Instruction manual

PARAMETERS
102
4.2.22 PWM carrier frequency (Pr. 72, Pr. 240)
Pr. 72 "PWM frequency selection"
Pr. 240 "Soft-PWM setting"
You can change the motor tone.
!
By parameter setting, you can select Soft-PWM control which changes the motor
tone.
!
Soft-PWM control changes motor noise from a metallic tone into an unoffending
complex tone.
Parameter
Number
Factory
Setting
Setting
Range
Remarks
72 1 0 to 15
0 : 0.7kHz,
15 : 14.5kHz
240 1 0, 1 1: Soft-PWM valid
<Setting>
"
Refer to the following list and set the parameters:
Parameter
Number
Setting Description
72 0 to 15
PWM carrier frequency can be changed.
The setting displayed is in [kHz].
Note that 0 indicates 0.7kHz and 15 indicates 14.5kHz.
0 Soft-PWM invalid
240
1 When any of "0 to 5" is set in Pr. 72, Soft-PWM is made valid.
Note:1. Note that when the inverter is run at the ambient temperature above 40
°
C
with a 2kHz or higher value set in Pr. 72, the rated output current of the
inverter must be reduced. (Refer to page 166.)
2. An increased PWM frequency will decrease motor noise but noise and
leakage current will increase. Take proper action (refer to pages 36 to 40).