Instruction manual

39
COMPUTER LINK FUNCTION
! FR-V500 series
No. Item
Instruction
Code
Description
1
Operation
mode
Read H7B
H0000: Computer link operation
H0001: External operation
H0002: PU operation
Write HFB
H0000: Computer link operation
H0001: External operation
H0002: PU operation
(Setting is enabled only during switch over mode (Pr.79="6").)
3 Run command HFA
H00 to HFF: Run command
0 0 0 0 0 0 1 0
b7 b0
0 0 0 0 0 0 0 0
b15
b0: -
b1: Forward rotation (STF)
b2: Reverse rotation (STR)*
b3: Low speed (RL/DI1)*
b4: Middle speed (RM/DI2)*
b5: High speed (RH/DI3)*
b6: Second function selection
(RT/DI4)*
b7: -
(For example 1)
[Example 1] H02 ......Forward
rotation
[Example 2] H00 ......Stop
*: The input signals marked * change with the settings of Pr. 180 to Pr. 183,
Pr. 187 (input terminal function selection). For details, refer to the Inverter
Instruction Manual.