TRANSISTORIZED INVERTER INSTRUCTION MANUAL HIGH-DUTY BRAKE RESISTOR FR-ABR-(H)0.
Thank you for choosing the Mitsubishi transistorized inverter option unit. This instruction manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please read this manual carefully to use the equipment to its optimum. Please forward this instruction manual to the end user.
2. Fire Prevention CAUTION • • Mount the brake resistor on a non-combustible surface. Installing it directly on or near a combustible surface could cause a fire. Use the alarm signal to switch power off. A failure to do so can overheat the brake resistor due to a brake transistor failure etc., causing a fire. 3. Injury Prevention CAUTION • • Ensure that the cables are connected to the correct terminals. Otherwise, damage, etc. may occur.
INSTALLATION INSTRUCTIONS FOR COMPLIANCE WITH UL Install the high-duty brake resistor FR-ABR as follows: • • • • The brake resistor may be mounted horizontally or vertically, depending on a suitable surface location. When the brake resistor is mounted externally to the enclosure housing the inverter, install a solid Type 1 enclosure at least 8 times the volume size of the brake resistor that incorporates mesh or perforated steel type ventilation openings at each end of the resistor.
1. UNPACKING AND CHECKING THE MODEL AND APPLICABLE INVERTERS Take the brake resistor out of the package and confirm that the product is as you ordered and intact. Type FR - ABR - 0.4 K Indicate capacity (kW) Symbol Voltage class 200V class No H 400V class (For the FR-ABR-H15K, a terminal block for connecting resistors is enclosed as two resistors need to be connected in parallel.) FR-ABR-15K is indicated on the resistor. (A type name indicated on the package is different.
400V Class High-Duty Brake Resistor Model Applicable Inverter Models FR-ABR-H0.4K FR-A540-0.4K(-**) FR-E540-0.4K(C)(-**) FR-A044-0.4K(-**) FR-A740-0.4K(-**) FR-ABR-H0.75K FR-A540-0.75K(-**) FR-E540-0.75K(C)(-**) FR-A044-0.75K(-**) FR-A740-0.75K(-**) FR-ABR-H1.5K FR-A540-1.5K(-**) FR-E540-1.5K(C)(-**) FR-V540-1.5K(-**) FR-A044-1.5K(-**) FR-A740-1.5K(-**) FR-ABR-H2.2K FR-A540-2.2K(-**) FR-E540-2.2K(C)(-**) FR-V540-2.2K(-**) FR-A044-2.2K(-**) FR-A740-2.2K(-**) FR-ABR-H3.7K FR-A540-3.
2. GENERAL INSTRUCTIONS FOR INSTALLATION (For compliance with UL standard, refer to page A-3.) • Never mount the resistor near wood, paper or any other combustible material. Doing so can cause a fire. • To prevent burns, do not install the resistor in a place where it is readily accessible. If it is easily accessible, mount in a well-ventilated enclosure (e.g. punched metal), suitable for the environment. • Mount the resistor carefully so that the leads do not come from the top of the resistor.
3. INSTRUCTIONS FOR WIRING When the regenerative brake transistor is damaged, the wiring sequence as shown in the following diagrams is recommended to prevent overheating and burnout of the brake resistor. Inverter MC R Power Supply P S PX T PR T(*2) High-duty brake resistor (FR-ABR) R ON ON MC C S PX T PR Thermal relay High-duty brake resistor (FR-ABR) (OCR)(*3) R Disconnect jumper.
• Connect the leads of the high-duty brake resistor to the P and PR terminals of the inverter. When using the FR-ABR-15K, 22K, connect two high-duty brake resistors (18Ω) in parallel. When using the FRABR-H15K, connect two high-duty brake resistors (18Ω) in series using a terminal block enclosed. FR-ABR-H15K brake resistor To the inverter PR terminal Terminal block enclosed To the inverter P terminal (To the thermal relay T3 terminal.
5. SPECIFICATIONS Permissible duty and torque Item FR-ABR- (200V Class) FR-ABR-H (400V Class) 0.75 0.4K 0.75 K 2.2K 3.7K 5.5K 7.5K 11K 15K 22K 0.4K K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K 22K Braking 150% 100% 5s 100% 5s torque 5s Permissib 10%ED 6%ED 10%ED 6%ED le duty* * The permissible duty represents the braking capability including the motor loss.The actual duty of the resistor is slightly lower than that. 6. OUTLINE DIMENSIONS FR-ABR-0.4K to 7.5K, H0.4K to H7.
FR-ABR-11K, 15K, 22K, H11K, H15K, H22K 700+200 W W1 ±1 W2 B1 A1 80.5 ±1 5.3 φd1 A1 A2 B2 Glass-braided cable 2.0mm2 white φd2 A2 2.5 50 100 Dimensions (Unit: mm) Brake Resistor Model Resistance (Ω) Crimping Terminal (Unit: mm) A1 A2 W W1 W2 B1 d1 B2 d2 400 385 360 13 12 6.4 9.5 5.3 200V FR-ABR-15K*1 Class FR-ABR-22K*3 300 285 260 18 12 8.4 12 8.4 400 385 360 13 12 8.4 12 8.4 FR-ABR-H11K 400V FR-ABR-H15K*2 Class FR-ABR-H22K*4 400 385 360 52 12 6.4 9.
7. BRAKING CAPABILITIES 7.1 Continuous Permissible Power Continuous Resistance Permissible Power FR-ABR-0.4K FR-ABR-0.75K FR-ABR-2.2K FR-ABR-3.7K FR-ABR-5.5K FR-ABR-7.5K FR-ABR-11K FR-ABR-15K 200Ω 100Ω 60Ω 40Ω 25Ω 20Ω 13Ω 9Ω*1 60W 80W 120W 155W 185W 340W 560W 805W FR-ABR-22K 6.5Ω*1 1120W Continuous Resistance Permissible Power Model 400V Class 200V Class Model 1200Ω 700Ω 350Ω 250Ω 150Ω 110Ω 75Ω 52Ω FR-ABR-H0.4K FR-ABR-H0.75K FR-ABR-H1.5K FR-ABR-H2.2K FR-ABR-H3.7K FR-ABR-H5.5K FR-ABR-H7.
REVISIONS *The manual number is given on the bottom left of the back cover. Print Date *Manual Number Nov., 1998 Mar., 2001 IB(NA)-66891-A IB(NA)-66891-B Revision First edition Partial Additions • Applicable inverters • Instructions for wiring Apr., 2002 IB(NA)-66891-C Additions FR-ABR-11K, FR-ABR-15K Aug., 2002 IB(NA)-66891-D Additions FR-ABR-H11K, FR-ABR-H15K Partial Addition Instructions for wiring Oct., 2003 IB(NA)-66891-E Additions UL compliance Mar.