TRANSISTORIZED INVERTER FR-A500 FR-A500 TRANSISTORIZED INVERTER INSTRUCTION MANUAL HIGH FUNCTION & LOW ACOUSTIC NOISE FR-A520-0.4K to 55K FR-A540-0.4K to 55K OUTLINE Chapter 1 INSTALLATION AND WIRING Chapter 2 OPERATION /CONTROL Chapter 3 PARAMETERS Chapter 4 PROTECTIVE Chapter 5 FUNCTIONS PRECAUTIONS FOR MAINTENANCE AND INSPECTION IB(NA)-0600133E-A (0303) MEE Printed in japan Specifications subject to change without notice.
Thank you for choosing this Mitsubishi transistorized Inverter. This instruction manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the inverter, please read this manual carefully to use the equipment to its optimum. Please forward this manual to the end user.
4. Additional instructions Also note the following points to prevent an accidental failure, injury, electric shock, etc. (1) Transportation and installation CAUTION Environment z When carrying products, use correct lifting gear to prevent injury. z Do not stack the inverter boxes higher than the number recommended. z Ensure that installation position and material can withstand the weight of the inverter. Install according to the information in the Instruction Manual.
(5) Emergency stop CAUTION z Provide a safety backup such as an emergency brake which will prevent the machine and equipment from hazardous conditions if the inverter fails. z When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to the internal parts of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
CONTENTS CHAPTER 1 1.1 Precautions for operation ...................................................................................................................2 Basic Configuration ............................................................................................. 3 1.2.1 1.3 Basic configuration .............................................................................................................................3 Structure .........................................................
3.3.4 PU operation mode (Operation using the operation panel (FR-DU04)) ..........................................................................61 Combined operation mode (Operation using the external input signals and PU)........................................................................62 CHAPTER 4 4.1 63 Parameter Lists .................................................................................................. 64 4.1.1 4.1.2 4.1.3 4.2 PARAMETERS Parameter lists .....................
4.2.43 4.2.44 4.2.45 4.2.46 4.2.47 4.2.48 4.2.49 4.2.50 4.2.51 4.2.52 4.2.53 4.2.54 4.2.55 4.2.56 4.2.57 4.2.58 4.2.59 4.2.60 4.2.61 4.2.62 4.2.63 4.2.64 4.2.65 4.2.66 4.2.67 4.2.68 Commercial power supply-inverter switch-over function (Pr. 135 to Pr. 139) ................................148 Output current detection function (Pr. 150, Pr. 151).......................................................................153 Zero current detection (Pr. 152, Pr. 153)..................................................
Periodic inspection .........................................................................................................................210 Insulation resistance test using megger .........................................................................................211 Pressure test ..................................................................................................................................211 Daily and periodic inspection.........................................................
CHAPTER 1 OUTLINE Chapter 1 This chapter gives information on the basic "outline" of this product. Always read the instructions in this chapter before using the equipment. 1.1 Pre-Operation Information....................................... 2 1.2 Basic Configuration ................................................. 3 1.3 Structure..................................................................
OUTLINE 1.1 Pre-Operation Information 1.1.1 Precautions for operation Incorrect handling might cause the inverter to operate improperly, its life to be reduced considerably, or at the worst, the inverter to be damaged. Handle the inverter properly in accordance with the information in each section as well as the precautions and instructions of this manual to use it correctly. This manual is written for the FR-A500 series transistorized inverters.
OUTLINE 1.2 Basic Configuration 1.2.1 Basic configuration The following devices are required to operate the inverter. Proper peripheral devices must be selected and correct connections made to ensure proper operation. Incorrect system configuration and connections can cause the inverter to operate improperly, its life to be reduced considerably, and in the worst case, the inverter to be damaged.
OUTLINE 1.3 Structure 1.3.
OUTLINE 1.3.2 Removal and reinstallation of the front cover FR-A520-0.4K to 11K, FR-A540-0.4K to 7.5K • Removal 1) Hold both sides of the front cover top and push the front cover down. 2) Hold down the front cover and pull it toward you to remove. (The front cover may be removed with the PU (FR-DU04/FR-PU04) on.) hook 1 Front cover Inverter • Removal 1) Insert the hooks at the bottom of the front cover into the sockets of the inverter.
OUTLINE FR-A520-30K to 55K, FR-A540-30K to 55K • Removal 1) Remove installation screws on the front cover. • Reinstallation 1) Fix the front cover with the installation screws. Note: 1. Fully make sure that the front cover has been reinstalled securely. 2. The same serial number is printed on the capacity plate of the front cover and the rating plate of the inverter.
OUTLINE 1.3.3 Removal and reinstallation of the operation panel To ensure safety, remove and reinstall the operation panel after powering off. • Removal Hold down the top button of the operation panel and pull the operation panel toward you to remove. Removal Reinstallation 1 When reinstalling the operation panel, insert it straight and reinstall it securely. • Reinstallation using the connection cable 1) Remove the operation panel. 2) Disconnect the modular jack type relay connector.
MEMO 8
CHAPTER 2 INSTALLATION AND WIRING Chapter 1 This chapter explains the basic "installation and wiring" for use of this product. Always read the instructions and other information before using the equipment. 2.1 Installation ............................................................. 10 2.2 Wiring .................................................................... 12 2.3 Other wiring ...........................................................
INSTALLATION AND WIRING 2.1 Installation 2.1.1 Instructions for installation 1) Handle the unit carefully. The inverter uses plastic parts. Handle it gently to protect it from damage. Also, hold the unit with even strength and do not apply too much strength to the front cover alone. 2) Install the inverter in a place where it is immune to vibration. (5.9 m/s2 or less) Also note the cart, press, etc. 3) Note on ambient temperature The life of the inverter is under great influence of ambient temperature.
INSTALLATION AND WIRING 8) For installation in an enclosure Ventilation fan Inverter Inverter Inverter Inverter Inverter Inverter Built-in cooling fan (Correct example) (Correct example) (Incorrect example) Position of Ventilation Fan (Incorrect example) Accommodation of two or more inverters 9) Vertical mounting 2 (1) Wiring cover and handling (22K or less) 1) When cable conduits are not connected Cut the protective bushes of the wiring cover with nippers or a cutter before running the cables.
INSTALLATION AND WIRING 2.2 Wiring 2.2.1 Terminal connection diagram NFB Motor U R PU connector S -phase AC power supply T V IM W Earth (Ground) R1 Jumper S1 24VDC power output and external transistor common (Contact input common for source logic) P1 PC Forward rotation start STF Reverse rotation start STR Start self-holding selection Jumper Remove this jumper when using FR-BEL. P/ + R (Note) PX (Note) PR Jumper Remove this jumper when using FR-ABR.
INSTALLATION AND WIRING (1) Description of main circuit terminals Symbol Terminal Name Description Connect to the commercial power supply. Keep these terminals open when using the high power factor converter (FR-HC) and power regeneration common converter (FR-CV). R, S, T AC power input U, V, W Inverter output Connect a three-phase squirrel-cage motor. R1, S1 Power supply for control circuit Connected to the AC power supply terminals R and S.
INSTALLATION AND WIRING Type Symbol Terminal Name 10E By entering 0 to 5VDC (0 to 10VDC), the maximum output frequency is reached at 5V (or 10V) and I/O are proportional. Switch between input 0 to 5VDC (factory setting) and 0 to 10VDC from the operation panel. Input resistance 10kΩ. Maximum permissible voltage 20V. 4 Frequency setting (current) By entering 4 to 20mADC, the maximum output frequency is reached at 20mA and I/O are proportional. This input signal is valid only when the AU signal is on.
INSTALLATION AND WIRING 2.2.2 Wiring of the main circuit (1) Wiring instructions 1) Crimping terminals with insulation sleeves are recommended for use with the power and motor cables. 2) Cut the protective bushes of the wiring cover when running the cables. (22K or less) 3) Power must not be applied to the output terminals (U, V, W) of the inverter. Otherwise the inverter will be damaged. 4) After wiring, wire off-cuts must not be left in the inverter.
INSTALLATION AND WIRING 9) Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF option) in the output side of the inverter. This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are installed, immediately remove them. (If the FR-BIF radio noise filter is connected, switching power off during motor operation may result in E.UVT.
INSTALLATION AND WIRING (2) Terminal block layout In the main circuit of the inverter, the terminals are arranged as shown below: 1) 200V class FR-A520-0.4K, 0.75K FR-A520-15K, 18.5K, 22K R S T U V W R1 S1 N/– P1 P/+ Screw size (M4) PR PX Charge lamp R1 S1 R S P1 P/+ Screw size (M4) Charge lamp Jumper Screw size (M4) R S T U V W N/– Screw size 15K (M6) 18.5K,22K (M8) Jumper Screw size (M6) FR-A520-1.5K, 2.2K, 3.
INSTALLATION AND WIRING 2) 400V class FR-A540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K R S R1 S1 U T V W P1 N/– P/+ FR-A540-30K PR R1 S1 R S Charge lamp Screw size (M4) PX Screw size (M4) R Charge lamp S T U V N/– P1 P/+ W Screw size (M6) Jumper Screw size (M4) Jumper Screw size (M6) FR-A540-5.5K, 7.
INSTALLATION AND WIRING (3) Cables, crimping terminals, etc. The following table lists the cables and crimping terminals used with the inputs (R, S, T) and outputs (U, V, W) of the inverter and the torques for tightening the screws: • FR-A520-0.4K to 55K Applicable Inverter Type FR-A520-0.4K to 2.2K FR-A520-3.7K FR-A520-5.5K FR-A520-7.5K FR-A520-11K FR-A520-15K FR-A520-18.
INSTALLATION AND WIRING (5) Connecting the control circuit to a power supply separately from the main circuit If the magnetic contactor (MC) on the inverter power supply side is opened when the protective circuit is operated, the inverter control circuit power is lost and the alarm output signal cannot be kept on. To keep the alarm signal, terminals R1 and S1 are available. In this case, connect the power supply terminals R1 and S1 of the control circuit to the primary side of the MC. • Model FR-A520-0.
INSTALLATION AND WIRING 2.2.3 Wiring of the control circuit (1) Wiring instructions 1) Terminals SD, SE and 5 are common to the I/O signals and isolated from each other. Do not earth (ground) these terminals. Avoid connecting the terminals SD and 5 and the terminals SE and 5. 2) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).
INSTALLATION AND WIRING (3) Changing the control logic The input signals are set to sink logic. To change the control logic, the jumper connector on the back of the control circuit terminal block must be moved to the other position. (The output signals may be used in either the sink or source logic independently of the jumper connector position.) 1) Loosen the two mounting screws in both ends of the control circuit terminal block. (The screws cannot be removed.
INSTALLATION AND WIRING 4) Sink logic type • The sink logic type is a logic where a signal turns on when a current flows out of the corresponding signal input terminal. Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals. Inverter AX40 R Current STF RUN 1 R R R STR SE SD 9 24VDC • When using an external power supply for transistor output, use terminal PC as a common to prevent misoperation caused by undesirable current.
INSTALLATION AND WIRING 5) Source logic type • The Source logic type is a logic where a signal switches on when a current flows into the corresponding signal input terminal. Terminal PC is common to the contact input signals. Terminal SE is common to the open collector output signals. PC Current Inverter AX80 RUN 1 STF R R SE R STR 24VDC 9 R • When using an external power supply for transistor output, use terminal SD as a common to prevent misoperation caused by undesirable current.
INSTALLATION AND WIRING 2.2.4 (1) Connection to the PU connector When connecting the operation panel or parameter unit using a connection cable • Parameter unit connection cable (FR-CB2 ) (option) or the following connector and cable. • Connector: RJ45 connector Example: 5-554720-3, Tyco Electronics Corporation • Cable: Cable conforming to EIA568 (e.g. 10BASE-T cable) Example: SGLPEV-T 0.5mm×4P (Twisted pair cable, 4 pairs), MITSUBISHI CABLE INDUSTRIES, LTD. Note: 1.
INSTALLATION AND WIRING 1) Connection of a computer to the inverter (1:1 connection) Station 0 Inverter Computer RS-232C connector RS-485 connector RS-485 interface/ terminal Station 0 Inverter Computer RS-232C cable RS-232C converter Max.
INSTALLATION AND WIRING 1) Wiring of one RS-485 computer and one inverter Cable connection and signal direction Computer Side Terminals Inverter Signal name Description RDA Receive data SDA RDB Receive data SDB SDA Send data RDA SDB Send data RDB RSA Request to send RSB Request to send CSA Clear to send CSB Clear to send SG Signal ground FG Frame ground PU connector 10BASE-T Cable (Note 1) 0.
INSTALLATION AND WIRING 2.2.5 Connection of stand-alone option units The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual. (1) Connection of the dedicated external brake resistor (FR-ABR) The built-in brake resistor is connected across terminals P and PR.
INSTALLATION AND WIRING (2) Connection of the brake unit (FR-BU) Connect the optional FR-BU brake unit as shown below to improve the braking capability during deceleration. T (Note 4) ON MC U Motor S V IM T W R ower upply Inverter PR Remove jumper. PX P/+ N/– MC OFF MC PR PR P/+ N/- P HA HB TH1 Normal : TH1 - TH2....close Alarm : TH1 - TH2....open HC THS TH2 Brake unit FR-BU-(H) Resistor unit FR-BR-(H) Note: 1.
INSTALLATION AND WIRING (3) Connection of the brake unit (BU type) Connect the BU type brake unit correctly as shown below. Incorrect connection will damage the inverter. Remove jumpers across terminals HB-PC and TB-HC, then fit a jumper across terminals PC-TB. NFB Inverter MC Power supply Remove jumpers. T(Note4) Motor U R S V T W IM PR PX P/+ N/- MC ON Discharge resistor OFF Connect a jumper. Remove jumpers. MC PC HA HB HC P TB N PR OCR OCR BU type brake unit Note: 1.
INSTALLATION AND WIRING Note: 1. Remove the jumpers across the R-R1 and S-S1 terminals of the inverter, and connect the control 2. 3. 4. 5. circuit power supply across the R1-S1 terminals. The power input terminals R, S, T must be open. Incorrect connection will damage the inverter. Opposite polarity of terminals N, P will damage the inverter. The voltage phases of terminals R, S, T and terminals R4, S4, T4 must be matched before connection. Use Pr. 180 to Pr.
INSTALLATION AND WIRING (6) Connection of the power regeneration converter (FR-RC) (For power coordination, always install the power factor improving reactor (FR-BAL).) When connecting the FR-RC type power regeneration converter, connect the inverter terminals (P/+, N/-) and FR-RC type power regeneration converter terminals as shown below so that their signals match with each other. After making sure that the wiring is correct, set "0" in Pr. 30 "regenerative function selection".
INSTALLATION AND WIRING 2.2.6 Design information 1) When performing commercial power supply-inverter switch-over operation, securely provide electrical and mechanical interlocks for MC1 and MC2 used for commercial power supply-inverter switch-over. When there is a commercial power supply-inverter switch-over circuit as shown below, the inverter will be damaged by leakage current from the power supply due to arcs generated at the time of switch-over or chattering caused by a sequence error.
INSTALLATION AND WIRING 2.3 Other wiring 2.3.1 Power harmonics Power harmonics may be generated from the converter section of the inverter, affecting power supply equipment, power capacitors, etc. Power harmonics are different in generation source, frequency and transmission path from radio frequency (RF) noise and leakage currents. Take the following measures.
INSTALLATION AND WIRING 2.3.2 Harmonic suppression guidelines Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic suppression guidelines were established to protect other consumers from these outgoing harmonic currents.
INSTALLATION AND WIRING Table 3 Equivalent Capacity Limits Received Power Voltage Reference Capacity 6.6kV 50kVA 22/33kV 300kVA 66kV or more 2000kVA Table 4 Harmonic Content (Values at the fundamental current of 100%) 5th 7th 11th 13th 17th 19th 23rd 25th Not used Reactor 65 41 8.5 7.7 4.3 3.1 2.6 1.8 Used (AC side) 38 14.5 7.4 3.4 3.2 1.9 1.7 1.3 Used (DC side) 30 13 8.4 5.0 4.7 3.2 3.0 2.2 Used (AC, DC sides) 28 9.1 7.2 4.1 3.2 2.4 1.6 1.
INSTALLATION AND WIRING 3) Harmonic suppression technique requirement If the outgoing harmonic current is higher than the maximum value per 1kW (contract power) × contract power, a harmonic suppression technique is required. 4) Harmonic suppression techniques No. Item Description 1 Reactor installation (ACL, DCL) Install a reactor (ACL) in the AC side of the inverter or a reactor (DCL) in its DC side or both to suppress outgoing harmonic currents.
INSTALLATION AND WIRING 2.3.3 Inverter-generated noises and their reduction techniques Some noises enter the inverter to malfunction it and others are radiated by the inverter to malfunction peripheral devices. Though the inverter is designed to be insusceptible to noise, it handles low-level signals, so it requires the following basic measures to be taken. Also, since the inverters chops outputs at high carrier frequency, that could generate noise.
INSTALLATION AND WIRING Noise Path Measures 1) 2) 3) When devices that handle low-level signals and are liable to malfunction due to noises, e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when their signal cables are run near the inverter, the devices may be malfunctioned by air-propagated noises. The following measures must be taken: (1) Install easily affected devices as far away as possible from the inverter.
INSTALLATION AND WIRING • Data line filter Noise entry can be prevented by providing a data line filter for the detector cable etc. • Data examples By decreasing the carrier frequency, the noise terminal voltage* can be reduced. Use Pr. 72 to set the carrier frequency to a low value (1kHz). Though motor noise increases at a low carrier frequency, selection of Soft-PWM in Pr. 240 will make it unoffending.
INSTALLATION AND WIRING 2.3.4 Leakage currents and countermeasures Leakage currents flow through static capacitances existing in the inverter I/O wiring and motor. Since their values depend on the static capacitances, carrier frequency, etc., take the following measures. (1) To-earth (ground) leakage currents Leakage currents may flow not only into the inverter's own line but also into the other line through the earth (ground) cable, etc.
INSTALLATION AND WIRING 2.3.5 Inverter-driven 400V class motor In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially for a 400V class motor, the surge voltage may deteriorate the insulation. When the 400V class motor is driven by the inverter, consider the following measures.
INSTALLATION AND WIRING 2.3.6 Peripheral devices (1) Selection of peripheral devices Check the capacity of the motor to be used with the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
INSTALLATION AND WIRING (2) Selection of the rated sensitivity current for the earth (ground) leakage circuit breaker When using the earth (ground) leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows, independent of the carrier frequency setting: • Breaker for harmonic and surge: Rated sensitivity current: l∆n ≥ 10 × (lg1 + lgn + lg2 + lgm) • Standard breakers: Rated sensitivity current: l∆n ≥ 10 × {lg1 + lgn + 3 ( (lg2+lgm)} Example of leakage current per 1
INSTALLATION AND WIRING (3) Power-off and magnetic contactor (MC) On the inverter primary side, it is recommended to provide an MC for the following purposes (Refer to page 46 for selection.): 1)To release the inverter from the power supply when the inverter protective function is activated or the drive becomes faulty (e.g. emergency stop operation).
INSTALLATION AND WIRING 2.3.7 Instructions for compliance with U.S. and Canadian Electrical Codes (Standard to comply with: UL 508C) (1) Installation The FR-A500 is UL-listed as a product for use in an enclosure. Design an enclosure so that the ambient temperature, humidity and ambience of the inverter will satisfy the specifications. (Refer to page 223.
INSTALLATION AND WIRING 2.3.8 Instructions for compliance with the European Directives (The products conforming to the Low Voltage Directive carry the CE mark.) (1) EMC Directive 1) Our view of transistorized inverters for the EMC Directive A transistorized inverter is a component designed for installation in a control box and for use with the other equipment to control the equipment/device. Therefore, we understand that the EMC Directive does not apply directly to transistorized inverters.
INSTALLATION AND WIRING (2) Low Voltage Directive 1) Our view of transistorized inverters for the Low Voltage Directive Transistorized inverters are covered by the Low Voltage Directive (compliant with Standard DIN VDE0160). 2) Compliance We have self-declared our inverters as products compliant to the Low Voltage Directive and place the CE mark on the inverters. 3) Excerpts from instructions * In the 400V class inverters, the rated input voltage range is three-phase, 380V to 415V, 50Hz/60Hz.
CHAPTER 3 OPERATION/CONTROL Chapter 1 This chapter explains the basic "operation/control" for use of this product. Always read the instructions and other information before using the equipment. 3.1 Pre-Operation Information ..................................... 50 3.2 Operation Panel .................................................... 53 3.3 Operation...............................................................
OPERATION/CONTROL 3.1 Pre-Operation Information 3.1.1 Devices and parts to be prepared for operation The inverter can be operated in any of the "external operation mode", "PU operation mode", "combined operation mode" and "communication operation mode". Prepare required instruments and parts according to the operation mode. (1) External operation mode (factory setting) The inverter is operated under the control of external operation signals (frequency setting potentiometer, start switch, etc.
OPERATION/CONTROL Preparation • Start signal.................................. Switch, relay, etc. (for 1) • Frequency setting signal............. 0 to 5V, 0 to 10V or 4 to 20mA DC signals from a potentiometer or outside the inverter (for 2) • Operation unit ............................. Operation panel (FR-DU04), parameter unit (FR-PU04) • Connection cable........................
OPERATION/CONTROL 3.1.2 Power on Before switching power on, check the following. Installation check Make sure that the inverter is installed correctly in a proper location. (Refer to page 10.) •Wiring check Make sure that the main and control circuits are wired correctly. Make sure that the options and peripheral devices are selected and connected correctly. (Refer to page 12.) Switch power on.
OPERATION/CONTROL 3.2 Operation Panel With the operation panel (FR-DU04), you can set the running frequency, monitor the operation command display, set parameters, display an error, and copy parameters. 3.2.
OPERATION/CONTROL 3.2.
OPERATION/CONTROL 3.2.5 Parameter setting method • A parameter value may either be set by updating its parameter number or setting the value digit-by-digit using the key. • To write the setting, change it and press the SET key 1.5s. Example: To change the Pr. 79 "operation mode selection" setting from "2" (external operation mode) to "1" (PU operation mode) (For details of Pr. 79, refer to page 113.) Press the MODE key, to choose the parameter setting mode.
OPERATION/CONTROL 3.2.6 Operation mode zExternal operation FR-DU04 zPU operation FR-DU04 CONTROL PANEL zPU jog operation CONTROL PANEL Hz A V MON EXT PU REV FWD FR-DU04 CONTROL PANEL Hz A V MON MODE EXT PU REV FWD Hz A V MON EXT PU REV FWD MODE MODE To 3.2.7 Help mode Note: If the operation mode cannot be changed, refer to page 205. 3.2.7 Help mode zAlarm history zAlarm history clear zParameter clear Four past alarms can be displayed with the key.
OPERATION/CONTROL (2) Alarm history clear Clears all alarm history. Flicker FR-DU04 Hz A V MON FR-DU04 CONTROL PANEL EXT PU REV FWD FR-DU04 CONTROL PANEL SET MON SET EXT PU REV FWD Hz A V MON FR-DU04 CONTROL PANEL Hz A V EXT PU REV FWD CONTROL PANEL Hz A V SET MON EXT PU REV FWD Cancel (3) Parameter clear Initialises the parameter values to the factory settings. The calibration values are not initialized. (Parameter values are not cleared by setting "1" in Pr.
OPERATION/CONTROL 3.2.8 Copy mode By using the operation panel (FR-DU04), the parameter values can be copied to another inverter (only the FR-A500 series). 1) Operation procedure After reading the parameter values from the copy source inverter, connect the operation panel to the copy destination inverter, and write the parameter values. After writing the parameters to the inverter of copy destination, always reset the inverter, e.g. switch power off once, before starting operation.
OPERATION/CONTROL 3.3 Operation 3.3.1 Pre-operation checks Before starting operation, check the following: • Safety Perform test operation after making sure that safety is ensured if the machine should become out of control. • Machine Make sure that the machine is free of damage. • Parameters Set the parameter values to match the operating machine system environment. • Test operation Perform test operation and make sure that the machine operates safely under light load at a low frequency.
OPERATION/CONTROL 3.3.2 External operation mode (Operation using external input signals) (1) Operation at 60Hz Frequency setting by voltage input requency setting potentiometer 0 to 10VDC Frequency setting by current input STF STR STF STR SD SD 10 Inverter 2 5 AU * Current input 4 to 20mADC 4 5 Inverter *Short terminals AU-SD for current input. For details of each terminal, refer to page 13 .
OPERATION/CONTROL 3.3.3 PU operation mode (Operation using the operation panel (FR-DU04)) (1) Operation at 60Hz While the motor is running, repeat the following steps 2 and 3 to vary the speed: Step 1 Description Power-on → Operation mode check Switch power on and make sure that the operation command indication "PU" is lit. (If it is not lit, press the MODE key to choose the operation mode and press the key to switch to PU operation.
OPERATION/CONTROL 3.3.4 Combined operation mode (Operation using the external input signals and PU) When entering the start signal from outside the inverter (switch, relay, etc,) and setting the running frequency from the PU (Pr. 79 = 3) The external frequency setting signals and the PU's FWD, REV and STOP keys are not accepted. (Note) Step Description Image Power-on Switch power on. ON 1 2 Operation mode selection Set "3" in Pr. 79 "operation mode selection".
CHAPTER 4 PARAMETERS Chapter 1 This chapter explains the "parameters" for use of this product. The inverter is designed to perform simple variable-speed operation with the factory settings of the parameters. Set the necessary parameters according to the load and operation specifications. Always read the instructions before using the equipment. Chapter 2 Chapter 3 4.1 Parameter Lists .....................................................64 4.2 Parameter Function Details ...................................
PARAMETERS 4.1.1 Function Parameter lists Parameter Number Standard operation functions Basic functions 0 Output terminal functions Palameter List 4.1 Parameter Lists Name Torque boost (Note 1) Setting Range Minimum Setting Increments Factory Setting Refer To Page: 0 to 30% 0.1% 6%/4%/3%/2% (Note 9) 73 1 Maximum frequency 0 to 120Hz 0.01Hz 120Hz 74 2 Minimum frequency 0 to 120Hz 0.01Hz 0Hz 74 3 Base frequency 0 to 400Hz 0.
PARAMETERS Operation selection functions Additional function Automatic restart functions Display functions Parameter Number Name Setting Range Minimum Setting Increments Factory Setting Refer To Page: 0 to 3600 s/ 0 to 360 s 0.1 s/0.01 s 5s 77 0 to 3600 s/0 to 360 s, 9999 0.1 s/0.01 s 9999 77 0 to 30%, 9999 0.1% 9999 73 0 to 400Hz, 9999 0.
PARAMETERS Advanced magnetic flux vectorcontrol 5-point flexible V/F characteristics 5-point flexible V/F characteristics Third functions Communication functions PID control Palameter List Function Parameter Number Name 80 Motor capacity 81 Number of motor poles 82 Setting Range Minimum Setting Increments Factory Setting Refer To Page: 0.4 to 55kW, 9999 0.
PARAMETERS Factory Setting Refer To Page: 0, 1 1 0 148 MC switch-over interlock time 0 to 100.0 s 0.1 s 1.0 s 148 Start waiting time 0 to 100.0 s 0.1 s 0.5 s 148 0, 1 1 0 148 Automatic inverter-commercial power supply switch-over frequency 0 to 60.00Hz, 9999 0.01Hz 9999 148 140 Backlash acceleration stopping frequency (Note 7) 0 to 400Hz 0.01Hz 1.00Hz 86 141 Backlash acceleration stopping time (Note 7) 0 to 360 s 0.1 s 0.
PARAMETERS Terminal assignment functions Additional function Programmed operation Multi-speed operation Sub functions Stop selection functions Additional function Palameter List Function Parameter Number Name Setting Range Minimum Setting Increments Factory Setting Refer To Page: 159 180 RL terminal function selection 0 to 99, 9999 1 0 181 RM terminal function selection 0 to 99, 9999 1 1 159 182 RH terminal function selection 0 to 99, 9999 1 2 159 183 RT terminal function selecti
Parameter Number 261 Power failure stop selection 262 Subtracted frequency at deceleration start Minimum Setting Increments Factory Setting Refer To Page: 0, 1 1 0 172 0 to 20Hz 0.01Hz 3Hz 172 Subtraction starting frequency 0 to 120Hz, 9999 0.01Hz 60Hz 172 Power-failure deceleration time 1 0 to 3600/0 to 360 s 0.1 s/0.01 s 5s 172 265 Power-failure deceleration time 2 0 to 3600/0 to 360 s, 9999 0.1 s/0.
PARAMETERS Note: 1. Indicates the parameter settings which are ignored when the advanced magnetic flux vector control mode is selected. 2. The factory setting of the FR-A540 (400V class) is 400V. 3. Can be set when Pr. 80, Pr. 81 ≠ 9999, Pr. 60 = 7 or 8. 4. Can be accessed when Pr. 80, Pr. 81 ≠ 9999, Pr. 77 = 801. 5. Can be accessed when Pr. 270 = 1 or 3, Pr. 80, Pr. 81 ≠ 9999. 6. The setting depends on the inverter capacity. 7. Can be accessed when Pr. 29 = 3. 8.
PARAMETERS 4.1.2 List of parameters classified by purpose of use Set the parameters according to the operating conditions. The following list indicates purpose of use and corresponding parameters. Parameter Numbers Others Related to incorrect operation prevention Related to monitoring Related to application operation Related to operation Purpose of Use Parameter numbers which must be set Adjustment of acceleration/deceleration time and pattern Pr. 7, Pr. 8, Pr. 20, Pr.
PARAMETERS 4.1.3 Parameters recommended to be set by the user We recommend the following parameters to be set by the user. Set them according to the operation specifications, load, etc.
PARAMETERS 4.2 Parameter Function Details 4.2.1 Torque boost (Pr. 0, Pr. 46, Pr. 112) Related parameters Pr. 0 "torque boost" Pr. 3 "base frequency" Pr. 19 "base frequency voltage" Pr. 71 "applied motor" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 180 to Pr. 186 (input terminal function selection) Pr. 46 "second torque boost" Pr. 112 "third torque boost" You can compensate for a voltage drop in the low frequency range to improve motor torque reduction in the low speed range.
PARAMETERS 4.2.2 Output frequency range (Pr. 1, Pr. 2, Pr. 18) Related parameters Pr. 1 "maximum frequency" Pr. 13 "starting frequency" Pr. 903 "frequency setting voltage gain" Pr. 905 "frequency setting current gain" Pr. 2 "minimum frequency" Pr. 18 "high-speed maximum frequency" Used to clamp the upper and lower limits of the output frequency. Used for high-speed operation at or over 120Hz. z Can be used to set the upper and lower limits of motor speed.
PARAMETERS 4.2.3 Base frequency, base frequency voltage (Pr. 3, Pr. 19, Pr. 47, Pr. 113) Related parameters Pr. 14 "load pattern selection" Pr. 71 "applied motor" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 83 "rated motor voltage" Pr. 84 "rated motor frequency" Pr. 180 to Pr. 186 (input terminal function selection) Pr. 3 "base frequency" Pr. 19 "base frequency voltage" Pr. 47 "second V/F (base frequency) Pr.
PARAMETERS 4.2.4 Multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239) Related parameters Pr. 4 "multi-speed setting (high speed)" Pr. 1 "maximum frequency" Pr. 2 "minimum frequency" Pr. 15 "jog frequency" Pr. 28 "multi-speed input compensation" Pr. 29 "acceleration/deceleration pattern" Pr. 79 "operation mode selection" Pr. 180 to Pr. 186 (input terminal function selection) Pr. 5 "multi -speed setting (middle speed)" Pr. 6 "multi -speed setting (low speed)" Pr. 24 to Pr.
PARAMETERS 4.2.5 Acceleration/deceleration time (Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 110, Pr. 111) Related parameters Pr. 7 "acceleration time" Pr. 3 "base frequency" Pr. 8 "deceleration time" Pr. 29 "acceleration/deceleration pattern" Pr. 20 "acceleration/deceleration reference Pr. 180 to Pr. 186 (input terminal frequency" function selection) Pr. 21 "acceleration/deceleration time increments" Pr. 44 "second acceleration/deceleration time" Pr. 45 "second deceleration time" Pr.
PARAMETERS Note: 1. In S-shaped acceleration/deceleration pattern A (refer to page 86), the set time is a period required to reach the base frequency set in Pr. 3. • Acceleration/deceleration time calculation expression when the set frequency is the base frequency or higher t= 4 9 × T (Pr.
PARAMETERS 4.2.7 DC injection brake (Pr. 10 to Pr. 12) Related parameters Pr. 13 "starting frequency" Pr. 71 "applied motor" Pr. 10 "DC injection brake operation frequency" Pr. 11 "DC injection brake operation time" Pr. 12 "DC injection brake voltage" 12 Parameter Number Factory Setting Setting Range Remarks 10 3Hz 0 to 120Hz, 9999 9999: Operated at or below Pr. 13 value. 11 0.5 s 0 to 10 s, 8888 7.
PARAMETERS 4.2.8 Starting frequency (Pr. 13) Related parameters Pr. 2 "minimum frequency" Pr. 13 "starting frequency" You can set the starting frequency between 0 and 60Hz. zSet the starting frequency at which the start signal is switched on. Parameter Factory Setting Setting Range 13 0.5Hz 0 to 60Hz utput frequency (Hz) Setting range 60 Pr.
PARAMETERS 4.2.9 Load pattern selection (Pr. 14) Pr. 14 "load pattern selection" Related parameters Pr. 0 "torque boost" Pr. 60 "intelligent mode selection" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 180 to Pr. 186 (input terminal function selection) You can select the optimum output characteristic (V/F characteristic) for the application and load characteristics. z The output voltage is automatically set by intelligent mode when "4" (energy-saving mode) is set in Pr.
PARAMETERS 4.2.10 Jog operation (Pr. 15, Pr. 16) Related parameters Pr. 15 "jog frequency" Pr. 16 "jog acceleration/deceleration time" Pr. 20 "acceleration/deceleration reference frequency" Pr. 21 "acceleration/deceleration time increments" Pr. 79 "operation mode selection" Pr. 180 to Pr.
PARAMETERS 4.2.11 MRS input selection (Pr. 17) Pr. 17 "MRS input selection" Used to select the logic of the MRS signal. When the MRS signal switches on, the inverter shuts off the output. Parameter Number Factory Setting Setting Range 17 0 0, 2 Pr. 17 Setting Specifications of MRS Signal 0 Normally open input 2 Normally closed input (N/C contact input specifications) • For sink logic Setting 0 (Factory setting) Setting 2 Inverter Inverter Output stop Pr.
PARAMETERS 4.2.12 Stall prevention (Pr. 22, Pr. 23, Pr. 66, Pr. 148, Pr. 149, Pr. 154) Related parameters Pr. 22 "stall prevention operation level" Pr. 48 "second stall prevention operation current" Pr. 49 "second stall prevention operation frequency" Pr. 73 "0-5V/0-10V selection" Pr. 114 "third stall prevention operation current" Pr. 115 "third stall prevention operation frequency" Pr. 156 "stall prevention operation selection" Pr.
PARAMETERS • In Pr. 22, set the stall prevention operation level. Normally set it to 150% (factory setting). Set "0" in Pr. 22 to disable the stall prevention operation. • To reduce the stall prevention operation level in the high-frequency range, set the reduction starting frequency in Pr. 66 and the reduction ratio compensation factor in Pr. 23. Calculation expression for stall prevention operation level Pr.22-A Pr.23-100 Stall prevention operation level (%) = A + B × [ ] ×[ ] 100 Pr.22-B Pr.
PARAMETERS 4.2.14 Acceleration/deceleration pattern (Pr. 29, Pr. 140 to Pr. 143) Related parameters Pr. 29 "acceleration/deceleration pattern" Pr. 3 "base frequency" Pr. 7 "acceleration time" Pr. 8 "deceleration time" Pr. 20 "acceleration/deceleration reference frequency" Pr. 44 "second acceleration/ deceleration time" Pr. 45 "second deceleration time" Pr. 110 "third acceleration/ deceleration time" Pr. 111 "third deceleration time" Pr. 140 "backlash acceleration stopping frequency" Pr.
PARAMETERS 4.2.15 Regenerative brake duty (Pr. 30, Pr. 70) Related parameters Pr. 30 "regenerative function selection" Pr. 180 to Pr. 186 (Input terminal function selection) Pr. 70 "special regenerative brake duty" z When making frequent starts/stops with a 7.5K or less inverter, use the optional "high-duty brake resistor" (FR-ABR) to increase the regenerative brake duty.
PARAMETERS Note: 1. The Pr. 70 setting is invalid for the inverter of 11K or more. 2. Pr. 70 "regenerative brake duty" indicates the %ED of the built-in brake transistor operation. Its setting should not be higher than the setting of the brake resistor used. Otherwise, the brake resistor can overheat. 3. The X10 signal may be replaced by the MRS signal. 4. When terminal assignment is changed using Pr. 180 to Pr. 186, the other functions may be affected.
PARAMETERS 4.2.17 Speed display (Pr. 37, Pr. 144) Related parameters Pr. 37 "speed display" Pr. 52 "DU/PU main display data selection" Pr. 53 "PU level display data selection" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr.
PARAMETERS 4.2.18 Up-to-frequency sensitivity (Pr. 41) Related parameters Pr. 41 "up-to-frequency sensitivity" Pr. 190 to Pr. 195 (output terminal function selection) The ON range of the up-to-frequency signal (SU) output when the output frequency reaches the running frequency can be adjusted between 0 and ±100% of the running frequency. This parameter can be used to confirm that the running frequency has been reached or used as the operation start signal etc. for related equipment.
PARAMETERS Output frequency (Hz) Refer to the figure below and set the corresponding parameters: • When Pr. 43 ≠ 9999, the Pr. 42 setting applies to forward rotation and the Pr. 43 setting applies to reverse rotation. Pr.42 Forward rotation Pr.50 Pr.116 Time Pr.43 Reverse rotation Pr.50 Pr.116 Output signal OFF FU,FU2,FU3 ON OFF ON OFF Output Signal Parameter Number Output Signal 42 FU 43 50 FU2 116 FU3 Use Pr. 190 to Pr.
PARAMETERS • Set the stall prevention operation level in Pr. 48 and Pr. 114. • Refer to the following list to set values in Pr. 49 and Pr. 115. • Pr. 114 and Pr. 115 are made valid by switching on the X9 signal. Set "9" in any of Pr. 180 to Pr. 186 to allocate the terminal used to input the X9 signal. Pr. 49 Setting Pr. 115 Setting 0 0.01Hz to 400Hz 9999 Operation Second (third) stall prevention function is not activated.
PARAMETERS Set Pr. 52 to Pr. 54 and Pr. 158 in accordance with the following table: Signal Type Parameter Setting Pr.53 Pr.54 Pr.52 Display Unit Pr.158 Full-Scale Value of FM, AM, Level Meter No display Output frequency Output current Output voltage Alarm display Frequency setting Hz A V Hz × 0/100 0/100 0/100 0/100 5 PU main monitor × 0/100 0/100 0/100 0/100 * Running speed r/min 6 * 6 6 6 % V % 7 8 9 * * * 7 8 9 7 8 9 7 8 9 Pr. 55 Pr. 56 400V or 800V Pr. 55 Pr.
PARAMETERS Note: 1. The monitoring of items marked cannot be selected. 2. By setting "0" in Pr. 52, the monitoring of "output frequency to alarm display" can be selected in sequence by the SET key. 3. *"Frequency setting to output terminal status" on the PU main monitor are selected by "other monitor selection" of the parameter unit (FR-PU04). 4. **The load meter is displayed in %, with the current set in Pr. 56 regarded as 100%. 5.
PARAMETERS 4.2.22 Monitoring reference (Pr. 55, Pr. 56) Related parameters Pr. 55 "frequency monitoring reference" Pr. 37 "speed display" Pr. 53 "PU level display data selection" Pr. 54 "FM terminal function selection" Pr. 158 "AM terminal function selection" Pr. 900 "FM terminal calibration" Pr. 901 "AM terminal calibration" Pr.
PARAMETERS 4.2.23 Automatic restart after instantaneous power failure (Pr. 57, Pr. 58, Pr. 162, Pr. 165, Pr. 611) Pr. 57 "restart coasting time" Pr. 58 "restart cushion time" Pr. 162 "automatic restart after instantaneous power failure selection" Pr. 163 "first cushion time for restart" Pr. 164 "first cushion voltage for restart" Pr. 165 "restart stall prevention operation level" Pr.
PARAMETERS Refer to the above figures and following table, and set the parameters: Parameter Number Setting 0 Frequency search made Frequency search is made after detection of an instantaneous power failure. 1 No frequency search Independently of the motor coasting speed, the output voltage is gradually increased with the frequency kept as preset. 162 0 0.4K to 1.5K 0.5 s coasting time 2.2K to 7.5K 1.0 s coasting time 11K or more 3.0 s coasting time 57 0.
PARAMETERS 4.2.24 Remote setting function selection (Pr. 59) Related parameters Pr. 1 "maximum frequency" Pr. 7 "acceleration time" Pr. 8 "deceleration time" Pr. 18 "high-speed maximum frequency" Pr. 28 "multi-speed input compensation" Pr. 44 "second acceleration/deceleration time" Pr. 45 "second deceleration time" Pr.
PARAMETERS Note: 1. The frequency can be varied by RH (acceleration) and RM (deceleration) between 0 and the maximum frequency (Pr. 1 or Pr. 18 setting). 2. When the acceleration or deceleration signal switches on, the set frequency varies according to the slope set in Pr. 44 or Pr. 45. The output frequency acceleration/deceleration times are as set in Pr. 7 and Pr. 8, respectively. Therefore, the longer preset times are used to vary the actual output frequency. 3.
PARAMETERS 4.2.25 Intelligent mode selection (Pr. 60) Related parameters Pr. 0 "torque boost" Pr. 7 "acceleration time" Pr. 8 "deceleration time" Pr. 13 "starting frequency" Pr. 19 "base frequency voltage" Pr. 80, Pr. 81 (advanced magnetic flux vector control) Pr. 278 to Pr. 285 (brake sequence functions) Pr. 60 "intelligent mode selection" The inverter automatically sets appropriate parameters for operation.
PARAMETERS Note: 1. When more accurate control is required for your application, set the other parameters as appropriate. 2. Because of the learning system, this control is not valid at the first time in the optimum acceleration/deceleration mode. Also, this mode is only valid for frequency setting of 30.01Hz or more. 3. When the advanced magnetic flux vector control has been selected using Pr. 80 and Pr. 81, the settings of the energy-saving mode and elevator mode are ignored.
PARAMETERS 4.2.26 Acceleration/deceleration reference current (Pr. 61 to Pr. 64) Related parameters Pr. 61 "reference I for intelligent mode" Pr. 60 "intelligent mode selection" Pr. 62 "ref. I for intelligent mode accel." Pr. 63 "ref. I for intelligent mode decel." Pr. 64 "starting frequency for elevator mode" z Set these parameters to improve performance in the intelligent mode. z Pr. 61 to Pr. 64 are only valid when any of "1 to 6" is selected for Pr. 60.
PARAMETERS 4.2.27 Retry function (Pr. 65, Pr. 67 to Pr. 69) Pr. 65 "retry selection" Pr. 67 "number of retries at alarm occurrence" Pr. 68 "retry waiting time" Pr. 69 "retry count display erasure" When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart and continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries made, and waiting time.
PARAMETERS • Use Pr. 67 to set the number of retries at alarm occurrence. Pr. 67 Setting Number of Retries 0 Retry is not made. Alarm Signal Output 1 to 10 1 to 10 times Not output. 101 to 110 1 to 10 times Output • Use Pr. 68 to set the waiting time from when an inverter alarm occurs until a restart in the range 0 to 10s. • Reading the Pr. 69 value provides the cumulative number of successful restart times made by retry. The setting of "0" erases the cumulative number of times. Note: 1.
PARAMETERS 4.2.28 Applied motor (Pr. 71) Pr. 71 "applied motor" Related parameters Pr. 0 "torque boost" Pr. 12 "DC injection brake voltage" Pr. 19 "base frequency voltage" Pr. 60 "intelligent mode selection" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 96 "auto tuning setting/status" Pr. 100 to Pr. 109 (V/F frequency/voltage) Set the motor used.
PARAMETERS 4.2.29 PWM carrier frequency (Pr. 72, Pr. 240) Pr. 72 "PWM frequency selection" Pr. 240 "Soft-PWM setting" You can change the motor tone. • By parameter setting, you can set whether to exercise the Soft-PWM control that changes the motor tone or select with or without long wiring mode. • Soft-PWM control is a control system that changes the motor noise from a metallic tone into an unoffending tone. • Surge voltage is suppressed regardless of wiring length in the long wiring mode.
PARAMETERS 4.2.30 Voltage input (Pr. 73) Related parameters Pr. 73 "0-5V/0-10V selection" Pr. 22 "stall prevention operation level" Pr. 903 "frequency setting voltage gain" Pr. 905 "frequency setting current gain" You can select the analog input terminal specifications, the override function and the function to switch between forward and reverse rotation depending on the input signal polarity. Parameter Number Factory Setting Setting Range 73 1 0 to 5, 10 to 15 Pr.
PARAMETERS 4.2.31 Input filter time constant (Pr. 74) Pr. 74 "filter time constant" You can set the input section's internal filter constant for an external voltage or current frequency setting signal. z Effective for eliminating noise in the frequency setting circuit. z Increase the filter time constant if steady operation cannot be performed due to noise. A larger setting results in lower response. (The time constant can be set between approximately 1ms to 1s with the setting of 0 to 8.
PARAMETERS How to make a restart after a stop made by the external operation STOP RESET key from the PU during (1) Operation panel (FR-DU04) 1) After completion of deceleration to a stop, switch off the STF or STR signal. 2)Press the MODE key three times* to call the Note: When Pr. 79 = "3", press the MODE indication. (Note 8) key three times to display , then press the key and proceed to step 3). (*: For monitor screen) ....
PARAMETERS 4.2.33 Alarm code output selection (Pr. 76) Related parameters Pr. 76 "alarm code output selection" Pr. 79 "operation mode selection" Pr. 190 to Pr. 195 (output terminal function selection) Pr. 200 to Pr. 231 (programmed operation) When an alarm occurs, its code can be output as a 4-bit digital signal from the open collector output terminals. When programmed operation has been selected, this parameter also serves to output a group operation signal.
PARAMETERS 4.2.34 Parameter write disable selection (Pr. 77) Related parameters Pr. 77 "parameter write disable selection" Pr. 79 "operation mode selection" You can select between write-enable and disable for parameters. This function is used to prevent parameter values from being rewritten by accident. Parameter Number Factory Setting Setting Range 77 0 0, 1, 2 Pr. 77 Setting Function 0 Write enabled during a stop only.
PARAMETERS 4.2.35 Reverse rotation prevention selection (Pr. 78) Pr. 78 "reverse rotation prevention selection" Related parameters Pr. 79 "operation mode selection" This function can prevent any reverse rotation fault resulting from the misoperation of the start signal. z Used for a machine which runs only in one direction, e.g. fan, pump. (The setting of this function is valid for the PU, external and communication operations.
PARAMETERS 4.2.36 Operation mode selection (Pr. 79) Related parameters Pr. 15 "job frequency" Pr. 4 to Pr. 6, Pr. 24 to 27, Pr.232 to Pr.239 (multi-speed operation) Pr. 75 "reset selection/disconnected PU detection/PU stop selection." Pr. 76 "alarm code output selection" Pr. 180 to Pr.186 (input terminal function selection) Pr. 200 to Pr. 231 (programmed operation) Pr. 79 "operation mode selection" Used to select the operation mode of the inverter.
PARAMETERS (2) Switch-over mode You can select between PU operation, external operation and computer link operation (when FR-A5NR option is used). Operation Mode Switching Switching Operation/Operating Status External operation to PU operation 1) Select the PU operation mode with the operation panel or parameter unit. • Rotation direction is the same as that of external operation. • Set frequency is as set by the potentiometer (frequency setting potentiometer).
PARAMETERS Operating Condition Operation mode X12 (MRS) Signal Status During stop ON → OFF (Note 3) During operation ON → OFF (Note 3) During stop ON → OFF PU External During operation Operation Mode (Note 4) Externa Operating Status Parameter Write Switching to PU Operation Mode During stop Allowed → disallowed Disallowed If external operation frequency setting and start signal are entered, operation is performed in th
PARAMETERS 4.2.37 Motor capacity/number of motor poles/speed control gain (Pr. 80, Pr. 81, Pr. 89) Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 89 "speed control gain" You can set the advanced magnetic flux vector control. z Advanced magnetic flux vector control Provides large starting torque and sufficient low-speed torque. Effective for great load fluctuation. Related parameters Pr. 71 "applied motor" Pr. 83 "rated motor voltage" Pr. 84 "rated motor frequency" Pr.
PARAMETERS Note: 1. Speed fluctuation is slightly greater than in the V/F control. (Advanced magnetic flux vector control may not be suitable for machines which attach importance to little speed fluctuation at low speed, e.g. grinders, lapping machines.) 2. When the surge voltage suppression filter (FR-ASF-H) is used between the inverter and motor, output torque may reduce. 3. When the terminal functions are changed using Pr. 180 to Pr. 186, the other functions may be affected.
PARAMETERS When you use the advanced magnetic flux vector control, you can perform the offline auto tuning operation to calculate motor constants automatically. z Offline auto tuning is made valid only when values other than "9999" are set in Pr. 80 and Pr. 81 to select the advanced magnetic flux vector control. z The online tuning data (motor constants) can be copied to another inverter with the PU (FR-DU04/FRPU04). z If the motor used is not the Mitsubishi standard motor (SF-JR 0.
PARAMETERS • • • • • The motor is connected. The motor capacity is equal to or one rank lower than the inverter capacity. (0.4kW or more) The maximum frequency is 120Hz. Special motors such as high-slip motor and high-speed motor cannot be tuned. When "101" (offline auto tuning with motor running) is set in Pr. 96, note the following: 1) Torque may not be enough during tuning. 2) The motor may be run at nearly its rated frequency (Pr. 84 setting) without problem.
PARAMETERS Parameter details Parameter Number 9 Setting 0 to 500A 0 1 2 20 3 13 23 71 (Note1) 4 14 24 83 84 90 91 92 93 94 96 (Note2) 5 15 6 16 7 17 8 18 0 to 1000V 50 to 120HZ 0 to, 9999 0 to, 9999 0 to, 9999 0 to, 9999 9999 0 to 100% 0 1 101 Description Set the rated motor current (A).
PARAMETERS (3) Monitoring the offline tuning status When the parameter unit (FR-PU04) is used, the Pr. 96 value is displayed during tuning on the main monitor as shown below. When the operation panel (FR-DU04) is used, only the same numerical value as on the PU is displayed: • Parameter unit (FR-PU04) main monitor (For inverter trip) 1. Setting 2. Tuning in progress TUNE 1 STOP PU PU TUNE 3 COMPLETION STF STOP PU PU TUNE 103 COMPLETION STF STOP PU 2 STF FWD 3.
PARAMETERS 5) When tuning was ended focibly. A forced end occurs when tuning is forced to end by pressing the STOP RESET key or turning off the start signal (STF or STR) during tuning. In this case, offline auto tuning was not brought to a normal end. (The motor constants are not yet set.) Reset the inverter and restart tuning. Note: 1. The motor constants measured once in the offline auto tuning are stored as parameters and their data is held until the offline auto tuning is performed again. 2.
PARAMETERS Note: 1. Pr. 82 and Pr. 90 to Pr. 94 values may only be read when the Pr. 80 and Pr. 81 settings are other than "9999" (advanced magnetic flux vector control selected). 2. Set "9999" in Pr. 90 to Pr. 94 to use the standard motor constants (including those for the constant-torque motor). 3. Set "3" (standard motor), "13" (constant-torque motor) or "23" (Mitsubishi standard motor SF-JR 4P (1.5kW or less)) in Pr. 71 to use the constants measured in the offline auto tuning. Set "4, 14 or 24" in Pr.
PARAMETERS z To enter the Pr. 92 and Pr. 93 motor constants in [mH] 1. Set any of the following values in Pr. 71: •Standard motor ....................................................................................... Pr. 71 = "0" •Constant-torque motor ............................................................................ Pr. 71 = "1" •Mitsubishi standard motor SF-JR 4 poles (1.5kW or less) ...................... Pr. 71 = "20" 2. Set "801" in Pr. 77. (Only when the Pr.
PARAMETERS Setting method of the motor constants of the SF-HR type high efficiency motor and SFHRCA type inverter drive dedicated constant torque motor. • When offline auto tuning is enabled with motor running 1) Set Pr. 9 "electoronic thermal O/L relay", Pr. 80 "motor capacity", Pr. 81 "number of motor poles", Pr. 83 "rated motor voltage" and Pr. 84 "rated motor frequency" according to the motor. 2) Set "13" in Pr. 71. (offline auto tunning selection of constant torque motor) 3) Set "101" in Pr.
PARAMETERS Note: 1. 2. 3. 4. 5. Underlined parameter values are values changed from the factory settings. The motor constants indicate the data measured in the offline auto tuning. The Pr. 85 settings of "9999" (factory setting) and "10" are equal. Wrong setting will provide an alarm output. Therefore, make sure that the settings are correct. For the output is 0.2kW, set Pr. 80 "motor capacity " to 0.4 (kW).
PARAMETERS 4.2.39 Online auto tuning selection (Pr. 95) Related parameters Pr. 71 "applied motor" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 83 "rated motor voltage" Pr. 84 "rated motor frequency" Pr. 89 "speed control gain" Pr. 90 to Pr. 94 (motor constants) Pr. 96 "auto tuning setting/status" Pr. 95 "online auto tuning selection" By online auto tuning, the motor conditions are tuned rapidly at the start.
PARAMETERS Note: 1. If any of the inverter starting conditions are not satisfied, e.g. when MRS is input, if the set frequency is lower than the starting frequency (Pr. 13) value, or during an inverter error, the online auto tuning is not activated. 2. For a restart during deceleration or DC injection brake operation, the online auto tuning is not activated. 3. The online auto tuning is invalid for programmed operation or jog operation. 4.
PARAMETERS 4.2.40 V/F control frequency (voltage) (Pr. 100 to Pr. 109) Pr. 100 "V/F1 (first frequency)" Related parameters Pr. 19 "base frequency voltage" Pr. 47 "second V/F (base frequency)" Pr. 60 "intelligent mode selection" Pr. 71 "applied motor" Pr. 113 "third V/F (base frequency)" Pr. 101 "V/F1 (first frequency voltage)" Pr. 102 "V/F2 (second frequency)" Pr. 103 "V/F2 (second frequency voltage)" Pr. 104 "V/F3 (third frequency)" Pr. 105 "V/F3 (third frequency voltage)" Pr.
PARAMETERS (2) Set the desired frequencies and voltages in Pr. 100 to Pr. 109. •The setting must satisfy the following relationship: F1≠F2≠F3≠F4≠F5≠Pr. 3 "base frequency". If the set frequencies are the same, a write error occurs. If any frequency setting is "9999", its point is ignored. Note: 1. The V/F 5-point flexible characteristic functions for V/F control only. It does not function for advanced magnetic flux vector control. 2. These functions are activated only when "0" is set in Pr. 60. 3.
PARAMETERS z For the data codes of the parameters, refer to the data code list in the appendices. REMARKS For computer link operation, set the value "8888" as 65520 (HFFF0) and the value "9999" as 65535 (HFFFF). Parameter Number Factory Setting 117 0 Setting Range 0 to 31 118 192 48, 96, 192 119 1 120 2 0, 1, 2 121 1 0 to 10, 9999 122* 0 0, 0.1 to 999.
PARAMETERS (1) Communication protocol Data communication between the computer and inverter is performed using the following procedure: Data read Computer ↓ (Data flow) *2 Time Inverter ↓ 5) 4) 1) Inverter 2) (Data flow) 3) *1 Data write Computer *1. If a data error is detected and a retry must be made, execute retry operation from the user program. The inverter comes to an alarm stop if the number of consecutive retries exceeds the parameter setting. *2.
PARAMETERS 2) Reply data from inverter to computer during data write [No data error detected] [Data error detected] *2 Inverter *1 station ACK number Format C 1 2 *4 3 4 Format D ←Number of characters *2 Inverter station number *3 NAK 1 2 Error code *4 4 5 3 ←Number of characters 3) Reply data from inverter to computer during data read [No data error detected] Format E *1 STX 1 Format E' *1 STX 1 [Data error detected] *2 Inverter station number 2 3 4 *2 Inverter station number 2
PARAMETERS 5) Waiting time Specify the waiting time between the receipt of data at the inverter from the computer and the transmission of reply data. Set the waiting time in accordance with the response time of the computer between 0 and 150ms in 10ms increments (e.g. 1 = 10ms, 2 = 20ms). Computer ↓ Inverter Inverter data processing time =waiting time + data check time (set value×10ms) (12ms) Inverter ↓ Computer ote : When Pr.
PARAMETERS 7) Sum check code The sum check code is 2-digit ASCII (hexadecimal) representing the lower 1 byte (8 bits) of the sum (binary) derived from the checked ASCII data. Computer→Inverter ENQ ASCII code→ H05 Station number Instruction code *Waiting time (Example1) Sum check code Data 0 1 E 1 1 0 7 A D F 4 H30 H31 H45 H31 H31 H30 H37 H41 H44 H46 H34 ←Binary code ↓ H H H H H H H H H 30 + 31 + 45 + 31 + 31 + 30 + 37 + 41 + 44 H =1F4 Sum When Pr.
PARAMETERS (5) Instructions for the program 1) When the data from the computer has an error, the inverter will not accept that data. Hence, in the user program, always insert a retry programs for date error. 2) Since any data communication, such as operation command or monitoring, is always requested by the computer, the inverter will not return data without the computer's request. Hence, design the program so that the computer gives a data read request for monitoring, etc. as required.
PARAMETERS After completion of parameter setting, set the instruction codes and data and start communication from the computer to allow various types of operation control and monitoring. No.
PARAMETERS No. Instruction Code Item b7 Run command HFA 0 0 0 0 0 1 0 H7A b0: Inverter running (RUN) * b1: Forward rotation (STF) b2: Reverse rotation (STR) b3: Up to frequency (SU) * b4: Overload (OL) * b5: Instantaneous power failure (IPF) * b6: Frequency detection (FU) * b7: Alarm occurrence * 2 digits [Example 1] H02 ... Forward rotation [Example 2] H00 ...
PARAMETERS No.
PARAMETERS (6) Communication specifications for RS-485 communication Operation Mode Operation Location Item Communication Operation from PU Connector External Operation Computer Link Operation (plug-in option used) Enable Disable Disable Enable Enable (Combined operation mode) Disable Run command (start) Running frequency setting Computer user program via PU connector Monitoring Parameter write Enable Enable Enable Enable (*4) Disable (*4) Disable (*4) Parameter read Inverter reset Compu
PARAMETERS 4.2.42 PID control (Pr. 128 to Pr. 134) Related parameters Pr. 73 "0-5V/0-10V selection" Pr. 79 "operation mode selection" Pr. 180 to Pr. 186 (input terminal assignment) Pr. 190 to Pr. 195 (output terminal assignment) Pr. 902 to Pr. 905 (frequency setting voltage (current) biases and gains) Pr. 128 "PID action selection" Pr. 129 "PID proportional band" Pr. 130 "PID integral time" Pr. 131 "upper limit" Pr. 132 "lower limit" Pr. 133 "PID action set point for PU operation" Pr.
PARAMETERS (2) PID action overview 1) PI action A combination of proportional control action (P) and integral control action (I) for providing a manipulated variable in response to deviation and changes with time. Deviation Set point [Operation example for stepped changes of process value] Process value Note: PI action is the sum of P and I actions.
PARAMETERS 4) Reverse action Increases the manipulated variable (output frequency) if deviation X (set point - process value) is positive, and decreases the manipulated variable if deviation is negative.
PARAMETERS Note: 1. The power supply must be selected in accordance with the power specifications of the detector used. 2. The output signal terminals used depends on the Pr. 191 to Pr. 194 settings. 3. The input signal terminals used depends on the Pr. 180 to Pr. 186 settings. (4) I/O signals Terminal Used Function Description Remarks PID control selection Switch on X14 to select PID control. Set any of "10, 11, 20 and 21" in Pr. 128. X14 Depending on Pr. 180 to Pr.
PARAMETERS (5) Parameter setting Parameter Number Setting Name 10 11 128 20 For heating, pressure control, etc. PID action selection 21 129 0.1 to 1000% 130 PID proportional band 0 to 100% PID integral time 0 to 100% Upper limit 134 0 to 100% 0.01 to 10.00 s PID forward action PID reverse action PID forward action If the proportional band is narrow (parameter setting is small), the manipulated variable varies greatly with a slight change of the process value.
PARAMETERS (7) Calibration example (A detector of 4mA at 0°C and 20mA at 50°C is used to adjust the room temperature to 25°C under PID control. The set point is given to across inverter terminals 2-5 (0-5V).) START Determine the set point. xxxxxxSet the room temperature to 25°C. Set Pr. 128 and switch on the X14 signal to enable PID control. Determine the set point of the item to be adjusted. Convert the set point into %. Calculate the ratio of the set point to the detector output. Make calibration.
PARAMETERS 1. Apply the input voltage of 0% set point setting (e.g. 0V) to across terminals 2-5. 2. Make calibration using Pr. 902. At this time, enter the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz). 3. Apply the voltage of 100% set point setting (e.g. 5V) to across terminals 2-5. 4. Make calibration using Pr. 903. At this time, enter the frequency which should be output by the inverter at the deviation of 100% (e.g. 60Hz).
PARAMETERS 4.2.43 Commercial power supply-inverter switch-over function (Pr. 135 to Pr. 139) Pr. 135 "commercial power supply-inverter switch-over sequence output terminal selection" Pr. 136 "MC switch-over interlock time" Pr. 137 "start waiting time" Pr. 138 "commercial power supply-inverter switch-over selection at alarm occurrence" Related parameters Pr. 11 "DC injection brake operation time" Pr. 57 "restart coasting time" Pr. 58 "restart cushion time" Pr. 180 to Pr.
PARAMETERS • Roles of the magnetic contactors (MC1, MC2, MC3) Magnetic Contactor Place of Installation MC1 Between power supply and inverter Normally shorted with the following exception: Opened only when an inverter fault occurs (shorted again by resetting) MC2 Between power supply and motor Shorted for commercial power supply operation, opened for inverter operation.
PARAMETERS (Note) When the commercial power supply-inverter switch-over sequence function is activated with the FR-A5AR mounted, a magnet contactor repeats switch on/off. Always use in the following connection diagram. MC2 1) Recommended connection example 1 Use inverter output terminals (Contact signal, open collector signal) instead of MC1 signals. The phenomenon occurs when relay output of the FR-A5AR is used as MC1 signal.
PARAMETERS (2) Parameter setting Parameter Number 135 Name Setting Commercial power supply-inverter switch-over sequence output terminal selection Description 0 Sequence output is not provided. (Pr. 136, Pr. 137, Pr. 138 and Pr. 139 settings are ignored.) 1 Sequence output is provided. When MC1 to MC3 are assigned with Pr. 190 to Pr. 195 (output terminal function selection), open collector outputs are provided. When they are not assigned, relay outputs are provided from the FR-A5AR (option).
PARAMETERS (3) Operation procedure 1) Operation procedure for running Operation pattern Switch power on. Set parameters. Start, inverter operation Pr. 135 = "1" (inverter's open collector output terminals) Pr. 136 = "2.0 s" Pr. 137 = "1.0 s" (Set the value equal to or longer than the time from when MC3 switches on actually until the inverter and motor are connected. If it is shorter, restart may not function properly.) Pr. 57 = "0.5 s" Pr. 58 = "0.
PARAMETERS 4.2.44 Output current detection function (Pr. 150, Pr. 151) Pr. 150 "output current detection level" Related parameters Pr. 190 to Pr. 195 (output terminal function selection) Pr. 151 "output current detection period" zIf the output current remains higher than the Pr. 150 setting during inverter operation for longer than the time set in Pr. 151, the output current detection signal (Y12) is output from the inverter's open collector output terminal. (Use any of Pr. 190 to Pr.
PARAMETERS 4.2.45 Zero current detection (Pr. 152, Pr. 153) Pr. 152 "zero current detection level" R elated param eters Pr. 190 to Pr. 195 (output terminal function selection) Pr. 153 "zero current detection period" When the inverter's output current falls to "0", torque will not be generated. This may cause a drop due to gravity when the inverter is used in vertical lift application.
PARAMETERS Pr. 154 Refer to Pr. 22. 4.2.46 RT signal activated condition selection (Pr. 155) R elated param eters Pr. 14 "load pattern selection" Pr. 44 to Pr. 49 (second function selection) Pr. 81 "number of motor poles" Pr. 180 to Pr. 186 (input terminal function selection) Pr. 155 "RT signal activated condition" zSet the condition of activating the RT terminal to select the second control functions by switching on-off the RT signal. Parameter Number Factory Setting Setting Range 155 0 0.
PARAMETERS Refer to the following list and set the parameters: Pr. 156 Setting 100 101 (Note 4) High-Response Current Limit {...Activated. z...Not activated 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 { z Driving Regenerative Driving Regenerative Stall Prevention Operation Selection z...Not activated {...Activated Constant Deceleration Acceleration speed OL Signal Output {...Operation continued z...
PARAMETERS 4.2.48 OL signal output timer (Pr. 157) Pr. 157 "OL signal waiting time" R elated param eters Pr. 190 to Pr. 195 "output terminal function selection" Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset period of time after occurrence of an overload status.
PARAMETERS 4.2.49 User group selection (Pr. 160, Pr. 173 to Pr. 176) Pr. 160 "user group read selection" Pr. 173 "user group 1 registration" Pr. 174 "user group 1 deletion" Pr. 175 "user group 2 registration" Pr. 176 "user group 2 deletion" • Pr. 160 "user group read selection" is used to limit the parameters which may be read. • From among all parameters, a total of 32 parameters can be registered to two different user groups. The registered parameters may only be accessed for reading and writing.
PARAMETERS 4.2.50 Watt-hour meter clear/actual operation hour meter clear (Pr. 170, Pr. 171) Pr. 170 "watt-hour meter clear" Pr. 171 "actual operation hour meter clear" R elated param eters P r. 52 "D U /P U m ain display data selection" You can clear the watt-hour value and actual operation hour monitoring function. Parameter Number Factory Setting Setting Range 170 0 0 171 0 0 Write "0" in the parameters to clear the watt-hour value and actual operation hour.
PARAMETERS Refer to the following list and set the parameters: Setting Signal Name Functions Pr. 59 = 0 0 RL Pr. 59 = 1, 2 Pr. 79 = 5 Low-speed operation command Remote setting (setting clear) Pr. 59 * Programmed operation group selection Pr. 79, Pr. 200, Pr. 201 to Pr. 210, Pr. 211 to Pr. 220, Pr. 221 to Pr. 230, Pr. 231 Pr. 59 = 0 2 3 RM RH RT Pr. 59 = 1, 2 Pr. 4 to Pr. 6 Pr. 24 to Pr. 27 Pr. 232 to Pr. 239 * Pr.
PARAMETERS Note: 1. One function can be assigned to two or more terminals. In this case, the terminal inputs are OR’ed. 2. The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL) and AU. 3. When the X10 signal (FR-HC, FR-CV connection, inverter operation enable signal) is not selected, the MRS signal shares this function. 4. Use common terminals to assign programmed operation group selection, multi-speeds (7 speeds) and remote setting. They cannot be set individually.
PARAMETERS 4.2.52 Output terminal function selection (Pr. 190 to Pr. 195) Pr. 190 "RUN terminal function selection" Pr. 191 "SU terminal function selection" Pr. 192 "IPF terminal function selection" Pr. 193 "OL terminal function selection" Pr. 194 "FU terminal function selection" Pr. 195 "A, B, C terminal function selection" You can change the functions of the open collector and contact output terminals.
PARAMETERS Setting Positive Negative logic logic Signal Name 17 MC1 18 MC2 19 MC3 20 25 120 125 BOF FAN Commercial power supplyinverter switch-over MC1 Commercial power supplyinverter switch-over MC2 Commercial power supplyinverter switch-over MC3 Brake opening request Fan fault output 26 126 FIN Fin overheat pre-alarm 27 28 29 30 31 32 33 127 128 129 130 131 132 133 ORA ORM Y29 Y30 Y31 Y32 RY2 In-position Orientation error Overspeed detection Forward running output Reverse ru
PARAMETERS 4.2.53 User initial value setting (Pr. 199) Pr. 199 "user's initial value setting" R elated param eters Pr. 77 "parameter write disable selection" Among the parameters, you can set user-only parameter initial values. These values may be set to 16 parameters. By performing user clear operation from the operation panel or parameter unit, you can initialize the parameters to the user-set initial values.
PARAMETERS 4.2.54 Programmed operation function (Pr. 200 to Pr. 231) Pr. 200 "programmed operation minute/second selection" R elated param eters Pr. 76 "alarm code output selection" Pr. 79 "operation mode selection" Pr. 201 to Pr. 210 "program set 1 1 to 10" Pr. 211 to Pr. 220 "program set 2 11 to 20" Pr. 221 to Pr. 230 "program set 3 21 to 30" Pr.
PARAMETERS (1) Set the time unit for programmed operation in Pr. 200. Select either of "minute/second" and "hour/ minute". Setting Description 0 Minute/second unit (voltage monitor) 1 Hour/minute unit (voltage monitor) 2 Minute/second unit (reference time of day monitor) 3 Hour/minute unit (reference time of day monitor) Note: 1. When "2" or "3" is set in Pr. 200, the reference time-of-day monitor screen is displayed instead of the voltage monitor screen. 2. Note that when the Pr.
PARAMETERS (Example: Set point No. 1, forward rotation, 30Hz, 4 hours 30 minutes) 1) Read Pr. 201 value. 2) Enter "1" (forward rotation) in Pr. 201 and press the SET key ( WRITE key when using the FR-PU04 parameter unit). 3) Enter 30 (30Hz) and press the SET 4) Enter "4.30" and press the key ( 5) Press the SET key ( key when using the FR-PU04 parameter unit). (Note 1) WRITE key when using the FR-PU04 parameter unit). (Note 2) WRITE key to move to the next parameter (Pr.
PARAMETERS (6) Operation 1) Ordinary operation After completion of all preparations and settings, turn on the desired group select signal (any of RH (group 1), RM (group 2) and RL (group 3)), then turn on the start signal (STF). This causes the internal timer (reference time of day) to be reset automatically and the operation of that group to be performed in sequence in accordance with the settings. When the operation of the group ends, a signal is output from the time-out output terminal.
PARAMETERS 4.2.55 Cooling fan operation selection (Pr. 244) Pr. 244 "cooling fan operation selection" You can control the operation of the cooling fan built in the inverter (200V class... 1.5K or more, 400V class... 2.2K or more). Parameter Number Factory Setting Setting Range 244 0 0,1 Setting Description 0 Operated at power on (independently of whether the inverter is running or at a stop).
PARAMETERS 4.2.56 Stop selection (Pr. 250) Pr. 250 "stop selection" R elated param eters Pr. 7 "acceleration time" Pr. 8 "deceleration time" Pr. 44 "second acceleration/deceleration time" Pr. 45 "second deceleration time" Pr. 110 "third acceleration/deceleration time" Pr. 111 "third deceleration time" Used to select the stopping method (deceleration to a stop or coasting) when the start signal (STF/STR) turns off. Parameter Number Factory Setting Setting Range 250 9999 0 to 100 s, 9999 (1) Pr.
PARAMETERS 4.2.57 Output phase failure protection selection (Pr. 251) Pr. 251 "output phase failure protection selection" You can make the output phase failure protection (E.LF) function which stops the inverter output invalid if one of the three phases (U, V, W) on the inverter's output side (load side) becomes open.
PARAMETERS 4.2.59 Power failure-time deceleration-to-stop function (Pr. 261 to Pr. 266) Pr. 261"power failure stop selection" R elated param eters Pr. 12 "DC injection brake voltage" Pr. 20 "acceleration/deceleration reference frequency" Pr. 262"subtracted frequency at deceleration start" Pr. 263"subtraction starting frequency" Pr. 264"power-failure deceleration time 1" Pr. 265"power-failure deceleration time 2" Pr.
PARAMETERS Note: 1. This function is invalid when the automatic restart after instantaneous power failure function is set. 2. If (output frequency at occurrence of undervoltage or power failure) minus (frequency set in Pr. 263) is negative, the calculation result is regarded as 0Hz. 3. The power failure stop function is not activated during a stop or error. 4. If power is restored during deceleration, the inverter is kept decelerating to a stop.
PARAMETERS 4.2.61 High-speed frequency control (Pr. 271 to Pr. 274) R elated param eters Pr. 271 "high-speed setting maximum current" Pr. 272 "mid-speed setting minimum current" Pr. 273 "current averaging range" Pr. 274 "current averaging filter constant" Pr. 4 "multi-seed setting (high speed)" Pr. 5 "multi-seed setting (middle speed)" Pr. 6 "multi-seed setting (low speed)" Pr. 59 "remote setting function selection" Pr. 180 to Pr. 186 (input terminal function selection) Pr.
PARAMETERS Power running A Pr.4 Regenerating B Pr.5 1 2 Pr.5 × Pr.5 1 2 Less than Pr. 271 setting × Pr.5 rated current More than Pr. 272 setting rated current ON Terminal OFF STF (STR) CS • When operation is performed with X19 (load detection high-speed frequency function selection) signal on, the inverter automatically varies the maximum frequency between Pr. 4 "multi-speed setting (high speed)" and Pr.
PARAMETERS Note: 1. This function is only valid in the external operation mode. This function is not activated when "1" or "2" (remote setting function) is selected for Pr. 59. 2. If the current averaging zone range the constant power region, the output current may increase in the constant power region. 3. When the average current within the current averaging range is small, the running frequency increases, which causes the longer deceleration time. 4. The maximum output frequency is 120Hz.
PARAMETERS zFunction list (The following specifications apply to the external operation mode.) Pr. 270 Setting Load Torque High-Speed Frequency Control Stop-On-Contact Control (RL, RT) Multi-Speeds (7 speeds) (RH, RM, RL) 1 × × 2 { × { 3 { { { 0 { × { { { Indicates that the function is valid. zRestrictions when 1 to 3 are selected for Pr. 270 Under the following conditions, the functions of Pr.
PARAMETERS 4.2.62 Stop-on-contact control function (Pr. 275, Pr. 276) R elated param eters Pr. 4 "multi-seed setting (high speed)" Pr. 5 "multi-seed setting (middle speed)" Pr. 6 "multi-seed setting (low speed)" Pr. 48 "second stall prevention Pr. 72 "PWM carrier frequency" operation current" Pr. 180 to Pr. 186 (input terminal function selection) Pr. 270 "stop-on-contact, load torque high-speed frequency selection" Pr. 275 "stop-on-contact excitation current low-speed multiplying factor" Pr.
PARAMETERS Note: 1. By increasing the Pr. 275 setting, the low-speed (stop-on-contact) torque increases, but the overcurrent alarm (E.OCT) may occur or the machine may oscillate in a stop-on-contact state. 2. The stop-on-contact function is different from the servo lock function, and if used to stop or hold a load for an extended period, the function can cause the motor to overheat. After a stop, immediately reset this function and use a mechanical brake to hold the load. 3.
PARAMETERS Frequencies set in stop-on-contact control (Pr. 270 = 1 or 3) (In external operation mode) The following table lists the frequencies set when the input terminals (RH, RM, RL, RT, JOG) are selected together. Input Signals RH RM RL RT { { { { { { { { { { { { { { { { { { { { { { { Jog frequency Pr. 15 Speed 6 Pr. 26 Middle speed when Pr. 26 = 9999 Speed 5 Pr. 25 Low speed when Pr. 25 = 9999 Speed 1 (high speed) Pr. 4 Jog frequency Pr. 15 Speed 4 Pr.
PARAMETERS 4.2.63 Brake sequence function (Pr. 278 to Pr. 285) Pr. 278 "brake opening frequency" R elated param eters Pr. 60 "intelligent mode selection" Pr. 80 "motor capacity" Pr. 81 "number of motor poles" Pr. 180 to Pr. 186 (input terminal function selection) Pr. 190 to Pr. 195 (output terminal function selection) Pr. 279 "brake opening current" Pr. 280 "brake opening current detection time" Pr. 281 "brake operation time at start" Pr. 282 "brake operation frequency" Pr.
PARAMETERS z At start: z At stop: When the start signal is input to the inverter, the inverter starts running. When the output frequency reaches the value set in Pr. 278 and the output current is not less than the value set in Pr. 279, the inverter outputs the brake opening request signal (BOF) after the time set in Pr. 280 has elapsed. When the time set in Pr.
PARAMETERS (1) Parameter setting 1) Select advanced magnetic flux vector control. (Pr. 80, Pr. 81 ≠ "9999") 2) Set "7 or 8" (brake sequence mode) in Pr. 60. To ensure more complete sequence control, it is recommended to set "7" (brake opening completion signal input) in Pr. 60. Note that the automatic restart after instantaneous power failure function is not activated when the brake sequence mode is selected.
PARAMETERS (3) Protective functions If any of the following errors occur in the brake sequence mode, the inverter results in an alarm, shuts off the output and switches off the brake opening request signal (BOF terminal). On the operation panel (FR-DU04) LED and parameter unit (FR-PU04) screen, the following errors are displayed: Error Display Error Display E.MB1 (Detected frequency) - (output frequency) > Pr. 285 in the encoder feedback control mode. (Overspeed detection function) E.
PARAMETERS 4.2.64 Droop control (Pr. 286, Pr. 287) Pr. 286 "droop gain" Related parameters Pr. 9 "electronic thermal O/L relay" Pr. 71 "applied motor" Pr. 84 "rated motor frequency" Pr. 287 "droop filter constant" This function balances the load in proportion to the load torque with or without encoder, and provides speed drooping characteristics. This is effective in balancing the load when using multiple inverters.
PARAMETERS 4.2.65 Capacitor life alarm (Pr. 503, Pr. 504) Pr. 503 "capacitor life timer" Related parameters Pr. 190 to Pr. 195 (output terminal / function selection) Pr. 504 "capacitor life alarm output setting time" When the cumulative operation time of the inverter has elapsed the time set in Pr.
PARAMETERS 4.2.66 FM / AM terminal calibration (Pr. 900, Pr. 901) Pr. 900 "FM terminal calibration" Related parameters Pr. 54 "FM terminal function selection" Pr. 55 "frequency monitoring reference" Pr. 56 "current monitoring reference" Pr. 158 "AM terminal function selection" Pr. 901 "AM terminal calibration" zBy using the operation panel/parameter unit, you can calibrate a meter connected to terminal FM to full scale. zTerminal FM provides the pulse output. By setting Pr.
PARAMETERS •When operation panel (FR-DU04) is used 1) Select the PU operation mode. 2) Set the running frequency. 3) Press the SET key. 4) Read Pr. 900 "FM terminal calibration" or Pr. 901 "AM terminal calibration". 5) Press the FWD key to run the inverter. (Motor need not be connected.) 6) Hold down the key to adjust the meter pointer to the required position. (Depending on the setting, it may take some time until the pointer moves.
PARAMETERS 4.2.67 Frequency setting voltage (current) bias and gain (Pr. 902 to Pr. 905) Pr. 902 "frequency setting voltage bias" Related parameters Pr. 20 "acceleration/deceleration reference frequency" Pr. 73 "0-5V/0-10V selection" Pr. 79 "operation mode selection" Pr. 903 "frequency setting voltage gain" Pr. 904 "frequency setting current bias" Pr.
PARAMETERS Pr. 903 "frequency setting voltage gain" (Pr. 902, Pr. 904, Pr. 905 can also be adjusted similarly.) When using the frequency setting signal from the operation panel (FR-DU04) to set the frequency. (1) Power-on (monitoring mode) FR-DU04 CONTROL PANEL Hz A V MON EXT PU REV FWD (2) Choose the PU operation mode. 1) Using the MODE key, make sure that the PU operation mode has been selected.
PARAMETERS 2) Set "1" (PU operation mode) in Pr. 79 "operation mode selection". Example: To change the external operation mode (Pr. 79=2) to the PU operation mode (Pr. 79=1) Using the MODE key, choose the "parameter setting mode" as in 1).
PARAMETERS (3) Read Pr. 903 and show the current setting of the gain frequency. (Pr. 902, Pr. 904 and Pr. 905 can also be adjusted similarly.) zParameter setting mode Using the FR-DU04 MODE key, choose the "parameter setting mode" as in (2)-1). CONTROL PANEL Hz A V MON EXT PU REV FWD SET Most significant digit flickers. Middle digit flickers. Least significant digit flickers.
PARAMETERS • When not adjusting the gain voltage → go to (5) - 1) • When adjusting any point by applying a voltage → go to (5) - 2) • When adjusting any point without applying a voltage → go to (5) - 3) (5) - 1) How to adjust only the gain frequency and not to adjust the voltage z Analog voltage value (%) across terminals 2-5 FR-DU04 zPress the or key once to display the current analog voltage adjustment.
PARAMETERS Note: 1. If the Pr. 903 or Pr. 905 (gain adjustment) value is changed, the Pr. 20 value does not change. The input signal to terminal 1 (frequency setting auxiliary input) is added to the frequency setting signal. 2. For the operation procedure using the parameter unit (FR-PU04), refer to the FR-PU04 instruction manual. CAUTION Be careful when setting any value other than "0" as the bias frequency at 0V.
CHAPTER 5 PROTECTIVE FUNCTIONS Chapter 1 This chapter explains the "protective functions" for use of this product. Always read the instructions and other information before using the equipment. 5.1 Errors (Alarms) .................................................... 196 5.2 Troubleshooting...................................................
PROTECTIVE FUNCTIONS 5.1 Errors (Alarms) If any fault has occurred in the inverter, the corresponding protective function is activated and the error (alarm) indication appears automatically on the PU display. When the protective function is activated, refer to "5.2 Troubleshooting" and clear up the cause by taking proper action. If an alarm stop has occurred, the inverter must be reset to restart it.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action E.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action E.THM FR-PU04 Motor Ovrload Motor overload shut-off (electronic overcurrent protection) (Note 1) The electronic overcurrent protection in the inverter detects motor overheat due to overload or reduced cooling capability during constant-speed operation. When 85% of the preset value is reached, pre-alarm (TH indication) occurs.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action E.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name E.BE FR-PU04 Br. Cct. Fault Brake transistor alarm detection If the brake circuit fault has occurred due to damaged brake transistors, etc., this function stops the inverter output. In this case, the inverter power must be switched off immediately. • Reduce load J.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action E.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name E. 6 Fault 6 FR-PU04 E. 7 Fault 7 CPU error This function stops the inverter output if a communication error occurs in the built-in CPU. • Check for excess electrical noises around the inverter.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action E.ECT FR-PU04 No encoder signal Wire break detection The inverter output is stopped if the encoder signal is turned off during orientation, encoder feedback or vector control executed with the FR-A5AP. Check for encoder signal wire break. Repair wire break. (2) Minor fault When the protective function is activated, the output is not shut off. You can make parameter setting to output the minor fault signal.
PROTECTIVE FUNCTIONS Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Name Description Check point Corrective action Operation Panel Indication Description Corrective action oL FR-PU04 oL Stall prevention (overvoltage) f the regenerative energy of the motor increases too much to During exceed the brake ca
PROTECTIVE FUNCTIONS 5.1.2 To know the operating status at the occurrence of an alarm When any alarm has occurred, the display automatically switches to the indication of the corresponding protective function (error). By pressing the MODE key at this point without resetting the inverter, the display shows the output frequency. In this way, it is possible to know the running frequency at the occurrence of the alarm. This also applies to the current.
PROTECTIVE FUNCTIONS 5.1.4 Alarm code output By setting Pr. 76 "alarm code output selection", an alarm definition can be output as a 4-bit digital signal. This signal is output from the open collector output terminals equipped as standard on the inverter. Correlations between alarm definitions and alarm codes are as follows. Output Terminal Signal On-Off Operation Panel Display (FR-DU04) SU IPF OL FU E.OC1 0 0 0 1 1 E.OC2 0 0 1 0 2 E.OC3 0 0 1 1 3 0 1 0 0 4 E.
PROTECTIVE FUNCTIONS 5.2 Troubleshooting POINT: Check the corresponding areas. If the cause is still unknown, it is recommended to initialize the parameters (return to factory settings), re-set the required parameter values, and check again. 5.2.1 Motor remains stopped 1) Check the main circuit Check that a proper power supply voltage is applied (operation panel display is provided). Check that the motor is connected properly. Check that the conductor across P-P1 is connected.
PROTECTIVE FUNCTIONS 5.2.6 Speed does not increase Check that the maximum frequency (Pr. 1) setting is correct. Check that the load is not too heavy. (In agitators, etc., load may become heavy in winter.) Check that the torque boost (Pr. 0, Pr. 46, Pr. 112) setting is not too large to activate the stall prevention function. Check that the brake resistor is not connected to terminals P-P1 by mistake. 5.2.
CHAPTER 6 PRECAUTIONS FOR MAINTENANCE AND INSPECTION Chapter 1 This chapter provides the "precautions for maintenance and inspection" of this product. Always read the instructions and other information before using the equipment. Chapter 2 6.1 Precautions for maintenance and inspection ............
PRECAUTIONS FOR MAINTENANCE AND INSPECTION 6.1 Precautions for maintenance and inspection The transistorized inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to adverse influence by the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors. 6.1.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION 6.1.4 Insulation resistance test using megger 1) Before performing the insulation resistance test using a megger on the external circuit, disconnect the cables from all terminals of the inverter so that the test voltage is not applied to the inverter. 2) For the continuity test of the control circuit, use a meter (high resistance range) and do not use the megger or buzzer.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION Interval Area of Inspec -tion Main circuit Inspect ion Item Description Periodic Daily 1 year Inverter module, Convert er module Check resistance across terminals. { Relay (1) Check for chatter during operation. (2) Check for rough surface on contacts. (1) Check for crack in resistor insulation. (2) Check for open cable. { (1) Check balance of output voltages across phases with inverter operated alone.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION z Checking the inverter and converter modules (1) Disconnect the external power supply cables (R, S, T) and motor cables (U, V, W). (2) Prepare a tester. (Use 100Ω range.) Change the polarity of the tester alternately at the inverter terminals R, S, T, U, V, W, P and N, and check for continuity. Note: 1. Before measurement, check that the smoothing capacitor is discharged. 2.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION 6.1.7 Replacement of parts The inverter consists of many electronic parts such as semiconductor devices. The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically. The part replacement guidelines for the inverter are indicated in the following table.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION (2) Smoothing capacitors A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum electrolytic capacitor is also used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the adverse effects of ripple currents, etc. The replacement intervals greatly vary with the ambient temperature and operating conditions.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION 6.1.9 Measurement of main circuit voltages, currents and powers z Measurement of main circuit voltages, currents and powers Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data depends on the instruments used and circuits measured. When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments given on the next page.
PRECAUTIONS FOR MAINTENANCE AND INSPECTION Measuring Points and Instruments Item Measuring Point Measuring Instrument Power supply voltage V1 Across R-S, S-T and T-R Moving-iron type AC voltmeter Power supply side current I1 R, S and T line currents Moving-iron type AC ammeter Power supply side power P1 At R, S and T, and across R-S, S-T and T-R Electrodynamic type singlephase wattmeter Remarks (Reference Measured Value) * Commercial power supply Within permissible AC voltage fluctuation (Refer
MEMO 218
CHAPTER 7 SPECIFICATIONS Chapter 1 This chapter provides the "specifications" of this product. Always read the instructions and other information before using the equipment. Chapter 2 7.1 Standard Specifications.......................................
SPECIFICATIONS 7.1 Standard Specifications 7.1.1 Model specifications ! 200V class Type FR-A520-""K Applicable motor capacity (Note 1) kW Rated capacity (kVA) (Note 2) Output Rated current (A) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 1.1 1.9 3.1 4.2 6.7 9.2 12.6 17.6 23.3 29 34 44 55 67 82 3 5 8 11 17.
SPECIFICATIONS ! 400V class Type FR-A540-""K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 Rated capacity (kVA) (Note 2) 1.1 1.9 3 4.6 6.9 9.1 13 17.5 23.6 29 32.8 43.4 54 65 84 Rated current (A) 1.5 2.5 4 6 9 12 17 23 31 38 43 57 71 86 110 80 100 Output Applicable motor capacity (Note 1) Overload current capacity (Note 3) 150% 60s, 200% 0.
SPECIFICATIONS 7.1.2 Common specifications Selectable between Soft-PWM control and high carrier frequency PWM control (Selectable between V/F control and advanced magnetic flux vector control) Control specifications Control system Output frequency range 0.2 to 400Hz Frequency setting resolution Analog input 0.015Hz/60Hz (terminal 2 input: 12 bits/0 to 10V, 11 bits/0 to 5V, terminal 1 input: 12 bits/-10 to +10V, 11 bits/-5 to +5V) Digital input 0.01Hz Frequency accuracy Within ±0.
SPECIFICATIONS Protective/alarm functions Environment Ambient temperature Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative overvoltage shut-off, undervoltage, instantaneous power failure, overload shut-off (electronic overcurrent protection), brake transistor alarm (Note 2), earth (ground) fault current, output short circuit, main circuit device overheat, stall prevention, overload alarm, brake resistor overheat protection, heatsink overheat, fan fault, option fault
SPECIFICATIONS 7.1.3 Outline dimension drawings z FR-A520-0.4K, 0.75K z 200V class D 110 2-φ6 hole 5 D 110 FR-A520-0.75K 125 245 260 Inverter Type FR-A520-0.4K 6 95 (Unit: mm) z FR-A520-1.5K, 2.2K, 3.7K z FR-A540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K 150 140 2-φ 6 hole 49.5 245 260 5 6 125 Note: FR-A540-0.4K to 1.5K are not provided with the cooling fan.
SPECIFICATIONS z FR-A520-5.5K, 7.5K, 11K z FR-A540-5.5K, 7.5K 220 z 200V class D 2-φ6 hole 10.5 H1 D D1 260 245 170 84 FR-A520-7.5K 260 245 170 84 FR-A520-11K 300 285 190 101.5 H1 Inverter Type D1 H H FR-A520-5.5K z 400V class Inverter Type 6 195 H H1 D D1 FR-A540-5.5K 260 245 170 84 FR-A540-7.5K 260 245 170 84 (Unit: mm) 211 z FR-A520-15K, 18.5K, 22K z FR-A540-11K, 15K, 18.5K, 22K 250 190 2-φ10 hole 101.5 380 400 10.
SPECIFICATIONS z FR-A520-30K, 37K, 45K, 55K z FR-A540-30K, 37K, 45K, 55K D H2 3.2 H D1 2-φC hole H1 W C W1 W2 z 200V class W W1 W2 H H1 H2 D D1 C FR-A520-30K Inverter Type 340 270 320 550 530 10 195 71.
SPECIFICATIONS z Operation panel (FR-DU04) 16.5 10.5 24 16.5 15 23.75 2- φ4 hole 3.5 46.5 19.75 81.5 2-M3 hole 46.5 17 20 72 Effective depth 4.5 54 3.25 54 (Unit: mm) Choose the mounting screws whose length will not exceed the effective depth of the mounting threads. z Parameter unit (FR-PU04) 16.5 24 23.75 11.75 13 17 1.25 1.5 14.5 21.5 80 125 5- 4 hole 1.5 13 81.
MEMO 228
CHAPTER 8 OPTIONS Chapter 1 This chapter describes the "options" for use of this product. Always read the instructions and other information before using the equipment. Chapter 2 8.1 Option List ...........................................................
OPTIONS 8.1 Option List 8.1.1 Stand-alone options Name Type Application, Specifications, etc. Applicable Inverter Parameter unit (8 languages) FR-PU04 Interactive parameter unit using LCD display (For use in Japanese, English, German, French, Spanish, Italian, Swedish and Finnish) Parameter unit connection cable FR-CB2 Cable for connection of the operation panel or parameter unit.
OPTIONS Name Type Applicable Inverter Application, Specifications, etc. Manual controller FR-AX (Note 4) For independent operation. With frequency meter, frequency setting potentiometer and start switch. DC tach. follower FR-AL (Note 4) For joint operation using external signals. (0 to 5VDC, 0 to 10VDC) (1.5VA) (Note 2) Three speed selector FR-AT (Note 4) For three-speed (high, middle, low) switching operation. (1.5VA) Motorized speed setter FR-FK (Note 4) For remote operation.
OPTIONS 8.1.2 Plug-in dedicated options z Plug-in options Name 12-bit digital input Type FR-A5AX • Among 26 standard output signals of the inverter, this option outputs any 7 selected signals from open collector output terminals. Digital output FR-A5AY Extension analog output Relay output Orientation, encoder output (Note 3) FR-A5AR FR-A5AP • Outputs extra 16 signals which can be monitored on the FM and AM terminals such as output frequency, • 20mADC or 5V(10V)DC meter can be connected.
OPTIONS (1) Addition of Pr. 285 "excessive speed deviation detection frequency" In case the motor speed is increased or decreased due to load, etc. during vector control and can not be controlled to meet the speed command value, alarm stop occurs (E. OSD). Parameter Number Name Setting Range Minimum Setting Increments Factory Setting Description 285 Excessive speed deviation detection frequency 0 to 30Hz, 9999 0.
OPTIONS About the setting values "10 and 12" of Pr. 340 "link startup mode selection" You can switch operation between the PU operation and network operation when using with the communication option. The inverter starts up in the network operation mode and operation can be switched between the PU operation and network operation from the operation panel (FR-DU04) or parameter unit. Pr. 340 Setting Operation Mode Pr.
OPTIONS Operation at a communication error occurrence (when a communication option is connected) You can select operation at a communication error occurrence by setting Pr. 500 to Pr. 502 during network operation with a communication option. (not available with the FR-A5NM, FR-A5NP, and FR-A5NR (communication options).) (1) Operation selection at a communication error occurrence 1) Pr.
OPTIONS 3) Pr. 502 "communication error-time stop mode selection" You can select the inverter operation if a communication line fault or a fault of the option itself occurs. Parameter Number Setting Range Minimum Setting Increments Factory Setting 502 0, 1, 2 1 0 About settings • At fault occurrence Plug-in option itself Communication line Fault Pr.
OPTIONS (2) Alarm and measures 1) The inverter operates as follows at alarm occurrences Fault Location Operation Mode Status Inverter alarm Communication line alarm External operation Network operation Inverter operation Inverter trip Inverter trip Data communication Continued Continued Inverter trip Continued Inverter operation Continued Continued Inverter trip (Depends on the Pr.502 setting) Data communication Stop Stop Stop Inverter operation Inverter trip (Depends on the Pr.
OPTIONS The methods of setting DeviceNet node address and baud rate using FR-DU04 or FR-PU04 are shown as follows.
APPENDIX This chapter provides the "appendix" for use of this product. Always read the instructions and other information before using the equipment. Appendix1 Data Code List ..............................................
APPENDIX Appendix1 Data Code List Rated output current Display functions Second functions Output terminal functions Standard operation functions Basic functions Function Read Write 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 80 81 82 83 84 85 86 87 88 89 8A 8B 8C 8D 8E 8F 90 91 92 93 94 95 96 17 97 0 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Torque boost Maximum frequency Minimum frequency Base frequency Multi-speed setting (high speed) Multi-speed setting (middle s
Parameter Number 59 60 61 62 63 64 65 Operation selection functions Function Additional function APPENDIX Advanced magnetic flux vectorcontrol 5-point flexible V/F characteristics Data Codes Link Parameter Extension Setting (Instruction code 7F/FF) Read Write Remote setting function selection 3B BB 0 3C 3D 3E 3F 40 41 BC BD BE BF C0 C1 0 0 0 0 0 0 42 C2 0 43 44 45 46 47 48 49 4A C3 C4 C5 C6 C7 C8 C9 CA 0 0 0 0 0 0 0 0 4B CB 0 76 Intelligent mode selection Reference I for intelligen
APPENDIX Backlash Commercial power supply-inverter switch-over PID control Communication functions Function Display Sub functions Current detection Additional functions 117 118 119 120 121 122 123 124 128 129 130 131 132 133 134 Name 155 156 157 158 Station number Communication speed Stop bit length/data length Parity check presence/absence Number of communication retries Communication check time interval Waiting time setting CR, LF presence/absence selection PID action selection PID proportion
Read Write Terminal assignment functions APPENDIX 180 181 182 183 184 185 186 190 191 192 193 194 195 RL terminal function selection RM terminal function selection RH terminal function selection RT terminal function selection AU terminal function selection JOG terminal function selection CS terminal function selection RUN terminal function selection SU terminal function selection IPF terminal function selection OL terminal function selection FU terminal function selection A, B, C terminal function sele
Read Write 3B 3C 3D 45 46 47 48 49 BB BC BD C5 C6 C7 C8 C9 4A CA 2 4E CE 2 271 272 273 Output phase failure protection selection Override bias Override gain Power failure stop selection Subtracted frequency at deceleration start Subtraction starting frequency Power-failure deceleration time 1 Power-failure deceleration time 2 Power-failure deceleration time switchover frequency Stop-on-contact/load torque high-speed frequency control selection High-speed setting maximum current Mid-speed setting
APPENDIX Communication Orientation control / Encoder feedback control / Pulse train input DfviceNet Communication Computer link function Function 330 331 332 333 334 335 336 337 338 339 340 341 RA output selection Communication station number Communication speed Stop bit length Parity check yes/no Communication retry count Communication check time interval Waiting time setting Operation command right Speed command right Link startup mode selection CR • LF yes/no selection 1E 1F 20 21 22 23 24 25 26
APPENDIX Parameter Number Name Read Write Data Codes Link Parameter Extension Setting (Instruction code 7F/FF) Capacitor life timer 03 83 6 504 Capacitor life alarm output setting time 04 84 8 611 Restart acceleration time 0B 8B 8 816 Acceleration torque restriction level 10 90 8 817 Deceleration torque restriction level 11 90 8 900 901 902 903 904 905 990 991 FM terminal calibration AM terminal calibration Frequency setting voltage bias Frequency setting voltage gain Frequen
MEMO
REVISONS * The manual number is given on the bottom left of the back cover. Print Data *Manual Number Mar., 2003 IB(NA)-0600133E-A First edition Oct., 2003 IB(NA)-0600133E-B Modification Revision Error correction For Maximum Safety • Mitsubishi transistorized inverters are not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life.