Service manual

83
13
SERVICE AND MAINTENANCE
The main controller settings changed from the default settings are reset by replacing the controller board. To facilitate reselecting settings on the main controller, it is
recommended to write down the changes in the sheet below before replacement.
13-1. Engineers Forms (1/2)
Should settings be changed from default, please enter and record new setting in ‘Field Setting’ column. This will ease resetting in the future should the system use
change or the circuit board need to be replaced.
Commissioning/Field settings record sheet
Main controller screen Parameters
Default setting
Field
setting
Notes
Main Zone1 heating room temp 10°C - 30°C 20°C
Zone2 heating room temp *1 10°C - 30°C 20°C
Zone1 heating ow temp 25°C - 60°C 45°C
Zone2 heating ow temp *1 25°C - 60°C 35°C
Cooling ow temp *2 5°C - 25°C 15°C
Zone1 heating compensation curve 9°C - + 9°C 0°C
Zone2 heating compensation curve *1 9°C - + 9°C 0°C
Holiday mode Active/Non active/Set time
Option Forced DHW operation On/Off
DHW On/Off/Timer On
Heating On/Off/Timer On
Holiday mode Active/Non active/Set time
Setting DHW *3 Operation mode Normal/Eco Normal
DHW max. temp. 40°C - 60°C 50°C
DHW temp. drop 5°C - 30°C 10°C
DHW max. operation time 30 - 120 mins 60 mins
DHW mode restriction 30 - 120 mins 30 mins
Legionella prevention *3 Active Yes/No Yes
Hot water temp 60°C - 70°C 65°C
Frequency 1 - 30 days 15 days
Start time 00.00 - 23.00 03.00
Max. operation time 1 - 5 hours 3 hours
Duration of maximum temp. 1 - 120 mins 30 min
Heating/Cooling *2 Zone1 operation mode Heating room temp/Heating ow temp/Heating
compensation curve/Cooling ow temp
Room temp
Zone2 operation mode *1 Heating room temp/Heating ow temp/Heating
compensation curve
Compensation
curve
Compensation
curve
Hi set point Zone1 outdoor ambient temp 15°C - +35°C –15°C
Zone1 ow temp 25°C – 60°C 50°C
Zone2 outdoor ambient temp *1 15°C - +35°C –15°C
Zone2 ow temp *1 25°C - 60°C 40°C
Lo set point Zone1 outdoor ambient temp 15°C - +35°C 35°C
Zone1 ow temp 25°C - 60°C 25°C
Zone2 outdoor ambient temp *1 15°C - +35°C 35°C
Zone2 ow temp *1 25°C - 60°C 25°C
Adjust Zone1 outdoor ambient temp 14°C - +34°C
Zone1 ow temp 25°C - 60°C
Zone2 outdoor ambient temp *1 14°C - +34°C
Zone2 ow temp *1 25°C - 60°C
Holiday DHW *3 Active/Non active Non active
Heating/Cooling *2 Active/Non active Active
Zone1 heating room temp 10°C - 30°C 15°C
Zone2 heating room temp *1 10°C - 30°C 15°C
Zone1 heating ow temp 25°C - 60°C 35°C
Zone2 heating ow temp *1 25°C - 60°C 25°C
Cooling ow temp *2 5°C - 25°C 25°C
Initial settings Language
ENG/FR/GER/SW/SP/IT/DA/NL/FIN/NOR/PT ENG
°C/°F
°C/°F °C
Temp. display
Room/DHW tank/Room&DHW tank /Off Off
Time display
hh:mm/hh:mm AM/AM hh:mm hh:mm
Room sensor settings for Zone1
TH1/Main RC/Room RC1-8/“Time/Zone” TH1
Room sensor settings for Zone2 *1
TH1/Main RC/Room RC1-8/“Time/Zone” TH1
Room RC zone select *1
Zone1/Zone2 Zone1
*1 The settings related to Zone2 can be switched only when Zone2 temperature control is enabled (when Dip SW2-6 and SW 2-7 are ON).
*2 Cooling mode settings are available for ERSC-VM2B only.
*3 Only available if DHW tank present in system.
OCH532A