4.2.15 Up-to-frequency sensitivity (Pr. 41)
Pr. 41 "up-to-frequency sensitivity"
The ON range of the up-to-frequency signal
(SU) output when the output frequency reaches
the running frequency can be adjusted between 0
and
±
100% of the running frequency.
This parameter can be used to ensure that the
running frequency has been reached or used as the operation start signal etc. for
related equipment.
Parameter
Number
Factory
Setting
Setting
Range
41 10% 0 to 100%
OFF
ON
Pr.41
O
utput si
g
nal
S
U
OFF
Time
Output frequency (Hz)
Running frequency
Adjustable range
!
Use any of Pr. 190 to Pr. 192 to allocate the terminal (remote input) used for SU
signal output.
!
Refer to page 132 for Pr. 190 to Pr. 192 (output terminal (remote input) function
selection).
Note: When terminal (remote input) assignment is changed using Pr. 190 to Pr.
192, the other functions may be affected. Check the functions of the
corresponding terminals (remote input) before making setting.
4.2.16 Output frequency detection (Pr. 42, Pr. 43)
Pr. 42 "output frequency detection"
Pr. 43 "output frequency detection for
reverse rotation"
The output frequency detection signal (FU) is output when the output frequency
reaches or exceeds the setting. This function can be used for electromagnetic brake
operation, open signal etc.
"
You can also set the detection of the frequency used exclusively for reverse rotation.
This function is effective for switching the timing of electromagnetic brake operation
between forward rotation (rise) and reverse rotation (fall) during vertical lift operation etc.
Parameter Number Factory Setting Setting Range Remarks
42 6Hz 0 to 400Hz
43 9999 0 to 400Hz, 9999
9999: Same as Pr. 42
setting