User`s manual

86
KX4
R410AR410A
Specifications
KX4 Outdoor units
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
Model No.
FDCA224HKXE4D
FDCA280HKXE4D
FDCA335HKXE4D
Nominal Cooling Capacity
22.4kW
28.0kW
33.5kW
Heat pump systems 8, 10, 12hp (22.4kW~33.5kW)
Uniform footprint of all models
allows continuous side-by-side installation
50
40
30
20
10
0
-10
-20
Heating
Cooling
+43
°
C
-5
°
C
+15.5
°
C
-20
°
C
Range of operation
Outdoor unit
Total length: 510m
To the
first branch:
max 130m
From the first
branch to the
furthest indoor
unit: 40m
Height difference
50m
(outdoor unit above)
40m
(outdoor unit below)
Furthest
indoor unit: 160m
Max height
difference
between
indoor units:
15m
Indoor unit
Indoor unit
Indoor unit
Item
Nominal horse power
Power source
Nominal capacity
Electrical characteristics
Exterior dimensions
Net weight
Refrigerant charge
Sound pressure level
Refrigerant piping size
Capacity control
Number of connectable indoor units
Cooling
Heating
Starting current
Power
consumption
Operating
current
HxWxD
R410A
Cooling/Heating
Liquid line
Gas line
Cooling
Heating
Cooling
Heating
kW
A
kW
A
mm
kg
kg
dB(A)
mm(in)
%
8HP
22.4
25.0
5.70
5.98
9.6-8.8
9.6-8.8
57/57
ø19.05(3/4")
27~126
13
FDCA224HKXE4D
10HP
3 Phase 380V-415V, 50Hz
28.0
31.5
5
8.26
8.06
13.6-12.4
13.3-12.4
1690x1350x720
245
11.5
57/58
20~114
16
FDCA280HKXE4D FDCA335HKXE4D
ø9.52(3/8")
ø22.22(7/8")
12HP
33.5
37.5
9.53
9.84
15.5-14.2
16.3-14.9
60.5/61
ø12.7(1/2")
19~117
20
IntakeIntake
185
outdoor
unit
*Up to 50 Pa
discharge duct
inside
outside
louvre
Air
Air
Superlink models (not Superlink- models)
The KX4 heat pump 2-pipe systems offer high performance VRF
for applications that require either cooling only or heating only.
Connect up to 20 indoor units/up to 130% capacity.
High efficiency with COP (in cooling) from 3.6 to 3.9.
In case an outdoor unit is installed inside the building
and outdoor exhaust air is discharged to outside the
building through duct system, these units have
necessary minimum external static pressure (50Pa).
Model
Production by order