Instruction manual

65
3
OPERATION/CONTROL
(3) Combined operation mode 1 (Pr. 79 "operation mode selection" = 3)
(4) Combined operation mode 2 (Pr. 79 "operation mode selection" = 4)
The start signal is an external signal.
The frequency setting signal
is set using the operation panel or
parameter unit.
Use Pr. 146 "frequency setting command selection" to choose
the way to make frequency setting from the operation panel. For
the Pr. 146 setting method, refer to page 71.
Pr. 146 = 0: Frequency setting using the built-in frequency
setting potentiometer (factory setting)
Pr. 146 = 1: Digital frequency setting using key
Start signal .......................Switch, relay, etc.
Operation unit ..................Operation panel (equipped as
standard) or parameter unit (FR-
PU04)
Connection cable .............Refer to (1) PU operation mode.
FR-E5P (option) ...............Refer to (1) PU operation mode.
The start signal
is entered from the operation command key
of the operation panel.
The frequency setting signal
is set using the external
frequency setting signal.
Frequency setting signal ..0 to 5V, 0 to 10V or 4 to 20mA
DC signals from an external
potentiometer or from outside
the inverter
Operation unit ..................Operation panel (equipped as
standard) or parameter unit
(FR-PU04)
Connection cable .............Refer to (1) PU operation mode.
FR-E5P (option) ...............Refer to (1) PU operation mode.
/