A500.A4 01.10.
The Culmination of Mitsubishi’s Expertise Reaches into the Realms of Advanced Technology Expanding the Potential of Inverters Announcing the FR-A500 Series, a new line of advanced inverters that combines Mitsubishi Electric’s original technology with the benefits of its vast pool of accumulated expertise.
CONTENTS Features 3 Model Configuration 7 Standard Specifications 8 External Dimension Diagrams 10 Terminal Connection Diagram 14 Explanation of Terminal Specifications 15 Explanation of Control Panel 16 Key Operations Using the Control Panel 17 Explanation of Parameter Unit 18 List of Parameters 19 Applications 23 Protective Functions 24 Selecting Peripherals and Options 26 List of Options 27 FR-BU Brake Units/FR-BR Resistor Units 32 FR-HC High-power Factor Converters FR-RC Po
Features 1. The Ability to Maximize Drive Performance ■ Advanced Flux Vector Control Example of motor temperature/speed variation characteristics (SFJR 4P 3.7kW motor). (Repeated operations at 90% usage rate, on-line auto tuning selected) New levels in drive performance have been achieved thanks to the use of advanced flux vector control, an original technology developed by Mitsubishi. 320 The units feature a RISC processor which is used for on-line auto tuning, turning the motor quickly when starting.
Features ■ Smart Driver Uneven rotation at low speeds has been greatly improved by the use of a smart driver (a newly developed ASIC) which directly monitors and controls the main circuit's status. • Uneven rotation: less than half that of a conventional Mitsubishi inverter at 1 Hz Example of comparative data on uneven rotation (inverter operation frequency: 3Hz; SF-JR 4P 3.
Features 2. Achieves New Levels of User-friendliness ■ Simple Operation FR-DU04 control panel ● The simple FR-DU04 control panel is provided as standard on all models. An optional extension cable can be used with the control panel. Operational and alarm signals can also be shown with this unit. ● The FR-PU04 LCD parameter unit with long-life backlight display is available as an option. The unit features Mitsubishi's original direct input method which uses the ten-key pad.
Features 3. Environmentally Friendly ■ Soft-PWM Control In addition to the conventional low-noise mode, Mitsubishi has developed its own original Soft-PWM control method which suppresses the increase in acoustic noise and limits RFI noise to minimum levels similar to those of the Mitsubishi FR-Z Series inverter. Note: The default setting is Soft-PWM control ON. ■ Motor Noise Data Example (SF-JR 4P 3.
Model Configuration ■ Model FR - A520 - 3.7K Type A520 A540 Voltage class 200V class 400V class Type 0.4K280K Applicable Motor Capacity Indicates capacity in kW ■ Model Configuration Applicable Motor Capacity (kW) Power Supply Voltage 200V class 400V class 0.4 FR-A520-0.4K FR-A540-0.4K 0.75 FR-A520-0.75K FR-A540-0.75K 1.5 FR-A520-1.5K FR-A540-1.5K 2.2 FR-A520-2.2K FR-A540-2.2K 3.7 FR-A520-3.7K FR-A540-3.7K 5.5 FR-A520-5.5K FR-A540-5.5K 7.5 FR-A520-7.5K FR-A540-7.
Standard Specifications Ratings ■ 200V class 0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 18.5K 22K 30K 37K 45K 55K Applicable motor capacity (kW) (Note 1) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 (Note 2) 1.1 1.9 3.1 4.2 6.7 9.2 12.6 17.6 23.3 29 34 44 55 67 82 3 5 8 11 17.
Standard Specifications ■ Common Specifications Control Method Soft-PWM control, high-carrier frequency PWM control (V/F control, advanced flux vector control selection) Output frequency range Control Specifications Frequency control resolution 0.2 to 400Hz Analog input 0.015 Hz (Terminal No. 2 input: 12 bit/0 to 10V, 11 bit/0 to 5V; Terminal No. 1 input: 12 bit/-10 to +10V, 11 bit/-5 to +5V) Digital input 0.01Hz Within ±0.2% of max. output frequency (25°C (53°F)±10°C (±21.
External Dimension Diagrams ■ FR-A520-0.4K, 0.75K units: mm (inch) 110 (4.33) D 2 (0.08)- 6 (0.24) mounting hole 245 (9.65) 260 (10.24) 5 (0.20) 6 (0.24) 95 (3.74) ● 200V class Inverter type D FR-A520-0.4K 110 (4.33) FR-A520-0.75K 125 (4.92) ■ FR-A520-1.5K, 2.2K, 3.7K ■ FR-A540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K 150 (5.91) 140 (5.51) 2 (0.08)- 6 (0.24) mounting hole units: mm (inch) 245 (9.65) 260 (10.24) 5 (0.20) 6 (0.24) 49.5 (1.95) 125 (4.92) Note: FR-A540-0.4K~1.
External Dimension Diagrams ■ FR-A520-5.5K, 7.5K, 11K, 15K, 18.5K, 22K ■ FR-A540-5.5K, 7.5K, 11K, 15K, 18.5K, 22K W D 2 (0.08)- 6 (0.24) mounting hole units: mm (inch) H H1 D1 10.5 (0.41) W2 As viewed from direction of arrow Note: FR-A520-5.5K-11K, FR-A540-5.5K, 7.5K do not have slits. C W1 ● 200V class Inverter type FR-A520-5.5K/7.5K FR-A520-11K FR-A520-15K/18.5K/22K W 220 (8.66) 220 (8.66) 250 (9.84) W1 195 (7.68) 195 (7.68) 230 (9.06) W2 211 (8.31) 211 (8.31) 242 (9.53) H H1 260 (10.
External Dimension Diagrams ■ Making the housing plate more compact Housing plate When the inverter is being used inside a housing plate, the heat generated inside the plate can be greatly reduced by projecting the inverter's heat radiating fin outside of the plate. This mounting method is recommended when trying to reduce the size of a completely sealed housing plate. Notes 1. When mounting, use mounting attachment FR-A5CN (sold separately) (for models 1.5K~55K). 2.
External Dimension Diagrams ■ Parameter Unit (option) FR-PU04 24 (0.94) 13 (0.51) 80 (3.15) 13 (0.51) 20 (0.79) 125 (4.92) 81.5 (3.21) 48 (1.89) 21.5 (0.85) 24 (0.94) 46.5 (1.83) 16.5 (0.65) 15 9.7 (0.59) (0.38) 72 (2.83) 9.7 (0.38) 15 (0.59) 20 (0.79) 72 (2.83) 18.5 (0.73) ■ Control Panel FR-DU04 2 (0.08)- 4 (0.16) mounting hole 5 (0.20)- 4 (0.16) mounting hole 54 (2.13) 40 (1.57) units: mm (inch) Panel cutaway dimensions 16.5 (0.65) 2 (0.08)- 4 (0.16) mounting hole 17 (0.
Terminal Connection Diagram Inverter FR-A500 NFB Motor MC R S T 3-phase AC power supply U PU connector (RS-485) IM V W (Note 8) R1 S1 Short bar (Note10) 24 VDC power supply and external transistor common Short bar (Note 3) Grounding Power factor improvement DC reactor FR-BEL (option) P1 PC Forward run start STF Reverse run start STR P R (Note 1) STOP Start self-hold selection High Multi-speed selection (Max.
Explanation of Terminal Specifications Terminal symbol Type Main Circuit Terminal name Explanation R,S,T AC power supply input Connected to the commercial power supply. U,V,W Inverter output Connects the 3-phase squirrel cage motor. R1,S1 Control circuit power supply Connected to the AC power supply terminals R and S. To hold the error display or error output, remove the short bar on the terminal block, and input a power supply to this terminal from an external source.
Explanation of Control Panel Control Panel FR-DU04 External View 4-digit LED monitor Frequency Unit indicators: Current Voltage Monitor, External operation, PU operation Mode display Reverse, Forward Arrow keys [UP/DOWN keys] Operation controls Reverse key Forward key MODE key STOP & RESET key SET key Note: The Control Panel is standard equipment, and may be detached. ■ External Operation When a Start or Frequency instruction is sent from the control terminal.
Key Operations Using the Control Panel (at power ON) ● Frequency monitor FR-DU04 ● Monitor Display MON CONTROL PANEL Hz A V EXT REV PU FWD ● Current monitor SET FR-DU04 MON SET CONTROL PANEL Hz A V EXT REV PU FWD ● Alarm monitor ● Voltage monitor FR-DU04 SET MON SET SET CONTROL PANEL Hz A V EXT REV PU FWD MON SET ❊1 No alarm MODE FR-DU04 ● Frequency Setting Display ● Write frequency setting to memory ● Change frequency setting MON FR-DU04 CONTROL PANEL Hz A V EXT REV PU FWD MO
Explanation of Parameter Unit Parameter Unit FR-PU04 Monitor screen ● Wide backlit LCD (13 characters x 4 line display) ● Interactive parameter setting ● Help function, troubleshooting guidance ● 21 types of monitor (frequency, current, voltage, etc.
List of Parameters Function Basic functions Standard operation functions Output terminal functions 2nd functions Display functions Restart Supplementary functions 19 Pr. No. Name Setting range Minimum setting Default setting 0 - 30% 0.1% 6%/4%/3%/2%(Note 1) Maximum frequency 0 - 120Hz 0.01Hz 120Hz Minimum frequency 0 -120Hz 0.01Hz 0Hz 3 Base frequency 0 - 400Hz 0.01Hz 60Hz 4 Multi-speed setting (high speed) 0 - 400Hz 0.
List of Parameters Function Operation selection functions Motor constants VF 5 points adjustable 3rd functions Communications functions Pr. No.
List of Parameters Function PID control Commercial power supply switchover Pr. No. Display Supplementary functions Current detection Auxiliary functions Supplementary functions Restart Initial monitor User functions Terminal function selection Supplementary functions Program operations 21 Setting range Minimum setting 10, 11, 20, 21 --- Default setting 10 0.1 - 1000%, 9999 0.1% 100% 0.1 - 3600sec., 9999 0.1sec. 1 sec. 0 - 100%, 9999 0.1% 9999 0 - 100%, 9999 0.
List of Parameters Function Multi-speed operations Auxiliary functions Stop selection functions Power failure stop functions Function selection Load torque high speed frequency control Stop on contact control Brake sequence functions Supplementary functions Calibration functions Supplementary functions Pr. No. Setting range Minimum setting Default setting 232 Multi-speed setting (speed 8) Name 0 - 400Hz, 9999 0.01Hz 9999 233 Multi-speed setting (speed 9) 0 - 400Hz, 9999 0.
Applications ■ High-speed Crane or Lift ■ Line control < Intermediate axis control using draw control > High-power factor converter Power supply NFB Accessories MC Inverter FR-A500 Main unit Elevation motor B Inverter FR-A500 ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ Mechanical brakes Feed roll Drive roll Travel motor IM IM IM IM IM FR-A500 FR-A500 FR-A500 FR-A500 FR-A500 B Fork motor Inverter FR-A500 Ratio setting Power supply B NFB MC ● Thanks to the wide-range speed control, high-speed o
Protective Functions Except for the motor's electronic thermal relay, the following functions are provided for the protection of the inverter itself, but they may also function when the inverter breaks down. Function name Description When the inverter output current exceeds the rated current by more than approximately 200% during acceleration/deceleration or at constant speed, the protective circuit activates, halting inverter output.
Protective Functions ● Resetting Methods When a protective function is activated, it halts inverter output (the motor coasts to a halt). It is held in this state and will not restart unless it is reset. To reset the inverter, three methods are available: - shut off the power, then turn it on again; - switch the reset (RES) signal ON for at least 0.1 second, then OFF; - press the RESET key on the control panel or parameter unit.
Selecting Peripherals and Options Name (Model) Power facility capacity Functions & Applications, etc. Please select a power supply that is larger than the kVA values stated in the "Power facility capacity" column in the Ratings table (p.8). However, in the case where the value exceeds 1000kVA and the wiring length is 10m or less, install an FR-BEL DC reactor (or AC reactor) to balance the power supply.
List of Options Name Type 12-bit digital input FR-A5AX Application, specifications, etc. Digital output Outputs signals such as output frequency, output voltage, output current in analog form. Relay output FR-A5AR Outputs the inverter main unit's standard output signal at the relay contact. Orientation control, PLG feedback control FR-A5AP Built-in options (FR-A500 only) Common to all units In combination with a pulse encoder, can halt the main axis at the home position (orientation).
List of Options ■ Built-in Options Name 12-bit digital input Model FR-A5AX Digital output FR-A5AY Expansion analog output Relay output Orientation control, PLG feedback control FR-A5AR FR-A5AP Pulse train input Communications Computer link FR-A5NR Function ● Input interface for precise setting of the inverter's frequency using external 3-digit digital signals of BCD or binary code. ● Can also execute gain/offset adjustments.
List of Options ■ Standalone Options Name (Type) FR-A5CN Attachment for external mounting of cooling fin FR-A5CV Attachment for IP40 Specifications, configurations, etc. • By using this attachment, the cooling fin, which is the inverter's heatgenerating component, can be extended to the back of the housing plate. This makes it possible to radiate the inverter's heat to the back of the housing plate, allowing the control panel to be made more compact.
List of Options Name (Type) Dimentions (units: mm) Connecters External Dimensions Brake resistor for frequent braking operations FR-ABR-(H) K 400V class FR-ABR-0.4K FR-ABR-0.75K FR-ABR-2.2K (Note) FR-ABR-3.7K FR-ABR-5.5K FR-ABR-7.5K FR-ABR-H0.4K FR-ABR-H0.75K FR-ABR-H1.5K FR-ABR-H2.2K FR-ABR-H3.7K FR-ABR-H5.5K FR-ABR-H7.5K Resist- Approximate ance weight value (Ω) (kg) A B C D E F 10% 140 125 100 40 20 2.5 200 0.2 10% 215 200 175 40 20 2.5 100 0.
List of Options Dimentions (units: mm) H Weight (kg) M3.5 25 0.5 120 53 102 1.6 105 6 M4 25 0.7 130 65 110 1.6 115 6 M4 30 1.1 130 65 110 1.6 115 6 M4 30 1.2 150 75 102 2 135 6 M4 40 1.7 150 75 126 2 135 6 M5 40 2.2 150 75 126 2 135 6 M5 40 2.3 170 93 132 2.3 155 6 M5 50 3.1 170 93 170 2.3 155 6 M8 56 3.8 185 94 184 2.6 165 7 M8 56 5.1 185 119 182 2.6 165 7 M8 70 5.4 185 119 201 2.6 165 7 M8 70 6.7 195 136 215 2.
FR-BU Brake Units/FR-BR Resistor Units ● Brake units and resistor units are options that fully enhance the regenerative braking capability of the inverter, and should be used together. ● There are 6 types of brake unit as shown in the table below. They should be selected according to the required braking torque and deceleration time using the selection table. ● Brake units are equipped with a 7-segment LED which displays duty (%ED) and errors.
FR-BU Brake Units/FR-BR Resistor Units ■ External Dimensions ● Resistor unit ● Brake unit (unit: mm) W3 D1 H3 ±1 6 H1 ±3 H ±5 7.5 W3 2- C (H2) (unit: mm) øC Terminal block TB2 225 240 Terminal block TB1 C (35) W1 In the case of FR-BR-55K, H55K, eyebolts are used. W2 128 204 33 W1 W 7.
FR-HC High-power Factor Converters FR-RC Power Regenerating Converters FR-HC High-power Factor Converters ● Used for suppressing the high frequencies of the inverter's power supply, it achieves an equivalent capacity conversion coefficient of K5=0 under the "Japanese Harmonics Suppression Countermeasure Guidelines for Specific Customers." ● Improves input current waves into sine waves. ● Reduces input capacity by improving input power factor. ● Power source regenerative functions included as standard.
FR-HC High-power Factor Converters FR-RC Power Regenerating Converters ■ External Dimensions MC1 MC2 Reactor 1 (FR-HCL01) Inverter (FR-A500) High-power factor converter (FR-HC) External box (FR-HCB) Resistor R Reactor 2 (FR-HCL02) S T NFB MC Power Supply R R2 S S2 T T2 R3 R2 S2 MC S3 T3 T2 R3 R4 R4 P P S3 S4 S4 N N T3 T4 T4 RDY MRS RSO RES R Phase S detector Resistor Filter condenser U V W Motor SD SE R1 Control S1 source T Notes: 1.
Points to Note when Using and Selecting Units ■ For Maximum Safety • In order to use the equipment properly and safely, please be sure to read the manual before use. • This product was not designed or manufactured as equipment or a system to be used in situations that can affect or endanger human life.
Points to Note when Selecting Peripherals ■ Selecting and Installing No-fuse Breakers Please install a no-fuse breaker (NFB) on the incoming side to protect the wiring on the inverter's primary side.
Points to Note when Selecting Peripherals ■ Wiring Thickness and Distances When the wiring distance between the inverter and the motor is long, use a thick wire that will keep the drop in voltage in the main circuit cable to 2% or less, especially during low frequency output.
A500.A4 01.10.13 6:40 PM Page 2 Safety Warning To ensure proper use of the products listed in this catalog, please be sure to read the instruction manual prior to use. L-174-8-C3377-A NA9801 Printed in Japan (BUN) M New publication, effective Jan.1998 Specifications subject to change without notice.