
49
Item
Combination (FDCH)
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Refrigerant piping size
Capacity connection
Number of connectable indoor units
Cooling
Heating
Starting current
Power consumption
Running current
HxWxD
R410A
Liquid line
Gas line
Cooling
Heating
Cooling
Heating
kW
kW
A
kW
kW
A
A
mm
kg
kg
mm(in)
%
FDCH960KXE6 FDCH1010KXE6 FDCH1065KXE6 FDCH1130KXE6
3 Phase 380-415V, 50Hz
16
2048x2700x720
11.5x2
450KXE6
504KXE6
34HP
96.0
108.0
27.70
28.22
45.2-41.3
46.9-43.0
319+343
69
504KXE6
504KXE6
36HP
101.0
113.0
29.46
30.24
48.2-44.0
50.4-46.2
59
504KXE6
560KXE6
38HP
106.5
119.5
31.52
31.91
51.5-47.1
53.2-48.8
343x2
62
560KXE6
560KXE6
40HP
113.0
127.0
33.58
33.58
54.8-50.2
56.0-51.4
66
Model
ø19.05(3/4")
ø31.8(1 1/4")[ø34.92(1 3/8")]
ø22.22(7/8")
ø38.1(1 1/2")
not fixed