Monitor
(3) Parameter list
(4) Parameter details
1. Trace status (Pr. 52, Pr. 190 to Pr. 192, Pr. 195)
The trace progress status, data output status and so on can be displayed on the DU/PU monitor and output to the
external output terminals.
Pr. 52 "PU/DU main display data selection"
When "38 (trace status)" is set in Pr. 52, the trace status is displayed on the FR-DU04-1/FR-PU04V.
Pr. 190 to Pr. 192, Pr. 195 "output terminal function selection"
When you set "40 (positive logic) and 140 (negative logic)" (Y40 signal: trace status) in Pr. 190 to Pr. 192 and
Pr. 195, the trace status is output from the output terminals.
Parameter Name Setting Range Factory Setting
52
PU/DU main display data
selection
0, 5 to 12, 17 to 20, 23,
24, 32 to 35, 38, 100
(5 to 12 are invalid for FR-PU04V)
0
190 DO1 terminal function selection 0 to 8, 10 to 16, 20, 25 to 27, 30 to
37, 39 to 44, 96 to 99,
100 to 108, 110 to 116, 120,
125 to 127, 130 to 137,
139 to 144, 196 to 199, 9999
0
191 DO2 terminal function selection 1
192 DO3 terminal function selection 2
195 ABC terminal function selection 99
520 Trace data CH1
1 to 12, 15 to 20, 23, 24,
32 to 36, 50 to 56, 9999
1 (speed)
521 Trace data CH2 2 (output current)
522 Trace data CH3 3 (output voltage)
523 Trace data CH4 4 (alarm display)
524 Trace data CH5 5 (set speed)
525 Trace data CH6 15 (input status (DI))
526 Trace data CH7 16 (output status (DO))
527 Trace data CH8 50 (U phase output current)
528 Trace data CH9 51 (V phase output current)
529 Trace data CH10 52 (W phase output current)
530 Sampling period 1 to 9998 1
531 Sampling count selection 1, 2, 3, 4 1
532 Trigger source selection 1 0 to 17, 22, 31 to 34, 9999 9999
533 Trigger source selection 2
0 to 23, 25, 26, 29 to 40,
46 to 48, 51, 52, 9999
9999
534 Trigger level 600% to 1400% (*) 1000%
535 Trigger slope selection 0, 1 0
536 Pre-trigger 0 to 100% 85%
538 Trace start/stop selection 0, 1 0
REMARKS
1. *: In Pr. 534, set the trigger level value (-400% to 400%) plus 1000.
2. When Pr. 538 = "1", you cannot write any parameter values to Pr. 520 to Pr. 536.
3. You can write parameter values to Pr. 520 to Pr. 536 and Pr. 538 if Pr. 77 = "0".
Monitor Display Trace Status
0Stop
1 During pre-trigger
2 Waiting for trigger
3 During trace
4 Trace completed
REMARKS
The trace status is displayed instead of the output voltage monitor of the DU/PU main monitor.
Y40 Signal
Trace Status
40
(positive logic)
140
(negative logic)
OFF ON Stop, trace completed, during data output, data output completed
ON OFF During pre-trigger, waiting for trigger, during trace