Specifications

Page 63
Indoor unit
Page 64
LOSSNAY
LGH-50RX
5
-E60
LGH-65RX5-E60
LGH-80RX5-E60
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2
O
)
(
Pa
)
Heating
Cooling
LGH-50RX
5
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
1.34-1.38
285-315
500
139
20.4
200
72.0
69.0
67.5
34-35.5
1.20-1.25
263-298
500
139
6.6
65
72.0
69.0
67.5
30-32.5
0.86-0.90
187-213
380
106
4.1
40
78.0
72.0
71.0
25-27.5
0.36-0.39
79-93
180
50
0.8
8
83.0
79.0
79.0
18-18.5
Extra High High Low Extra Low
1.34-1.39
285-317
500
139
20.4
200
34.5-36
1.20-1.25
263-298
500
139
6.6
65
31-33
0.86-0.90
187-213
380
106
4.1
40
25.5-27.5
0.36-0.39
79-93
180
50
0.8
8
18-18.5
32
Under 2.5A Less
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 16dB greater than the indicated value.(at High Fan speed)
Frequency / Power source
60Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2
O
)
(
Pa
)
Heating
Cooling
LGH-65RX
5
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
1.9-2.0
415-470
650
181
18.9
185
71.0
67.5
67.0
35.5-37.5
1.8-1.9
390-435
650
181
6.1
60
71.0
67.5
67.0
33-34.5
1.2-1.3
253-290
470
131
3.1
30
76.0
72.5
72.5
26.5-29
0.6-0.6
120-140
240
67
0.8
8
82.0
79.0
79.0
19-20
Extra High High Low Extra Low
2.0-2.0
433-470
650
181
18.9
185
36-37.5
1.8-1.9
390-435
650
181
6.1
60
33-35
1.2-1.3
253-290
470
131
3.1
30
27-30
0.6-0.6
120-140
240
67
0.8
8
19-20
40
Under 4.0A Less
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 10dB greater than the indicated value.(at High Fan speed)
Frequency / Power source
60Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2
O
)
(
Pa
)
Heating
Cooling
LGH-80RX
5
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
2.4-2.4
498-542
800
222
23.5
230
74.0
71.0
70.0
35.5-37
2.1-2.2
456-505
800
222
12.7
125
74.0
71.0
70.0
32.5-34.5
1.6-1.7
350-407
660
183
8.7
85
76.0
73.0
72.0
29-31
0.6-0.7
130-158
300
83
1.8
18
84.0
82.0
82.0
21-21
Extra High High Low Extra Low
2.4-2.4
505-550
800
222
23.5
230
36-38
2.1-2.2
456-508
800
222
12.7
125
33-35
1.6-1.7
350-407
660
183
8.7
85
31-32
0.6-0.7
130-158
300
83
1.8
18
21-21
53
Under 4.5A Less
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 16dB greater than the indicated value.(at High Fan speed)
Frequency / Power source
60Hz / Single phase 220-240V
Model line up
Specification
LGH-15RX
5
-E60
LGH-35RX5-E60
LGH-25RX5-E60
Frequency / Power source
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2
O
)
(
Pa
)
Heating
Cooling
LGH-15RX
5
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
0.54-0.56
118-134
150
42
14.8
145
80.0
73.5
74.5
29.5-31
0.45-0.46
98-109
150
42
10.7
105
80.0
73.5
74.5
27-29
0.28-0.3
61-69
110
31
5.6
55
82.0
76.5
78.5
21.5-22.5
0.15-0.16
32-37
60
17
1.6
16
85.0
81.5
82.0
18-18
Extra High High Low Extra Low
0.54-0.57
117-135
150
42
14.8
145
29.5-31
0.45-0.47
97-112
150
42
10.7
105
27-29
0.28-0.3
61-69
110
31
5.6
55
22-23.5
0.15-0.16
32-37
60
17
1.6
16
18-19
20
Under 0.9A Less
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 6dB greater than the indicated value.(at High Fan speed)
60Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2
O
)
(
Pa
)
Heating
Cooling
LGH-25RX
5
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
0.61-0.64
132-150
250
69
11.7
115
73.0
63.5
66.5
27.5-29
0.54-0.56
118-134
250
69
7.6
75
73.0
63.5
66.5
25.5-27
0.28-0.3
61-70
145
40
2.5
25
79.5
73.0
75.0
20-21
0.17-0.18
37-42
95
26
1.0
10
82.0
78.0
78.0
18-18
Extra High High Low Extra Low
0.62-0.65
134-152
250
69
11.7
115
28-29.5
0.55-0.57
119-135
250
69
7.6
75
26-27.5
0.28-0.3
61-70
145
40
2.5
25
20.5-21
0.17-0.18
37-42
95
26
1.0
10
18-18
20
Under 1.0A Less
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 10dB greater than the indicated value.(at High Fan speed)
Frequency / Power source
60Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2
O
)
(
Pa
)
Heating
Cooling
LGH-35RX
5
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
1.02-1.02
222-241
350
97
19.4
190
75.0
71.5
71.0
31.5-33
0.93-0.96
202-229
350
97
7.6
75
75.0
71.5
71.0
28.5-30.5
0.65-0.68
141-162
255
71
4.1
40
80.5
74.5
73.5
22.5-26
0.29-0.31
62-73
115
32
0.8
8
85.0
78.0
77.0
18-18
Extra High High Low Extra Low
1.02-1.02
222-241
350
97
19.4
190
32-33.5
0.94-0.97
204-231
350
97
7.6
75
29-31
0.65-0.68
141-162
255
71
4.1
40
22.5-26
0.29-0.31
62-73
115
32
0.8
8
18-18
29
Under 2.0A Less
*The Air outlets noise (45 angle,1.5meters in front of the unit) is about 10dB greater than the indicated value.(at High Fan speed)
Frequency / Power source
60Hz / Single phase 220-240V