FR-E700-NC INVERTER FR-E700 INSTRUCTION MANUAL (Applied) CC-Link communication function INVERTER FR-E720-0.1KNC to 15KNC FR-E740-0.4KNC to 15KNC FR-E720S-0.1KNC to 2.2KNC OUTLINE 1 WIRING 2 PRECAUTIONS FOR USE OF THE INVERTER 3 CC-LINK COMMUNICATION FUNCTION IB(NA)-0600402ENG-A (1111)MEE Printed in Japan Specifications subject to change without notice.
Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (Applied) provides instructions for advanced use of the FR-E700 series CC-Link type inverters. Incorrect handling might cause an unexpected fault. Before using the inverter, always read this Instruction Manual and the Instruction Manual (Basic) [IB-0600401ENG] packed with the product carefully to use the equipment to its optimum performance.
(5) Emergency stop (2) Wiring CAUTION z Do not install a power factor correction capacitor or surge suppressor/capacitor type filter on the inverter output side. These devices on the inverter output side may be overheated or burn out. z The connection orientation of the output cables U, V, W to the motor affects the rotation direction of the motor. (3) Trial run CAUTION z Before starting operation, each parameter must be confirmed and adjusted.
CONTENTS OUTLINE 1.1 Product checking and parts identification ......................................... 2 1.2 Inverter and peripheral devices .......................................................... 3 1.2.1 1.3 Peripheral devices .......................................................................................................................... 4 Removal and reinstallation of the cover............................................. 5 1.3.1 Front cover ........................................
3.2 Installation of power factor improving reactor................................ 39 3.3 Power-OFF and magnetic contactor (MC) ........................................ 40 3.4 Inverter-driven 400V class motor ..................................................... 41 3.5 Precautions for use of the inverter .................................................. 42 3.6 Failsafe of the system which uses the inverter............................... 44 4 CC-LINK COMMUNICATION FUNCTION 4.
Programming example for parameter writing ............................................................................... 71 4.7.7 Programming example for setting the running frequency ............................................................. 72 4.7.8 Programming example for fault record reading ............................................................................ 73 4.7.9 Programming example for resetting the inverter at inverter error .................................................
5.8.1 Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47) .......................................................................... 126 5.8.2 Load pattern selection (Pr. 14) .................................................................................................. 128 5.9 Frequency setting with input signals ............................................ 130 5.9.1 Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)........... 130 5.9.
5.16 Operation setting at fault occurrence ........................................... 188 5.16.2 Input/output phase loss protection selection (Pr. 251, Pr. 872) ................................................. 190 5.16.3 Earth (ground) fault detection at start (Pr. 249) ......................................................................... 190 5.17 Energy saving operation................................................................. 191 5.17.1 Optimum excitation control (Pr. 60) ...................
6.2 List of fault or alarm indications .................................................... 233 6.3 Causes and corrective actions....................................................... 234 6.4 Correspondences between digital and actual characters ............ 243 6.5 Check first when you have a trouble.............................................. 244 6.5.1 Motor does not start....................................................................................................................
Common specifications................................................................... 268 8.3 Outline dimension drawings............................................................ 269 APPENDIX 273 Appendix 1 Main differences with the FR-E500(N) CC-Link model .......................... 274 Appendix 2 Specification change ................................................................................ 275 Appendix 2-1 SERIAL number check ...............................................................
MEMO VIII
1 OUTLINE This chapter explains the "OUTLINE" for use of this product. Always read the instructions before using the equipment. 1.1 1.2 1.3 1.4 1 Product checking and parts identification ................................. 2 Inverter and peripheral devices................................................... 3 Removal and reinstallation of the cover ..................................... 5 Installation of the inverter and enclosure design ...................... 8 2 Inverter ...............
Product checking and parts identification 1.1 Product checking and parts identification Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact. zInverter model FR - E740 - 2.2 KNC No.
Inverter and peripheral devices Inverter and peripheral devices Programmable controller Load the "QJ61BT11N", "LJ61BT11", "AJ61QBT11", "A1SJ61QBT11", "AJ61BT11" or "A1SJ61BT11" CC-Link system master/local module on the main or extension base unit having the programmable controller CPU used as the master station. AC power supply Use within the permissible power supply specifications of the inverter.
Inverter and peripheral devices 1.2.1 Peripheral devices Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices: Applicable Inverter Single-Phase 200V Three-Phase 400V Three-Phase 200V Model Output (kW) Magnetic Contactor (MC) Reactor ∗3 Reactor connection without with FR-HAL FR-HEL FR-E720-0.1KNC 0.1 5A 5A S-N10 S-N10 0.4K ∗4 0.
Removal and reinstallation of the cover 1.3 1.3.1 Removal and reinstallation of the cover Front cover FR-E720-3.7KNC or lower, FR-E740-7.5KNC or lower, FR-E720S-0.1KNC to 2.2KNC zRemoval (Example of FR-E720-0.75KNC) Remove the front cover by pulling it toward you in the direction of arrow. 1 zReinstallation (Example of FR-E720-0.75KNC) OUTLINE To reinstall, match the cover to the inverter front and install it straight.
Removal and reinstallation of the cover FR-E720-5.5KNC or higher, FR-E740-11KNC or higher zRemoval (Example of FR-E720-5.5KNC) 1) Loosen the installation screws of the front cover 1. 2) Remove the front cover 1 by pulling it toward you in the direction of arrow. 3) Remove the front cover 2 by pulling it toward you in the direction of arrow. 1) 2) 3) Front cover 2 Front cover 1 Installation screws zReinstallation (Example of FR-E720-5.
Removal and reinstallation of the cover 1.3.2 Wiring cover zRemoval and reinstallation The cover can be removed easily by pulling it toward you. To reinstall, fit the cover to the inverter along the guides. FR-E720-1.5KNC to 3.7KNC FR-E720-0.1KNC to 0.75KNC FR-E740-0.4KNC to 3.7KNC FR-E720S-0.1KNC to 0.4KNC FR-E720S-0.75KNC to 2.2KNC Guide Guide Wiring cover Wiring cover 1 Example of FR-E740-3.7KNC FR-E720-5.5KNC to 15KNC FR-E740-5.5KNC, 7.5KNC OUTLINE Example of FR-E720-0.
Installation of the inverter and enclosure design 1.4 Installation of the inverter and enclosure design When an inverter enclosure is to be designed and manufactured, heat generated by contained equipment, etc., the environment of an operating place, and others must be fully considered to determine the enclosure structure, size and equipment layout. The inverter unit uses many semiconductor devices.
Installation of the inverter and enclosure design (3) Dust, dirt, oil mist Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due to moisture absorption of accumulated dust and dirt, and in-panel temperature rise due to clogged filter. In the atmosphere where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated insulation and short circuit in a short time.
Installation of the inverter and enclosure design 1.4.2 Cooling system types for inverter enclosure From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-panel temperature lower than the permissible temperatures of the in-panel equipment including the inverter. The cooling systems are classified as follows in terms of the cooling calculation method.
Installation of the inverter and enclosure design 1.4.3 Installation of the inverter Enclosure surface mounting Remove the front cover and wiring cover to fix the inverter to the surface. (Remove the covers in the directions of the arrows.) FR-E720-0.1KNC to 0.75KNC FR-E720S-0.1KNC to 0.4KNC FR-E720-1.5KNC or higher FR-E740-0.4KNC or higher FR-E720S-0.
Installation of the inverter and enclosure design (2) Above inverter Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be heat resistant. (3) Arrangement of multiple inverters When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown in the right figure (a).
2 WIRING This chapter describes the basic "WIRING" for use of this product. Always read the instructions before using the equipment. 2.1 2.2 2.3 2.4 1 2 Wiring............................................................................................. 14 Main circuit terminal specifications ............................................ 15 Control circuit specifications ...................................................... 20 Connection of stand-alone option unit ......................................
Wiring 2.1 2.1.1 Wiring Terminal connection diagram Sink logic Main circuit terminal Control circuit terminal *1. DC reactor (FR-HEL) When connecting a DC reactor, remove the jumper across P1 and P/+.
Main circuit terminal specifications 2.2 2.2.1 Main circuit terminal specifications Specification of main circuit terminal Terminal Symbol Terminal Name Description R/L1, S/L2, AC power input Connect to the commercial power supply. U, V, W Inverter output Connect a three-phase squirrel-cage motor. P/+, PR Brake resistor connection PR. P/+, N/- Brake unit connection Connect a brake unit (FR-BU2).
Main circuit terminal specifications Three-phase 400V class FR-E740-0.4KNC to 3.7KNC FR-E740-5.5KNC, 7.5KNC Jumper Jumper N/- P/+ R/L1 S/L2 T/L3 R/L1 S/L2 T/L3 P/+ PR N/PR IM IM Power supply Power supply Motor Motor FR-E740-11KNC, 15KNC N/- P/+ PR R/L1 S/L2 T/L3 Jumper IM Power supply Motor Single-phase 200V class FR-E720S-0.1KNC to 0.4KNC FR-E720S-0.75KNC to 2.
Main circuit terminal specifications 2.2.3 (1) Cables and wiring length Applicable cable size Select the recommended cable size to ensure that a voltage drop will be 2% or less. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency. The following table indicates a selection example for the wiring length of 20m.
Main circuit terminal specifications NOTE Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage. Use crimping terminals with insulation sleeve to wire the power supply and motor.
Main circuit terminal specifications (3) Total wiring length The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below. Pr. 72 PWM frequency selection Setting (carrier frequency) 0.1K 0.2K 0.4K 0.75K 1.5K 2.2K 3.7K or higher 200V class 200m 200m 300m 500m 500m 500m 500m 400V class - - 200m 200m 300m 500m 500m 2 to15 200V class 30m 100m 200m 300m 500m 500m 500m (2kHz to 14.
Control circuit specifications 2.3 Control circuit specifications 2.3.1 Control circuit terminal indicates that terminal functions can be selected using Pr.190 RX2 (terminal Y0) function selection. (Refer to page 167). (1) Input signal Terminal Type 24V external power supply Symbol Rated Specifications 24V external power supply Link communication continues with the input from the 24V external power supply.
Control circuit specifications 2.3.2 (1) Wiring of control circuit Control circuit terminal model Recommend wire size: 0.3mm2 to 0.75mm2 +24 SD S1 S2 PC Y0 SE (2) Wiring method z Wiring Use a blade terminal and a wire with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of the wire and apply directly. Insert the blade terminal or the single wire into a socket of the terminal. 1) Strip off the sheath about the size below.
Control circuit specifications 3) Insert the wire into a socket. When using a single wire or stranded wire without a blade terminal, push an open/close button all the way down with a flathead screw driver, and insert the wire. Open/close button Flathead screwdriver NOTE When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or wires. Place the flathead screwdriver vertical to the open/close button.
Control circuit specifications 2.3.3 Connecting the 24V external power supply CC-Link communication between the master module and the inverter can be continued while the main power circuit is OFF if the 24V external power supply is connected across terminals +24 and SD. When the main circuit power supply is turned ON, the power supply changes from the 24V external power supply to the main circuit power supply. (1) Specification of the applied 24V external power supply Input voltage 23.5 to 26.
Control circuit specifications 2.3.4 (1) Safety stop function Description of the function The terminals related to the safety stop function are shown below. Terminal Symbol Between S1 and PC / S2 and PC Open: In safety stop state. Short: Other than safety stop state. For input of safety stop channel 1. S2 ∗1 For input of safety stop channel 2. PC ∗1 Common terminal for terminal S1 and S2.
Control circuit specifications (3) Safety stop function operation Input Input signal power S1-PC S2-PC OFF — — ON Short Short Open Open Short Open Internal safety circuit∗1 Output signal SAFE∗3 SAFE2∗3 Inverter operation enable signal — OFF OFF No failure OFF ON Output shutoff (Safe state) Drive enabled Failure OFF OFF Output shutoff (Safe state) No failure ∗2 ON ON Output shutoff (Safe state) Failure OFF OFF Output shutoff (Safe state) Open Failure OFF OFF Output s
Connection of stand-alone option unit 2.4 Connection of stand-alone option unit The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual. 2.4.1 Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR) (0.
Connection of stand-alone option unit It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal relay as shown below, to prevent overheat and burnout of the brake resistor (MRS type, MYS type) and high duty brake resistor (FR-ABR) in case the regenerative brake transistor is damaged. (The brake resistor cannot be connected to the 0.1K and 0.2K.
Connection of stand-alone option unit 2.4.2 Connection of the brake unit (FR-BU2) Connect the brake unit (FR-BU2(-H)) as shown below to improve the braking capability at deceleration. If the transistors in the brake unit should become faulty, the resistor can be unusually hot. To prevent unusual overheat and fire, install a magnetic contactor on the inverter's input side to configure a circuit so that a current is shut off in case of fault.
Connection of stand-alone option unit (2) Connection example with the FR-BR(-H) type resistor ON OFF ∗2 T MC MC FR-BR MCCB MC Three-phase AC power supply R/L1 U Motor S/L2 V IM T/L3 W P TH1 PR TH2 ∗3 FR-BU2 Inverter PR ∗1 ∗4 P/+ P/+ N/- N/- A ∗1 B C BUE ∗5 ∗3 SD 5m or less ∗1 ∗2 ∗3 ∗4 ∗5 Connect the inverter terminals (P/+ and N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other.
MEMO 30
3 PRECAUTIONS FOR USE OF THE INVERTER This chapter explains the "PRECAUTIONS FOR USE OF THE 1 INVERTER" for use of this product. Always read the instructions before using the equipment. 3.1 EMC and leakage currents .......................................................... 32 3.2 Installation of power factor improving reactor ......................... 39 3.3 Power-OFF and magnetic contactor (MC) ................................. 40 3.4 Inverter-driven 400V class motor ...........................
EMC and leakage currents 3.1 EMC and leakage currents 3.1.1 Leakage currents and countermeasures Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following measures.
EMC and leakage currents (3) Selection of rated sensitivity current of earth (ground) leakage current breaker When using the earth leakage current breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency.
EMC and leakage currents 3.1.2 EMC measures Some electromagnetic noises enter the inverter to malfunction it and others are radiated by the inverter to malfunction peripheral devices. Though the inverter is designed to have high immunity performance, it handles low-level signals, so it requires the following basic techniques. Also, since the inverter chops outputs at high carrier frequency, that could generate electromagnetic noises.
EMC and leakage currents Propagation Path Measures When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when their signal cables are run near the inverter, the devices may be malfunctioned by air-propagated electromagnetic noises. The following measures must be taken: Install easily affected devices as far away as possible from the inverter.
EMC and leakage currents 3.1.3 Power supply harmonics The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path. Take the following countermeasure suppression techniques.
EMC and leakage currents 3.1.4 Harmonic Suppression Guidelines in Japan Harmonic currents flow from the inverter to a power receiving point via a power transformer. The Harmonic Suppression Guidelines was established to protect other consumers from these outgoing harmonic currents. The three-phase 200V input specifications 3.7kW or lower (single-phase 200V power input model 2.
EMC and leakage currents Table 4 Harmonic Contents (Values at the fundamental current of 100%) Three-phase bridge (Capacitor smoothing) Single-phase bridge (Capacitor smoothing) Reactor 5th 7th 11th 13th 17th 19th 23rd 25th Not used Used (AC side) Used (DC side) Used (AC, DC sides) Not used Used (AC side) * 65 38 30 28 50 6.0 41 14.5 13 9.1 24 3.9 8.5 7.4 8.4 7.2 5.1 1.6 7.7 3.4 5.0 4.1 4.0 1.2 4.3 3.2 4.7 3.2 1.5 0.6 3.1 1.9 3.2 2.4 1.4 0.1 2.6 1.7 3.0 1.6 - 1.8 1.3 2.2 1.
Installation of power factor improving reactor 3.2 Installation of power factor improving reactor When the inverter is connected near a large-capacity power transformer (500kVA or more) or when a power capacitor is to be switched over, an excessive peak current may flow in the power input circuit, damaging the converter circuit. To prevent this, always install an optional reactor (FR-HAL, FR-HEL).
Power-OFF and magnetic contactor (MC) 3.3 (1) Power-OFF and magnetic contactor (MC) Inverter input side magnetic contactor (MC) On the inverter input side, it is recommended to provide an MC for the following purposes. (Refer to page 4 for selection.) 1) To release the inverter from the power supply when the fault occurs or when the drive is not functioning (e.g. emergency stop operation).
Inverter-driven 400V class motor 3.4 Inverter-driven 400V class motor In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially for a 400V class motor, the surge voltage may deteriorate the insulation.
Precautions for use of the inverter 3.5 Precautions for use of the inverter The FR-E700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following points. (1) Use crimping terminals with insulation sleeve to wire the power supply and motor. (2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter.
Precautions for use of the inverter (12) Across terminals P/+ and PR, connect only an external regenerative brake discharging resistor. Do not connect a mechanical brake. The brake resistor can not be connected to the 0.1K or 0.2K. Leave terminals P/+ and PR open. Also, never short between these terminals. (13) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Failsafe of the system which uses the inverter 3.6 Failsafe of the system which uses the inverter When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc.
Failsafe of the system which uses the inverter 4) Checking the motor operating status by the start signal input to the inverter and inverter output current detection signal. The output current detection signal (Y12 signal) is output when the inverter operates and currents flows in the motor. Check if Y12 signal is output when inputting the start signal to the inverter (forward signal is STF signal and reverse signal is STR signal).
MEMO 46
CC-LINK COMMUNICATION FUNCTION 4 This chapter explains the "CC-Link communication 1 function" for use of this product. Always read the instructions before using the equipment. 2 4.1 CC-Link communication specifications...................................... 48 4.2 CC-Link version ............................................................................ 48 4.3 Wiring for CC-Link communication............................................. 49 4.4 Function overview .............................
CC-Link communication specifications 4.1 CC-Link communication specifications Type Power supply Number of units connected Station type Number of stations Built-in to the inverter, one-touch connector connection, online connector (T type (2 to 1)) supported Supplied from the inverter or the external 24VDC power supply 42 units max. (Refer to page 106 for the number of stations occupied.) May be used with other equipment. Remote device station CC-Link Ver. 1: occupies one station CC-Link Ver.
Wiring for CC-Link communication 4.3 Wiring for CC-Link communication 4.3.1 (1) System configuration example Programmable controller side Mount the "QJ61BT11N", "LJ61BT11", "AJ61QBT11", "A1SJ61QBT11", "AJ61BT11" or "A1SJ61BT11" "CC-Link system master/local module" on the main or extension base unit having the programmable controller CPU used as the master station.
Wiring for CC-Link communication 4.3.2 Connection of several inverters An inverter can join the link system as a CC-Link remote device station, and such device stations can be controlled and monitored with a user program of a programmable controller. These devices can be useful components of an automated factory. Connect shielding wires of the CC-Link dedicated cable to "SLD" of each unit.
Wiring for CC-Link communication 4.3.3 Connection cable and plug In the CC-Link system, use CC-Link dedicated cables. If the cable used is other than the CC-Link dedicated cable, the performance of the CC-Link system is not guaranteed. For the specifications of the CC-Link dedicated cable, refer to the website of the CC-Link Partner Association. Website of the CC-Link Partner Association http://www.cc-link.
Wiring for CC-Link communication (4) Crimping the plug cover Push the plug cover onto the plug with a tool such as pliers. After crimping, check that the plug cover is securely snapped into the plug as shown in the right figure. REMARKS Misaligned latches between the plug cover and the plug may keep the cover lifted. The plug cover is not sufficiently crimped in this condition. Push the plug cover until it snaps into the plug. 4.3.
Wiring for CC-Link communication 4.3.5 Unit replacement while online Connect an online communication connector to the CC-Link communication connector. The online communication connector enables a unit replacement without interrupting the communication. Always connect the online communication connector to CONA (front side) of the CC-Link communication connector. (Do not connect it to CONB (back side) of the CC-Link communication connector.
Function overview 4.4 Function overview 4.4.1 Function block diagram Using function blocks, this section explains I/O data transfer to/from an inverter in CC-Link: • Link refresh is continuously executed between the master station and inverter in the CC-Link system at intervals of 1.
Function overview 4.4.2 Output from the inverter to the network Main items which can be output from the inverter to the master and their descriptions are explained below. Item Description Inverter status monitor The output terminal status of the inverter can be monitored. Output frequency monitor The output frequency can be monitored. Output current monitor The output current can be monitored. Output voltage monitor The output voltage can be monitored.
I/O signal list 4.5 I/O signal list 4.5.1 (1) I/O signals when CC-Link Ver. 1 one station (FR-E500 series compatible) is occupied (Pr. 544 = "0") Remote I/O (32 points fixed) Device No. Signal RYn0 RYn1 Forward rotation command (STF signal) *2 Reverse rotation command (STR signal) *2 High-speed operation command RYn2 Refer to Page Device No.
I/O signal list 4.5.2 (1) I/O signals when CC-Link Ver. 1 one station is occupied (Pr. 544 = "1") Remote I/O (32 points) Same as when Pr. 544 = "0" (Refer to page 56) (2) Remote register Description Address RWwn RWwn+1 RWwn+2 Upper 8 Bits Lower 8 Bits Monitor code 2 Monitor code 1 Set frequency (0.
I/O signal list 4.5.4 I/O signals when CC-Link Ver. 2 quadruple setting is selected (Pr. 544 = "14") (1) Remote I/O (32 points) Same as when Pr. 544 = "0" (Refer to page 56) (2) Remote register Address RWwn RWwn+1 RWwn+2 RWwn+3 RWwn+4 RWwn+5 RWwn+6 RWwn+7 RWwn+8 RWwn+9 RWwn+A Description Upper 8 Bits Lower 8 Bits Monitor code 2 Monitor code 1 Set frequency (0.
I/O signal list 4.5.5 (1) I/O signals when CC-Link Ver. 2 octuple setting is selected (Pr. 544 = "18") Remote I/O (32 points) Same as when Pr. 544 = "0" (Refer to page 56) Remote register Description Address RWwn RWwn+1 RWwn+2 RWwn+3 RWwn+4 RWwn+5 RWwn+6 RWwn+7 RWwn+8 RWwn+9 RWwn+A RWwn+B RWwn+C RWwn+D RWwn+E RWwn+F Upper 8 Bits Lower 8 Bits Refer to Description Address Page Monitor code 2 Monitor code 1 Set frequency (0.
Details of I/O signals Details of I/O signals 4.6 The following device numbers are for the station 1. For the stations 2 and later, the device numbers are different. (Refer to the master module manual for the correspondence between device numbers and station numbers.) 4.6.1 (1) Details of remote I/O signals Output signals (master module to inverter) The output signals from the master module are indicated. (Input signals to the inverter) Device No.
Details of I/O signals (2) Input signals (inverter to master module) The input signals to the master module are indicated. (Output signals from the inverter) Device No. RX0 Signal Forward running Description OFF: Other than forward running (during stop or reverse rotation) ON: Forward running OFF: Other than reverse running (during stop or forward rotation) RX1 Reverse running RX2 Turning ON the signal activates the function assigned to Pr. 190.
Details of I/O signals 4.6.2 (1) Details of remote registers Remote register (master module to inverter) Remote register definition Device No. RWw0 Signal Monitor code1/ Monitor code2 Description Set the monitor code to be monitored (Refer to page 66). By setting "1" in RYC after setting, the specified monitored data is stored in RWr0/RWr1. ⋅ Specify the set frequency or machine speed. At this time, whether to write to RAM or EEPROM is decided with the RYD and RYE settings.
Details of I/O signals (2) Remote register (inverter to master module) Remote register definition Device No. Signal Description When "1" is set in RYC, the specified monitored data is set to the lower 8 bits of the monitor RWr0 First monitor value code (RWw0). When Pr. 37 Speed display ≠ 0 and output frequency or set frequency monitor is set for monitor code (RWw0), machine speed setting (1 unit) is monitored.
Details of I/O signals (3) Instruction codes Instruction code definition Set the instruction code using a remote register (RWw). (Refer to page 62.) The definition read by the instruction code is stored in the remote register (RWr). (Refer to page 63.) Item Read / Write Code Number Read H7B Operation mode Write HFB Output frequency *1 Read H6F Output current Read H70 Output voltage Read H71 Special monitor Read H72 Special monitor selection No.
Details of I/O signals Item Inverter reset Link parameter extended setting *5 Read / Write Code Number Write HFD H9696: Resets the inverter. Read H7F Write HFF Parameter settings are switched according to the H00 to H09 settings. Refer to instruction codes in the parameter list on page 84 for the setting value details. Description ∗1 When "100" is set in Pr. 52 DU/PU main display data selection, set frequency is monitored during a stop and output frequency is monitored during running.
Details of I/O signals (4) Monitor codes Monitored items can be selected with the special monitor selection No. of the instruction code and the remote registers, RWw0 and RWw4 to 7. Divide the monitor code (RWw0) into half to select the first monitor description (RWr0) from the lower 8 bits and the second monitor description (RWr1) from the upper 8 bits. Refer to page 176 for the details of monitors. REMARKS • When Pr.
Programming examples Programming examples 4.7 This chapter provides programming examples which control the inverter with sequence programs.
Programming examples (3) Remote I/O The relation between the device of the programmable controller CPU and remote I/O (RX, RY) of the remote device station is as follows: The devices used actually are indicated in shaded regions.
Programming examples 4.7.1 Programming example for reading the inverter status The following program turns ON Y00 of the output unit when station 1 inverter is running. X0 X0F M0 X1002 X1 SW80.
Programming examples 4.7.3 Programming example for setting the operation commands The following program gives a forward command and middle speed command to station 1 inverter X0 X0F M0 X20 X1 SW80.
Programming examples 4.7.5 Programming example for parameter reading The following program reads Pr. 7 Acceleration time of station 1 inverter to D1. ⋅ Pr. 7 Acceleration time reading code number: H07 (hexadecimal) ⋅ Refer to the parameter list on page 84 to find out the code number of each parameter. ⋅ The reply code at the time of instruction code execution is set to D2. (Refer to page 63) X0 X0F M0 X20 X1 SW80.
Programming examples 4.7.7 Programming example for setting the running frequency 1) The following program example changes the running frequency of station 1 inverter to 50.00Hz Set frequency: K5000 decimal The reply code at the time of instruction code execution is set to D2. (Refer to page 63) X0 X0F M0 X20 X1 SW80.0 0 M0 7 PLS M300 SET M301 Check the data link status of the station 1 M300 11 M301 X100D 13 MOV K5000 W101 Write set frequency to RWw1.
Programming examples 4.7.8 Programming example for fault record reading The following program reads fault records of station 1 inverter to D1. ⋅ Faults history No. 1, No. 2 reading code number: H74 (hexadecimal) For the error code numbers, refer to page 65. The reply code at the time of instruction code execution is set to D2. (Refer to page 63) X0 X0F M0 X20 X1 SW80.
Programming examples 4.7.10 Instructions (1) Programming instructions ⋅ Since the buffer memory data of the master station is kept transferred (refreshed) to/from the inverters, the TO instruction need not be executed every scan in response to data write or read requests. The execution of the TO instruction every scan does not pose any problem. ⋅ If the FROM/TO instruction is executed frequently, data may not be written reliably.
How to check for error using the LEDs 4.8 4.8.1 How to check for error using the LEDs Operation status indication LEDs LED L.RUN Description Lit when refresh data is properly received. Turns OFF when a data Operation status indicator (LED) transmission is stopped for a certain period of time. ⋅ Lit when a communication error occurs in the own station and flickers when settings of switch, etc. are changed while power is ON. L.ERR ⋅ Flickers when the Pr. 542 or Pr. 543 setting is changed.
How to check for error using the LEDs 4.8.3 When two or more inverters are connected The following table shows how the cause of a fault can be determined with the inverter's (FR-E700-NC) LED statuses in the system configuration shown below. (In this example, assume SW, M/S, PRM LEDs of the master module are OFF. (The master module is in normal operation.
How to check for error using the LEDs 4.8.4 Communication stops during operation • Check that CC-Link dedicated cable is fitted properly. (Check for contact fault, break in the cable, etc.) • Check that the programmable controller program is executed properly. • Check that data communication has not stopped due to an instantaneous power failure, etc. Master Module LED States Inverters (FR-E700-NC) Station 1 RUN L.RUN SD RD L.ERR TIME LINE or TIME LINE Station 2 Corrective Action Station 3 RUN L.
MEMO 78
5 PARAMETERS This chapter explains the "PARAMETERS" for use of this 1 product. Always read the instructions before using the equipment. 2 The following marks are used to indicate the controls as below. V/F AD MFVC ......V/F control ......Advanced magnetic flux vector control 3 ......General-purpose magnetic flux vector control (Parameters without any mark are valid for all controls.
Operation panel 5.1 5.1.1 Operation panel Names and functions of the operation panel The operation panel cannot be removed from the inverter. Operation mode indicator PU: Lit to indicate PU operation mode. EXT: Not used. NET: Lit to indicate Network operation mode. (Lit at power-ON at initial setting.) Unit indicator Hz: Lit to indicate frequency. (Flickers when the set frequency monitor is displayed.) A: Lit to indicate current. (Both "Hz" and "A" turn OFF when other than the above is displayed.
Operation panel 5.1.2 Basic operation (factory setting) Operation mode switchover At power-ON (Network operation mode) Parameter setting Monitor/frequency setting PU Jog operation mode (Example) PU operation mode (output frequency monitor) Value change and frequency flicker.
Operation panel 5.1.3 Changing the parameter setting value Changing example Change the Pr. 1 Maximum frequency setting. Operation Display 1. Screen at power-ON The inverter starts up in Network operation mode. The monitor display appears. 2. Press to choose the PU operation mode. 3. Press to choose the parameter setting PU indicator is lit. PRM indicator is lit. mode. (The parameter number read previously appears.) 4. Turn until 5. Press " (Pr. 1) appears. to read the currently set value.
Operation panel 5.1.4 Setting dial push Push the setting dial ( ) to display the set frequency* currently set. ∗ Appears when PU operation mode is selected.
Parameter list 5.2 5.2.1 Parameter list Parameter list Parameter list Parameter List For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check are available from the operation panel. These instruction codes are used for parameter read and write by using CC-Link communication.
Parameter list Parameter — 29 Acceleration/deceleration pattern selection — 30 Regenerative function selection Minimum Setting Increments Initial Value Refer to Page 0, 1, 2 1 0 139 0, 1, 2 1 0 Name Setting Range 155, 180 Customer Setting Instruction Code Parameter Read Write Extended Control Mode-based Correspondence Parameter V/F AD MFVC GP MFVC Clear All clear 29 1D 9D 0 30 1E 9E 0 31 Frequency jump 1A 0 to 400Hz, 9999 0.
Parameter list Function Parameter — 77 Parameter write selection — 78 Reverse rotation prevention selection — 79 Operation mode selection Name Minimum Setting Increments Initial Value Refer to Page 0, 1, 2 1 0 196 77 4D — 0, 1, 2 1 0 197 78 4E CE 0, 1, 2, 3, 4, 6, 7 1 0 103 79 4F 80 Setting Range Customer Setting Instruction Code Parameter Read Write Extended Control Mode-based Correspondence Parameter GP MFVC Clear All clear
Parameter Name Setting Range — 156 Stall prevention operation selection 0 to 31, 100, 101 — 157 OL signal output timer 0 to 25s, 9999 — 160 User group read selection functions Automatic restart — monitor clear Cumulative User group Read Write Extended Control Mode-based Correspondence Parameter V/F AD MFVC GP MFVC Clear All clear 120 156 38 B8 1 120 157 39 B9 1 0, 1, 9999 1 0 197 160 00 80 2 161 Frequency setti
Parameter list Initial Value Refer to Page 1 1 213 244 34 B4 0 to 50%, 9999 0.01% 9999 119 245 35 Slip compensation time constant 0.01 to 10s 0.01s 0.5s 119 246 247 Constant-power range slip compensation selection 0, 9999 1 9999 119 249 Earth (ground) fault detection at start 0, 1 1 0 0 to 100s, 1000 to 1100s, 8888, 9999 0.
Parameter list Parameter list Function Parameter — 338 — 339 — 340 — 342 Communication EEPROM write selection — 343 Parameter for manufacturer setting. Do not set. — 349 Name Setting Range Minimum Setting Increments Initial Value Refer to Page Customer Setting Instruction Code Parameter Read Write Extended Control Mode-based Correspondence V/F Parameter AD MFVC GP MFVC Clear All clear 338 Parameter for manufacturer setting. Do not set.
Function Parameter Parameter list Name Setting Range Minimum Setting Increments Initial Value Refer to Page Customer Setting Instruction Code Parameter Read Write Extended Control Mode-based Correspondence Parameter V/F AD MFVC GP MFVC Clear All clear — 563 Energization time carrying-over times (0 to 65535) 1 0 176 563 3F BF 5 — 564 Operating time carrying-over times (0 to 65535) 1 0 176 564 40 C0 5 — 571 Holding time at a start 0 to 1
Clear parameters Initial value change list Function Parameter Parameter list Name Setting Range Minimum Setting Increments Initial Value Refer to Page Customer Setting Instruction Code Parameter Read Write Control Mode-based Correspondence Parameter Extended V/F AD MFVC GP MFVC Clear All clear Pr.CL Parameter clear 0, 1 1 0 227 Pr.CL — FC — — — — — — ALLC All parameter clear 0, 1 1 0 227 ALLC — FC — — — — — — Er.
Parameters according to purposes 5.3 Selection of operation mode 5.3.1 5.4 Operation mode selection (Pr. 79).............................................................................................. 103 Operation via CC-Link communication and its settings 105 5.4.1 CC-Link communication setting (Pr.541 to Pr.544) .................................................................... 105 5.4.2 Operation selection at CC-Link communication error occurrence (Pr. 500 to Pr. 502)...............
5.12.3 Stop selection (Pr. 250) .............................................................................................................. 157 5.12.4 Stop-on contact control function (Pr. 6, Pr. 48, Pr. 270, Pr. 275, Pr. 276) ................................. 158 5.12.5 Brake sequence function (Pr. 278 to Pr. 283, Pr. 292) ............................................................... 160 163 5.13.1 Input terminal function selection (Pr. 180 to Pr. 184) .........................................
5.21.1 Cooling fan operation selection (Pr. 244) ................................................................................... 213 5.21.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259)......................................................... 214 5.21.3 Maintenance timer alarm (Pr. 503, Pr. 504)................................................................................ 217 5.21.4 Average current monitor signal (Pr. 555 to Pr. 557) ............................................
Selection of operation mode 5.3 Selection of operation mode 5.3.1 Operation mode selection (Pr. 79) Select the operation mode of the inverter. The operation mode can be selected between the CC-Link communication operation (Network operation) and the operation panel operation (PU operation). At power-ON or power restoration after instantaneous power failure, the inverter always starts in the Network operation mode.
Selection of operation mode (2) Network operation mode (Pr. 79 setting "0" (initial value), "2") Select the Network operation mode to give start and frequency commands via CC-Link communication. Generally, parameter change cannot be performed from the operation panel in the Network operation mode. (Some parameters can be changed. Refer to the detailed description of each parameter.) When "0" (initial value) is selected for Pr. 79, the inverter enters the Network operation mode at power-ON.
Operation via CC-Link communication and its settings 5.4 Operation via CC-Link communication and its settings Purpose Parameter that should be Set To make CC-Link communication settings To select the operation at CC-Link communication error occurrence To select the error reset operation at inverter failure To limit parameter writing via CC-Link communication 5.4.1 Refer to Page Communication station number setting Baud rate setting Pr.541 to Pr.
Operation via CC-Link communication and its settings (2) Baud rate setting (Pr. 543) Set the transmission speed. (Refer to the manual of the CC-Link master module for details of transmission speed.) REMARKS "L.ERR" LED flickers when a setting is changed. Power OFF-ON the inverter (inverter reset) to apply the setting and to turn OFF the LED. (3) Frequency command with sign (Pr. 541) By frequency command with sign, start command (forward rotation/reverse rotation) can be inversed to operate.
Operation via CC-Link communication and its settings 5.4.2 Operation selection at CC-Link communication error occurrence (Pr. 500 to Pr. 502) The inverter operation after an error occurs in the CC-Link communication can be selected. Parameter Name Number 500 501 502∗ Initial Setting Value Range 0 0 to 999.
Operation via CC-Link communication and its settings (3) Inverter operation at a communication error occurrence (Pr.502) The inverter operation after a fault occurs in the communication line or in the CC-Link communication circuit can be selected. About setting Operation at an error occurrence Error Definition Pr. 502 Setting Operation Indication Fault Output Continued ∗ Normal indication ∗ Not provided ∗ 0 (initial value), 3 Coast to stop E. 1 lit Provided 1, 2 Decelerated to stop E.
Operation via CC-Link communication and its settings Faults and measures The following table shows how the inverter operates at a fault occurrence in each operation mode. Fault Indication∗ Fault Location Communication line E.OP1 Faults other than E.1 and E.OP1 Inverter E.
Operation via CC-Link communication and its settings 5.4.3 CC-Link communication reset selection (Pr.349) The RY1A error reset command (on page 60) transmitted via CC-Link communication in PU operation mode can be disabled.
Control mode 5.5 Control mode V/F control (initial setting), Advanced magnetic flux vector control and General-purpose magnetic flux vector control are available with this inverter. (1) V/F Control It controls frequency and voltage so that the ratio of frequency (F) to voltage (V) is constant when changing frequency.
Control mode 5.5.1 Changing the control method (Pr. 80, Pr. 81, Pr. 800) Set when selecting the control method for Advanced magnetic flux vector control and General-purpose magnetic flux vector control. The initial value is V/F control. Select a control mode using Pr. 800 Control method selection. Parameter Initial Name Number Value 80 Motor capacity 9999 81 Number of motor poles 9999 800 Control method selection 20 Setting Range 0.
Adjustment of the output torque (current) of the motor 5.6 Adjustment of the output torque (current) of the motor Purpose Set starting torque manually Automatically control output current according to load Compensate for motor slip to secure low-speed torque Limit output current to prevent inverter trip 5.6.
Adjustment of the output torque (current) of the motor 5.6.2 Advanced magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr.89, Pr. 800) AD MFVC Advanced magnetic flux vector control can be selected by setting the capacity, poles and type of the motor used in Pr. 80 and Pr. 81. Advanced magnetic flux vector control? The low speed torque can be improved by providing voltage compensation to flow a motor current which meets the load torque.
Adjustment of the output torque (current) of the motor Perform secure wiring. (Refer to page 14) Set the motor. (Pr. 71) Pr. 71 Setting ∗1 Motor Mitsubishi standard motor Mitsubishi high efficiency motor Mitsubishi constanttorque motor 0 (initial value) 40 Others 3 Offline auto tuning is necessary. ∗2 SF-JRCA 4P SF-HRCA Others (SF-JRC, etc.) 1 50 13 Offline auto tuning is necessary. ∗2 — 3 Offline auto tuning is necessary.
Adjustment of the output torque (current) of the motor (1) Adjust the motor speed fluctuation at load fluctuation (Pr. 89 Speed control gain (Advanced magnetic flux The motor speed fluctuation at load fluctuation can be adjusted using Pr. 89. (It is useful when the speed command does not match the motor speed after the FR-E500 series inverter is replaced with the FR-E700 series inverter, etc.) Load torque vector)) Speed Parameters referred to Pr. 71, Pr. 450 Applied motor Pr.
Adjustment of the output torque (current) of the motor 5.6.3 General-purpose magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr. 800) GP MFVC General-purpose magnetic flux vector control is the same function as the FR-E500 series. Select this control when the same operation characteristic is necessary. For other cases, select Advanced magnetic flux vector control.
Adjustment of the output torque (current) of the motor Perform secure wiring. (Refer to page 14) Set the motor.(Pr. 71) Pr. 71 Setting ∗1 Motor Mitsubishi standard motor Mitsubishi high efficiency motor Mitsubishi constanttorque motor 0 (initial value) 40 Others 3 Offline auto tuning is necessary. ∗2 SF-JRCA 4P SF-HRCA Others (SF-JRC, etc.) 1 50 13 Offline auto tuning is necessary. ∗2 — 3 Offline auto tuning is necessary.
Adjustment of the output torque (current) of the motor 5.6.4 Slip compensation (Pr. 245 to Pr. 247) V/F GP MFVC When V/F control or General-purpose magnetic flux vector control is performed, the inverter output current may be used to assume motor slip to keep the motor speed constant. Parameter Name Number 245 Initial Value Rated slip 9999 Setting Range 0.01 to 50% 0, 9999 Description Rated motor slip. No slip compensation Slip compensation response time.
Adjustment of the output torque (current) of the motor 5.6.5 Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 66, Pr. 156, Pr. 157, Pr. 277) This function monitors the output current and automatically changes the output frequency to prevent the inverter from coming to trip due to overcurrent, overvoltage, etc. In addition, simple torque limit which limits the output torque to the predetermined value can be selected.
Adjustment of the output torque (current) of the motor (2) Setting of stall prevention operation level (Pr. 22) Set in Pr. 22 the percentage of the output current to the rated inverter current at which stall prevention operation will be Output current performed. Normally set this parameter to 150% (initial value). Stall prevention operation stops acceleration (makes Pr.
Adjustment of the output torque (current) of the motor (5) Setting of stall prevention operation in high frequency range (Pr. 22, Pr. 23, Pr. 66) Setting example (Pr. 22 = 150%, Pr. 23 = 100%, Pr. 66 = 60Hz) Pr. 22 Stall prevention operation level Stall prevention operation level (%) (%) When Pr. 23 = 9999 When Pr. 23 = "9999", the stall prevention operation level is as set in Pr. 22 to 400Hz. Stall prevention operation level as set in Pr. 23 150 90 60 45 30 22.5 0 400Hz Output frequency (Hz) Pr.
Adjustment of the output torque (current) of the motor (7) Limit the stall prevention operation and fast-response current limit operation according to the operating status (Pr. 156) Refer to the following table and select whether stall prevention operation and fast-response current limit operation will be performed or not and the operation to be performed at OL signal output.
Limiting the output frequency 5.7 Limiting the output frequency Purpose Parameter that should be Set Set upper limit and lower limit of output frequency Perform operation by avoiding mechanical resonance points 5.7.1 Maximum/minimum frequency Refer to Page Pr. 1, Pr. 2, Pr. 18 124 Pr. 31 to Pr. 36 125 Frequency jump Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18) Motor speed can be limited. Clamp the upper and lower limits of the output frequency.
Limiting the output frequency 5.7.2 Avoiding mechanical resonance points (frequency jumps) (Pr. 31 to Pr. 36) When avoiding resonance arisen from the natural frequency of a mechanical system, use these parameters to jump the resonant frequencies.
V/F pattern 5.8 V/F pattern Purpose Parameter that should be Set Refer to Page Set motor ratings Base frequency, Base frequency voltage Pr. 3, Pr. 19, Pr. 47 126 Select a V/F pattern according to applications. Load pattern selection Pr. 14 128 5.8.1 Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47) V/F Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
V/F pattern (3) Base frequency voltage setting (Pr. 19) Use Pr. 19 Base frequency voltage to set the base voltage (e.g. rated motor voltage). If the setting is less than the power supply voltage, the maximum output voltage of the inverter is as set in Pr. 19. Pr. 19 can be utilized in the following cases. (a) When regeneration is high (e.g. continuous regeneration) During regeneration, the output voltage becomes higher than the reference and may cause an overcurrent trip (E.
V/F pattern 5.8.2 Load pattern selection (Pr. 14) V/F You can select the optimum output characteristic (V/F characteristic) for the application and load characteristics. Parameter Name Number 14 Initial Value Load pattern selection Setting Range 0 Description 0 For constant-torque load 1 For variable torque load 2 3 For constant-torque elevators (at reverse rotation boost of 0%) For constant-torque elevators (at forward rotation boost of 0%) The above parameters can be set when Pr.
V/F pattern 100% Forward rotation Reverse rotation 100% Pr. 0 Pr. 46 Base frequency Output frequency (Hz) Constant-torque load application (setting "2, 3") For vertical lift loads At forward rotation boost...0% At reverse rotation boost...Pr. 0 (Pr. 46) setting Output voltage Reverse rotation Forward rotation Base frequency Output frequency (Hz) Set "2" when a vertical lift load is fixed as power driving load at forward rotation and regenerative load at reverse rotation. Pr.
Frequency setting with input signals 5.9 Frequency setting with input signals Purpose Parameter that should be Set To control the frequency with combinations of input signals To command smooth speed transition with input signals 5.9.1 Multi-speed operation Refer to Page Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 130 Pr. 59 132 Remote setting function Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr.
Frequency setting with input signals (2) Multi-speed setting for 4 or more speeds (Pr. 24 to Pr. 27, Pr. 232 to Pr. 239) Frequency from 4 speed to 15 speed can be set according to the combination of the RH, RM, RL and REX signals. Set the running frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239. (In the initial value setting, speed 4 to speed 15 are invalid.) Output frequency (Hz) To input the REX signal to a virtual terminal of CC-Link communication, set "8" in one of Pr.180 to Pr.
Frequency setting with input signals 5.9.2 Remote setting function (Pr. 59) Continuous variable-speed operation can be performed with acceleration and deceleration signals. By simply setting this parameter, you can use the acceleration, deceleration and setting clear functions of the remote speed setter (FR-FK).
Frequency setting with input signals (1) Remote setting function Use Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting storage function in the remote setting mode is used or not. When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL signals are changed to acceleration (RH), deceleration (RM) and clear (RL).
Frequency setting with input signals REMARKS During Jog operation or PID control operation, the remote setting function is invalid.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 5.10 Setting of acceleration/deceleration time and acceleration/ deceleration pattern Purpose Motor acceleration/deceleration time setting Starting frequency Set acceleration/deceleration pattern suitable for application Automatically set optimum acceleration/deceleration time.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern (1) Pr. 20 (60Hz) Output frequency (Hz) Running frequency Acceleration time setting (Pr. 7, Pr. 20) Use Pr. 7 Acceleration time to set the acceleration time required to reach Pr. 20 Acceleration/deceleration reference frequency from 0Hz. Set the acceleration time according to the following formula. Time Acceleration time setting Acceleration time Deceleration time Pr. 7, Pr. 44 Pr. 8, Pr. 45 Pr.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern Set two kinds of acceleration/deceleration times (RT signal, Pr. 44, Pr. 45, Pr. 147 ) Pr. 44 and Pr. 45 are valid when the RT signal is ON, or the output frequency reaches or exceeds the setting of Pr. 147. When "9999" is set to Pr. 45, the deceleration time becomes equal to the acceleration time (Pr. 44). For the RT signal, set "3" in any of Pr. 180 to Pr. 184 (input terminal function selection) to assign the function.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 5.10.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571) You can set the starting frequency and hold the set starting frequency for a certain period of time. Set these functions when you need the starting torque or want to smooth motor drive at a start. Parameter Name Number Initial Value Setting Range Description Frequency at start can be set in the range 13 Starting frequency 0.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 5.10.3 Acceleration/deceleration pattern (Pr. 29) You can set the acceleration/deceleration pattern suitable for application. Parameter Name Number 29 Initial Value Acceleration/deceleration pattern selection Setting Range 0 Description 0 Linear acceleration/ deceleration 1 S-pattern acceleration/deceleration A 2 S-pattern acceleration/deceleration B The above parameters can be set when Pr.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 5.10.4 Shortest acceleration/deceleration (automatic acceleration/deceleration) (Pr. 61 to Pr. 63, Pr. 292, Pr. 293) The inverter operates in the same conditions as when appropriate values are set in each parameter even if acceleration/deceleration time and V/F pattern are not set. This function is useful when you just want to operate, etc. without fine parameter setting.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern (2) Adjustment of shortest acceleration/deceleration mode (Pr. 61 to Pr. 63) By setting the adjustment parameters Pr. 61 and Pr. 63, the application range can be made wider. Parameter Number Name Setting Range Description For example, when the motor and inverter are different in capacity, 61 0 to 500A Reference current set the rated motor current value.
Selection and protection of a motor 5.11 Selection and protection of a motor Purpose Parameter that should be Set Motor protection from overheat Use the constant-torque motor The motor performance can be maximized for operation in magnetic flux vector control method. 5.11.1 Electronic thermal O/L relay Applied motor Refer to Page Pr. 9, Pr. 51 Pr. 71 Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr.
Selection and protection of a motor (2) Set two different electronic thermal O/L relays (Pr. 51) Use this function when running two motors of different rated currents individually by a single inverter. (When running two motors together, use external thermal relays.) Set the rated current of the second motor to Pr. 51. When the RT signal is ON, thermal protection is provided based on the Pr. 51 setting. To input the RT signal to a virtual terminal of CC-Link communication, set "3" in one of Pr. 180 to Pr.
Selection and protection of a motor 5.11.2 Applied motor (Pr. 71, Pr. 450) Setting of the used motor selects the thermal characteristic appropriate for the motor. Setting is required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay function suitable for the motor is set. When General-purpose magnetic flux vector or Advanced magnetic flux vector control is selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA, etc.) necessary for control are selected as well.
Selection and protection of a motor (2) Use two motors (Pr. 450) Set Pr. 450 Second applied motor to use two different motors with one inverter. When "9999" (initial value) is set, no function is selected. When a value other than 9999 is set in Pr. 450, the second motor is valid when the RT signal turns ON. For the RT signal, set "3" in any of Pr. 180 to Pr. 184 (input terminal function selection) to assign the function.
Selection and protection of a motor 5.11.3 Exhibiting the best performance for the motor (offline auto tuning) (Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 859) The motor performance can be maximized with offline auto tuning.
Selection and protection of a motor The setting range and increments of Pr. 82, Pr. 90 to Pr. 94 and Pr. 859 changes according to the setting value of Pr. 71 and Pr. 96. Applied Motor Parameter Internal Stored Value ∗1 Setting Direct Input Value ∗2 ∗3 Setting Range 82 Motor excitation current 0 to 500A, 9999 0.01A 0 to 500A, 9999 0.01A 0 to ****, 9999 1 90 Motor constant (R1) 0 to 50Ω, 9999 0.001Ω 0 to 50Ω, 9999 0.001Ω 0 to ****, 9999 1 91 Motor constant (R2) 0 to 50Ω, 9999 0.
Selection and protection of a motor (2) Setting 1) Select Advanced magnetic flux vector control (Refer to page 114) or General-purpose magnetic flux vector control (Refer to page 117). 2) Set "1" or "11" in Pr. 96 Auto tuning setting/status. When the setting is "1" ....... Tune all motor constants without running the motor. When performing Advanced magnetic flux vector control, set "1" to perform tuning. It takes approximately 25 to 75s∗ until tuning is completed.
Selection and protection of a motor Execution of tuning POINT Before performing tuning, check the monitor display of the operation panel if the inverter is in the status for tuning. (Refer to 2) below.) When the start command is turned ON under V/F control, the motor starts. 1) In the PU operation mode, press on the operation panel. In the Network operation mode, turn ON the start command via CC-Link communication. Tuning will start.
Selection and protection of a motor 3) When offline auto tuning ends, press on the operation panel during PU operation. In the Network operation mode, turn OFF the start command via CC-Link communication. This operation resets the offline auto tuning and returns the operation panel monitor display to the normal display. (Without this operation, next operation cannot be started.) REMARKS Do not change the Pr. 96 setting after completion of tuning (3 or 13). If the Pr.
Selection and protection of a motor (4) Utilizing or changing offline auto tuning data for use The data measured in the offline auto tuning can be read and utilized or changed. 1) Set Pr. 71 according to the motor used. Pr. 71 Setting ∗1 Motor Mitsubishi standard motor Mitsubishi high efficiency motor Mitsubishi constant-torque motor SF-JR SF-JR 4P 1.5kW or less SF-HR Others SF-JRCA 4P SF-HRCA Others (SF-JRC, etc.
Selection and protection of a motor (5) Method to set the motor constants without using the offline auto tuning data The Pr. 90 to Pr. 94 motor constants may either be entered in [Ω] or in [mH]. Before starting operation, confirm which motor constant unit is used. To enter the Pr. 90 to Pr. 94 motor constants in [Ω] 1)Set Pr. 71 according to the motor used.
Selection and protection of a motor To enter the Pr. 90 to Pr. 94 motor constants in [mH] 1) Set Pr. 71 according to the motor used. Motor Pr.71 Setting ∗1 Mitsubishi standard motor Mitsubishi high efficiency motor Mitsubishi constant-torque motor ∗1 SF-JR SF-HR SF-JRCA 4P SF-HRCA 0 40 1 50 For other settings of Pr. 71, refer to page 144. 2) In the parameter setting mode, read the following parameters and set desired values. Calculate the Pr. 94 value from the following formula.
Motor brake and stop operation 5.
Motor brake and stop operation CAUTION As stop holding torque is not produced, install a mechanical brake. Parameters referred to Pr. 13 Starting frequency Pr. 71 Applied motor Refer to page 138 Refer to page 144 5.12.2 Selection of a regenerative brake (Pr. 30, Pr. 70) When making frequent starts/stops, use the optional brake resistor (MRS type, MYS type), high-duty brake resistor (FR-ABR) and brake unit (FR-BU2) to increase the regenerative brake duty.
Motor brake and stop operation (4) Regenerative brake duty alarm output and alarm signal (RBP signal) [RB] appears on the operation panel and an alarm signal (RBP) is output when 85% of the regenerative 100%: regenerative overvoltage protection operation value brake duty set in Pr. 70 is reached. If the regenerative brake duty reaches 100% of the Pr. 70 setting, a Ratio of the brake duty to the Pr. 70 setting (%) regenerative overvoltage (E.OV1 to E.OV3) occurs. Note that [RB] is not displayed when Pr.
Motor brake and stop operation 5.12.3 Stop selection (Pr. 250) Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns OFF. Used to stop the motor with a mechanical brake, etc. together with switching OFF of the start signal. Parameter Initial Name Number Description Stop operation Setting Range Value The motor is coasted to a stop when the preset time elapses 0 to 100s 250 Stop selection 9999 after the start signal is turned OFF.
Motor brake and stop operation 5.12.4 Stop-on contact control function (Pr. 6, Pr. 48, Pr. 270, Pr. 275, Pr. 276) AD MFVC GP MFVC To ensure accurate positioning at the upper limit etc. of a lift, stop-on-contact control causes a mechanical brake to be closed while the motor is developing a holding torque to keep the load in contact with a mechanical stopper etc.
Motor brake and stop operation (3) Function switching of stop-on-contact control selection Main Functions Normal Operation With stop-on-contact Control (either RL or RT is OFF or both are OFF) (both RL and RT are ON) Multi-speed operation setting, set frequency, etc. Output frequency Stall prevention operation Pr. 22 setting level Excitation current low — speed scaling factor Carrier frequency Pr. 72 setting Fast-response current Pr. 48 setting (Pr. 22 when Pr. 48 = "9999") Only Pr.
Motor brake and stop operation 5.12.5 Brake sequence function (Pr. 278 to Pr. 283, Pr. 292) AD MFVC GP MFVC This function is used to output from the inverter the mechanical brake operation timing signal in vertical lift and other applications. This function prevents the load from dropping with gravity at a start due to the operation timing error of the mechanical brake or an overcurrent alarm from occurring at a stop, ensuring secure operation.
Motor brake and stop operation (2) With brake opening completion signal input (Pr. 292 = "7") Output frequency (Hz) When the start signal is input to the inverter, the inverter starts running. When the internal speed command reaches the value set in Pr. 278 and the output current is not less than the value set in Pr. 279, the inverter outputs the brake opening request signal (BOF) after the time set in Pr. 280 has elapsed. When the time set in Pr.
Motor brake and stop operation REMARKS If brake sequence function has been selected, inputting the RT signal (second function selection) during an inverter stop will make brake sequence function invalid and give priority to the second function selection. Note that RT signal input is invalid even if RT signal is input during operation with brake sequence function.
Function assignment of external terminals and CC-Link communication virtual terminals 5.
Function assignment of external terminals and CC-Link communication virtual terminals (1) Input terminal function assignment Using Pr. 180 to Pr. 184, set the functions of the input virtual terminals. Refer to the following table and set the parameters: Setting 0 1 2 3 4, 5, 7 8 10, 12 Signal RL RM RH RT Function Related Parameters Refer to Page Pr. 4 to Pr. 6, Pr. 24 to Pr. 27 Pr.232 to Pr.239 130 Pr. 59 = 0 (initial value) Low-speed operation command Pr.
Function assignment of external terminals and CC-Link communication virtual terminals (2) Second function selection signal (RT) When the RT signal turns ON, the second function becomes valid. For the RT signal, set "3" in any of Pr. 180 to Pr. 184 (input terminal function selection) to assign the function. The second function has the following applications.
Function assignment of external terminals and CC-Link communication virtual terminals 5.13.2 Inverter output shutoff signal (MRS signal, Pr. 17) The inverter output can be shut off by the MRS signal. Also, logic for the MRS signal can be selected. Parameter Name Number Initial Value Setting Range 0, 4 17 MRS input selection 0 2 Description Normally open input Normally closed input (NC contact input specifications) The above parameters can be set when Pr. 160 User group read selection = "0".
Function assignment of external terminals and CC-Link communication virtual terminals 5.13.3 Output terminal function selection (Pr. 190 to Pr. 192, Pr. 313 to Pr. 315) The function assigned to the terminal Y0 or an output virtual terminal of CC-Link communication can be changed.
Function assignment of external terminals and CC-Link communication virtual terminals Setting Positive Negative logic logic Signal Function Operation Related Parameter Pr. 65 to Pr. 69 Refer to Page 64 164 Y64 During retry Output during retry processing. 68 168 EV 24V external power supply operation The signal is output while the main circuit power supply is off and the 24V power is supplied externally.
Function assignment of external terminals and CC-Link communication virtual terminals (2) Inverter operation ready signal (RY signal) and inverter running signal (RUN signal) ON Power supply OFF ON STF OFF ON Output frequency RH DC injection brake operation point DC injection brake operation Pr. 13 Starting frequency Time Reset processing ON RY OFF ON RUN OFF When the inverter is ready to operate, the output of the operation ready signal (RY) is ON. (It is also ON during inverter running.
Function assignment of external terminals and CC-Link communication virtual terminals (3) Fault output signal (ALM signal) Inverter fault occurrence (Trip) If the inverter comes to trip, the ALM signal is output. Output frequency Time ALM ON OFF ON OFF Reset processing (about 1s) Reset ON Inverter reset REMARKS The ALM signal is initially assigned to a virtual terminal of CC-Link communication.
Function assignment of external terminals and CC-Link communication virtual terminals 5.13.4 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43) The inverter output frequency is detected and output at the output signals. Parameter Name Number Initial Value Setting Range 10% 0 to 100% Level where the SU signal turns ON. 6Hz 0 to 400Hz Frequency where the FU signal turns ON.
Function assignment of external terminals and CC-Link communication virtual terminals 5.13.5 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153) The output current during inverter operation can be detected and output to terminal Y0 or a virtual terminal of CC-Link communication.
Function assignment of external terminals and CC-Link communication virtual terminals NOTE Changing the assignment of the terminal Y0 or a virtual terminal of CC-Link communication with one of Pr. 190 to Pr. 192, and Pr. 313 to Pr. 315 (output terminal function selection) may affect other functions. Set parameters after confirming the function of the terminal Y0 and virtual terminals.
Function assignment of external terminals and CC-Link communication virtual terminals 5.13.6 Remote output selection (REM signal, Pr. 495, Pr. 496) You can utilize the ON/OFF of the inverter's output signals instead of the remote output terminal of the programmable logic controller.
Monitor display and monitor output signal 5.14 Monitor display and monitor output signal Purpose Refer to Parameter that should be Set Page Display motor speed Speed display and speed setting Pr. 37 Set speed Change operation panel monitor Operation panel main display data selection Pr. 52, Pr. 170, Pr. 171, Pr. 268, display data Cumulative monitor clear Pr. 563, Pr. 564 175 176 5.14.1 Speed display and speed setting (Pr.
Monitor display and monitor output signal 5.14.2 Monitor display selection of operation panel (Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564) The monitor to be displayed on the main screen of the operation panel can be selected.
Monitor display and monitor output signal Types of Monitor Cumulative power ∗3 Increment 0.01kWh ∗5 Pr. 52 Description Setting 25 Adds up and displays the power amount based on the output power monitor. Can be cleared by Pr. 170. (Refer to page 178) PID set point 0.1% 52 PID measured value 0.1% 53 PID deviation 0.1% 54 — 55 Motor thermal load factor 0.1% 61 Displays the motor thermal heat cumulative value. (Motor overload trip (E.THM) at 100%) Inverter thermal load factor 0.
Monitor display and monitor output signal (2) Display set frequency during stop Pr. 52 0 During (Pr. 52) When "100" is set in Pr. 52, the set frequency and output frequency are displayed during stop and operation respectively. (LED of Hz flickers 100 Output frequency during stop and is lit during operation.
Monitor display and monitor output signal (5) Cumulative energization time and actual operation time monitor (Pr. 171, Pr. 563, Pr. 564) Cumulative energization time monitor (Pr. 52 = "20") accumulates energization time from shipment of the inverter every one hour. On the actual operation time monitor (Pr. 52 = "23"), the inverter running time is added up every hour. (Time is not added up during a stop.) If the monitored value exceeds 65535, it is added up from 0.
Operation selection at power failure and instantaneous power failure 5.15 Operation selection at power failure and instantaneous power failure Purpose At instantaneous power failure occurrence, restart inverter without stopping motor When undervoltage or a power failure occurs, the inverter can be decelerated to a stop. Parameter that should be Set Automatic restart operation after instantaneous power failure/flying start Power failure-time deceleration-to-stop function Refer to Page Pr. 57, Pr.
Operation selection at power failure and instantaneous power failure When Pr. 162 = 1, 11 (without frequency search) Instantaneous (power failure) time Automatic restart operation selection (Pr. 162, Pr. 299) Without frequency search When Pr.
Operation selection at power failure and instantaneous power failure Restart operation at every start When Pr. 162 = "10 or 11", automatic restart operation is also performed every start, in addition to the automatic restart after instantaneous power failure. When Pr. 162 = "0", automatic restart operation is performed at the first start after power supply ON, but not performed at the second time or later. (2) Restart coasting time (Pr.
Operation selection at power failure and instantaneous power failure zBefore performing offline auto tuning Check the following before performing offline auto tuning. The inverter is under V/F control A motor should be connected. Note that the motor should be at a stop at a tuning start. The motor capacity should be equal to or one rank lower than the inverter capacity. (note that the capacity is 0.1kW or more) A high-slip motor, high-speed motor and special motor cannot be tuned.
Operation selection at power failure and instantaneous power failure 2) Monitor is displayed on the operation panel during tuning as below. Operation Panel Indication Pr. 96 setting 21 (1) Setting (2) Tuning in progress Flickering (3) Normal end (4) Error end (when inverter protective function operation is activated) Reference: Offline auto tuning time (when the initial value is set) Offline Auto Tuning Setting Time Tune motor constants (R1) only Approx.
Operation selection at power failure and instantaneous power failure NOTE The motor constants measured once in the offline auto tuning are stored as parameters and their data are held until the offline auto tuning is performed again. An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the inverter goes into the normal operation mode. Therefore, when STF (STR) signal is ON, the motor runs in the forward (reverse) rotation.
Operation selection at power failure and instantaneous power failure 5.15.2 Power-failure deceleration stop function (Pr. 261) When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and reaccelerated to the set frequency. Parameter Name Number Initial Setting Value Range Description Coasts to stop. 0 Power failure stop selection 261 0 When undervoltage or power failure occurs, the inverter output is shut off.
Operation selection at power failure and instantaneous power failure (4) Operation continuation at instantaneous power failure function (Pr. 261 = "2") When power is restored during deceleration after a power failure, the inverter accelerates back up to the set frequency. When this function is used in combination with the automatic restart after instantaneous power failure function(Pr.57 ≠ "9999"), deceleration can be made at a power failure and acceleration can be made again after power restoration. Pr.
Operation setting at fault occurrence 5.16 Operation setting at fault occurrence Purpose Parameter that should be Set Recover by retry operation at fault occurrence Do not output input/output phase failure alarm Detect an earth (ground) fault at start Retry operation Refer to Page Pr. 65, Pr. 67 to Pr. 69 188 Pr. 251, Pr. 872 190 Pr. 249 190 Input/output phase failure protection selection Earth (ground) fault detection at start 5.16.1 Retry function (Pr. 65, Pr. 67 to Pr.
Operation setting at fault occurrence Using Pr. 65, you can select the fault that will cause a retry to be executed. No retry will be made for the fault not indicated. (Refer to page 234 for the fault description.) indicates the faults selected for retry. Fault for Retry E.OC1 E.OC2 E.OC3 E.OV1 E.OV2 E.OV3 E.THM E.THT E. BE E. GF 0 1 Pr. 65 Setting 2 3 4 5 Fault for Retry E.USB E.OLT E.OPT E.OP1 E. PE E.MB4 E.MB5 E.MB6 E.MB7 E.ILF 0 1 Pr.
Operation setting at fault occurrence 5.16.2 Input/output phase loss protection selection (Pr. 251, Pr. 872) You can choose whether to make the input/output phase loss protection valid or invalid. Output phase loss protection is a function to stop the inverter output if one of the three phases (U, V, W) on the inverter's output side (load side) is lost. Input phase loss protection is a function to stop the inverter output if one of the three phases (R/L1, S/L2, T/L3) on the inverter's input side is lost.
Energy saving operation 5.17 Energy saving operation Purpose Parameter that should be Set Energy saving operation Optimum excitation control 5.17.1 Optimum excitation control (Pr. 60) Refer to Page Pr. 60 191 V/F Without a fine parameter setting, the inverter automatically performs energy saving operation.
Motor noise, EMI measures, mechanical resonance 5.18 Motor noise, EMI measures, mechanical resonance Purpose of Use Reduction of the motor noise Measures against EMI and leakage currents Reduce mechanical resonance Parameter that should be Set Carrier frequency and Soft-PWM selection Speed smoothing control Refer to Page Pr. 72, Pr. 240 192 Pr. 653 193 5.18.1 PWM carrier frequency and soft-PWM control (Pr. 72, Pr. 240) You can change the motor sound.
Motor noise, EMI measures, mechanical resonance 5.18.2 Speed smoothing control (Pr. 653) Vibration due to mechanical resonance influences the inverter control, causing the output current (torque) unstable. In this case, the output current (torque) fluctuation can be reduced to ease vibration by changing the output frequency. Parameter Number 653 Name Speed smoothing control Initial Value Setting Range 0 0 to 200% Description Increase or decrease the value using 100% as reference to check an effect.
Misoperation prevention and parameter setting restriction 5.
Misoperation prevention and parameter setting restriction (3) How to restart the motor stopped by input in the Network operation mode (PU stop (PS) reset method) 1)After completion of deceleration to a stop, switch OFF the Speed STF or STR signal. Time Key 2)Press to display 3)Press to return to . .............. ( reset) Operation panel Key STF ON (STR) OFF . 4)Switch ON the STF or STR signal.
Misoperation prevention and parameter setting restriction 5.19.2 Parameter write disable selection (Pr. 77) You can select whether write to various parameters can be performed or not. Use this function to prevent parameter values from being rewritten by misoperation. Parameter Name Number Initial Value Parameter write selection 77 Setting Range 0 Description 0 Write is enabled only during a stop. 1 Parameter can not be written.
Misoperation prevention and parameter setting restriction 5.19.3 Reverse rotation prevention selection (Pr. 78) This function can prevent reverse rotation fault resulting from the incorrect input of the start signal. Parameter Name Number Initial Value Reverse rotation prevention selection 78 Setting Range 0 Description 0 Both forward and reverse rotations allowed 1 Reverse rotation disabled 2 Forward rotation disabled The above parameters can be set when Pr.
Misoperation prevention and parameter setting restriction (3) Registration of parameter to user group (Pr. 173) When registering Pr. 3 to user group Operation Display 1. Confirm the operation display and operation mode display. The inverter should be at a stop. Make sure that the inverter is in PU operation mode. 2. Press to choose the parameter setting Parameter setting mode mode. 3. Turn " to change the set value to Displays Pr. 173 User group registration ". 4. Press to display 5.
Misoperation prevention and parameter setting restriction 5.19.5 Password function (Pr. 296, Pr. 297) Registering a 4-digit password can restrict parameter reading/writing. Parameter Number 296 ∗1 Name Initial Value Password lock level Setting Range Description 0 to 6, 99, 100 to Select restriction level of parameter reading/ writing when a password is registered. 106, 199 ∗4 9999 9999 No password lock 1000 to 9998 Register a 4-digit password Displays password unlock error count.
Misoperation prevention and parameter setting restriction REMARKS After registering a password, a read value of Pr. 297 is always one of "0" to "5". When a password restricted parameter is read/written, is displayed. Even if a password is registered, parameters which the inverter itself writes, such as inverter parts life, are overwritten as needed. There are two ways of unlocking the password. Enter a password in Pr. 297. Unlocked when a password is correct.
Special operation and frequency control 5.20 Special operation and frequency control Purpose Parameter that should be Set Perform jog operation Perform process control such as pump and air volume. Frequency control appropriate for load torque Avoid overvoltage alarm due to regeneration by automatic adjustment of output frequency Jog operation Pr. 15, Pr. 16 Pr. 127 to Pr. 132, Pr. 134, Pr. 125, C2 PID control Droop control Regeneration avoidance function Refer to Page 201 203 Pr. 286, Pr.
Special operation and frequency control (1) Jog operation from operation panel Selects Jog operation mode from the operation panel. Operation is performed only while the start button is pressed. Operation 1. Confirmation of the operating status indicator Display and operation mode indicator The monitor mode should have been selected. The inverter should be at a stop. 2. Press to choose the PU Jog operation mode. 3. Press While . is pressed, the motor rotates. Hold down. The motor runs at 5Hz.
Special operation and frequency control 5.20.2 PID control (Pr. 125, Pr. 127 to Pr. 132, Pr. 134, C2) The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure. Use the value set in the CC-Link communication register (RWw9) as the set point, and the value set in the CC-Link communication register (RWwA) as the feedback value. With these values, configure a feedback system and perform PID control.
Special operation and frequency control Pr.
Special operation and frequency control 4)Reverse operation Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is positive, and decreases the manipulated variable if deviation is negative.
Special operation and frequency control (4) I/O signals and parameter setting Set "50, 51, 60 or 61" in Pr. 128 to perform PID operation. Set "14" in any of Pr. 180 to Pr. 184 (input terminal function selection) to assign the PID control selection signal (X14) to turn the X14 signal ON. When the X14 signal is not assigned, only the Pr. 128 setting makes PID control valid. Enter the set point and measured value via CC-Link communication. REMARKS When Pr.
Special operation and frequency control (5) PID automatic switchover control (Pr. 127) The system can be started up without PID control only at a start. When the frequency is set to Pr. 127 PID control automatic switchover frequency within the range 0 to 400Hz, the inverter starts up without PID control from a start until output frequency is reached to the set frequency of Pr. 127, and then it shifts to PID control.
Special operation and frequency control (7) Adjustment procedure Parameter setting Adjust the PID control parameters, Pr.127 to Pr.134. Set the I/O virtual terminals for PID control (Pr. 180 to Pr. 184 (input Virtual terminal setting terminal function selection), Pr. 190 to Pr. 192 and Pr. 313 to Pr. 315 (output terminal function selection)) When X14 signal is not assigned, setting a value other than "0" in Pr. 128 Turn ON the X14 signal. activates PID operation.
Special operation and frequency control Changing the frequency at a deviation input (Pr.125, C2) To change the output frequency at 0% deviation, set the new frequency in C2 Frequency setting bias (initially 0Hz). To change the output frequency at 100% deviation, set the new frequency in Pr. 125 Frequency setting gain (initially 60Hz). Initial value 60Hz Output frequency (Hz) Gain Pr.
Special operation and frequency control 5.20.3 Droop control (Pr. 286, Pr. 287) AD MFVC This function is designed to balance the load in proportion to the load torque to provide the speed drooping characteristic under Advanced magnetic flux vector control. This function is effective for balancing the load when using multiple inverters. Parameter Name Number Initial Setting Value Range 0 286 Droop gain 0% Droop control is invalid (Normal operation) 0.
Special operation and frequency control 5.20.4 Regeneration avoidance function (Pr. 665, Pr. 882, Pr. 883, Pr. 885, Pr. 886) This function detects a regeneration status and increases the frequency to avoid the regenerative status. Possible to avoid regeneration by automatically increasing the frequency and continue operation if the fan happens to rotate faster than the set speed due to the effect of another fan in the same duct.
Special operation and frequency control REMARKS The acceleration/deceleration ramp while the regeneration avoidance function is operating changes depending on the regeneration load. The DC bus voltage of the inverter is about 2 times as input voltage. When the input voltage is 220VAC, bus voltage is approximately 311VDC. When the input voltage is 440VAC, bus voltage is approximately 622VDC. However, it varies with the input power supply waveform. The Pr.
Useful functions 5.21 Useful functions Purpose Parameter that should be Set Increase cooling fan life To determine the maintenance time of parts. Communication using USB (FR Configurator) Freely available parameter Cooling fan operation selection Inverter part life display Maintenance output function Current average value monitor signal USB communication Refer to Page Pr. 244 213 Pr. 255 to Pr. 259 214 Pr. 503, Pr. 504 217 Pr. 555 to Pr. 557 218 Pr. 547, Pr. 548, Pr. 551 220 Pr. 888, Pr.
Useful functions 5.21.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259) Degrees of deterioration of main circuit capacitor, control circuit capacitor, cooling fan and inrush current limit circuit can be diagnosed by monitor. When any part has approached the end of its life, an alarm can be output by self diagnosis to prevent a fault. (Use the life check of this function as a guideline since the life except the main circuit capacitor is calculated theoretically.
Useful functions (1) Life alarm display and signal output (Y90 signal, Pr. 255) Whether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit has reached the life alarm output level or not can be checked by Pr. 255 Life alarm status display and life alarm signal (Y90). bit 15 7 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 Pr. 255 read Pr.
Useful functions (4) Main circuit capacitor life display (Pr. 258, Pr. 259) The deterioration degree of the control circuit capacitor is displayed in Pr. 258 as a life. On the assumption that the main circuit capacitor capacitance at factory shipment is 100%, the capacitor life is displayed in Pr. 258 every time measurement is made. When the measured value falls to or below 85%, Pr. 255 bit 1 is turned ON and also an alarm is output to the Y90 signal.
Useful functions (5) Cooling fan life display The cooling fan speed of 50% or less is detected and "FN" is displayed on the operation panel. As an alarm display, Pr. 255 bit 2 is turned ON and also an alarm is output to the Y90 signal. REMARKS When the inverter is mounted with two or more cooling fans, "FN" is displayed with one or more fans with speed of 50% or less. NOTE For replacement of each part, contact the nearest Mitsubishi FA center. 5.21.3 Maintenance timer alarm (Pr. 503, Pr.
Useful functions 5.21.4 Average current monitor signal (Pr. 555 to Pr. 557) The average value of the output current during constant speed operation and the maintenance timer Programmable controller Output unit value are output as a pulse to the current average value monitor signal (Y93).
Useful functions 3) Setting of Pr. 557 Current average value monitor signal output reference current Set the reference (100%) for outputting the signal of the current average value. Obtain the time to output the signal from the following calculation. 4) Setting of Pr. 503 Maintenance timer After the output current average value is output as low pulse shape, the maintenance timer value is output as high pulse shape. The output time of the maintenance timer value is obtained from the following calculation.
Useful functions 5.21.5 USB communication (Pr. 547, Pr. 548, Pr. 551) Inverter setup can be easily performed using the FR Configurator by connecting the inverter and personal computer with a USB cable. A personal computer and inverter can be easily connected with one USB cable.
Useful functions REMARKS USB cable available on the market Name Model MR-J3USBCBL3M USB cable (2) Application/Specifications Cable length 3m Connector for amplifier mini-B connector (5 pin) Connector for personal computer A connector Select the command source of the PU operation mode (Pr. 551) Either the operation panel, or USB connector can be specified as the command source in the PU operation mode.
Useful functions 5.21.6 Free parameter (Pr. 888, Pr. 889) You can input any number within the setting range 0 to 9999. For example, the number can be used: As a unit number when multiple units are used. As a pattern number for each operation application when multiple units are used. As the year and month of introduction or inspection. Parameter Name Number Initial Value Setting Range Description 888 Free parameter 1 9999 0 to 9999 Any values can be set.
Setting from the operation panel 5.22 Setting from the operation panel Purpose Parameter that should be Set Selection of rotation direction by of the operation panel Use the setting dial of the operation panel like a potentiometer for frequency setting. Key lock of operation panel Change the magnitude of change of frequency setting by the setting dial of the operation panel Refer to Page RUN key rotation direction selection Pr. 40 223 Operation panel operation selection Pr.
Setting from the operation panel 5.22.2 Operation panel frequency setting/key lock operation selection (Pr. 161) The setting dial of the operation panel can be used for setting like a potentiometer. The key operation of the operation panel can be disabled. Parameter Name Number Initial Value Setting Description Range 0 Setting dial frequency setting 1 Setting dial potentiometer 0 161 10 Setting dial frequency setting 11 Setting dial potentiometer The above parameters can be set when Pr.
Setting from the operation panel Disable the setting dial and key operation of the operation panel (Press [MODE] long (2s)) Operation using the setting dial and key of the operation panel can be invalid to prevent parameter change, and unexpected start or frequency setting. Set "10 or 11" in Pr. 161, then press for 2s to make the setting dial and key operation invalid. When the setting dial and key operation are invalid, appears on the operation panel.
Setting from the operation panel 5.22.3 Magnitude of frequency change setting (Pr. 295) When setting the set frequency with the setting dial, frequency changes in 0.01Hz increments in the initial status. Setting this parameter increases the magnitude of frequency which changes according to the rotated amount of the setting dial, improving operability. Parameter Name Number Initial Value Setting 0 295 Magnitude of frequency change setting 0.01 0 Description Range 0.10 1.00 10.
Parameter clear/ All parameter clear 5.23 Parameter clear/ All parameter clear POINT Set "1" in Pr.CL Parameter clear, ALLC all parameter clear to initialize all parameters. (Parameters are not cleared when "1" is set in Pr. 77Parameter write selection.) Refer to the extended parameter list on page 84 for parameters cleared with this operation. Operation Display 1. Screen at power-ON The inverter starts up in Network operation mode. The monitor display appears. 2.
Initial value change list 5.24 Initial value change list Displays and sets the parameters changed from the initial value. Operation Display 1. Screen at power-ON The inverter starts up in Network operation mode. The monitor display appears. 2. Press to choose the PU operation mode. 3. Press to choose the parameter setting PU indicator is lit. PRM indicator is lit. mode. (The parameter number read previously appears.) 4. Turn 5. Pressing until appears.
Check and clear of the faults history 5.25 Check and clear of the faults history (1) Check for the faults history Monitor/frequency setting [Operation panel is used for operation] Faults history Parameter setting [Parameter setting change] [Operation for displaying the faults history] Eight past faults can be displayed with the setting dial. (The latest fault is ended by ".".) When no fault exists, i is displayed.
Check and clear of the faults history (2) Clearing procedure POINT Set "1" in Er.CL Fault history clear to clear the faults history. Operation Display 1. Screen at power-ON The inverter starts up in Network operation mode. The monitor display appears. 2. Press to choose the parameter setting mode. PRM indicator is lit. (The parameter number read previously appears.) 3. Turn until (faults history clear) appears. 4. Press to read the currently set value. " " (initial value) appears. 5.
6 TROUBLESHOOTING This chapter provides the "TROUBLESHOOTING" of this product. Always read the instructions before using the equipment. 6.1 6.2 6.3 6.4 6.5 Reset method of protective function ......................................... List of fault or alarm indications ................................................ Causes and corrective actions ................................................... Correspondences between digital and actual characters ....... Check first when you have a trouble ..........
Reset method of protective function When a fault occurs in the inverter, the inverter trips and the operation panel display automatically changes to one of the following fault or alarm indications. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales representative. Retention of fault output signal ..
List of fault or alarm indications List of fault or alarm indications Name Indication Error message Warning Alarm to Name Indication to Page Page Faults history 229 E.ILF Input phase loss 239 HOLD Operation panel lock 234 E.OLT Stall prevention stop 240 LOCD Password locked 234 E. BE Brake transistor alarm detection 240 E.GF Output side earth (ground) fault overcurrent at start 240 E.LF Output phase loss 240 E.OP1 Communication option fault 240 E.OPT Option fault 241 E.
Causes and corrective actions 6.3 Causes and corrective actions (1) Error message A message regarding operational troubles is displayed. Output is not shutoff. Operation panel indication Name Description HOLD Operation panel lock Operation lock mode is set. Operation other than Check point is invalid. (Refer to page 225) -------------- Corrective action Press for 2s to release lock. Operation panel LOCD indication Password locked Name Password function is active.
Causes and corrective actions (2) Warning When a warning occurs, the output is not shut off. indication Name Description Check point Corrective action Operation panel indication Name OL Stall prevention (overcurrent) When the output current (output torque when Pr. 277 Stall prevention current switchover = "1") of the inverter exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.
Causes and corrective actions Operation panel indication Name RB Regenerative brake prealarm Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 Special regenerative brake duty value. When the setting of Pr. 70 Special regenerative brake duty is the initial value (Pr. 70 = "0"), this warning does not occur. If Description the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs. The RBP signal can be simultaneously output with the [RB] display.
Causes and corrective actions Operation panel indication Name Description Check point Corrective action EV 24V external power supply operation Flickers when the main circuit power is not supplied and the 24V external power is supplied. Check if the 24V external power is supplied. Check if the power supply for the inverter (main circuit) is ON. Check if the power supply voltage is low. Check if the jumper between terminal P/+ and P1 is removed. Turn ON the power supply for the inverter (main circuit).
Causes and corrective actions Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description Check point Corrective action 238 E.
Causes and corrective actions Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description Check point Corrective action Inverter overload trip (electronic thermal relay function) If the temperature of the output transistor element exceeds the protection level under the condition that a current not less than the rated inverter current flows and overcurrent trip does not occur (230% or less), the electronic thermal relay activates to stop the in
Causes and corrective actions Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description E.OLT Stall prevention stop If the output frequency has fallen to 1Hz by stall prevention operation and remains for 3s, a fault (E.OLT) appears and trips the inverter. OL appears while stall prevention is being activated. E.OLT may not occur if stall prevention (OL) is activated during output phase loss. Check the motor for use under overload.
Causes and corrective actions Operation Panel E.OPT Indication Option fault Name Appears when a communication option is connected while Pr. 296 = "0 or 100." Description Check if password lock is activated by setting Pr. 296 = "0, 100" Check point Corrective action Operation panel indication Name Description Check point Corrective action To apply the password lock when installing a communication option, set Pr.296 ≠ "0,100". (Refer to page 199).
Causes and corrective actions Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description Check point Corrective action Operation panel indication Name Description Check point Corrective action E.MB4 to 7 to Brake sequence fault The inverter output is stopped when a sequence error occurs during use of the brake sequence function (Pr. 278 to Pr. 283). This protective function is not available in the initial status. (Refer to page 160).
Correspondences between digital and actual characters 6.
Check first when you have a trouble 6.5 Check first when you have a trouble POINT If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then set the required parameter values and check again. 6.5.1 Motor does not start Refer Check Possible Cause points Countermeasures to page Power ON a moulded case circuit breaker (MCCB), an Main circuit Appropriate power supply voltage is not applied.
Check first when you have a trouble Refer Check Possible Cause points to Countermeasures page Inverter decelerated to a stop when power failure deceleration stop function is selected. When power is restored, ensure the safety, and turn OFF the start signal once, then turn ON again to restart. 186 Inverter restarts when Pr. 261="2". When offline auto tuning ends, press on the operation panel for the PU operation. For the Network operation, turn OFF the start signal (STF or STR).
Check first when you have a trouble 6.5.2 Motor or machine is making abnormal acoustic noise Refer Check Possible Cause points Countermeasures to page In the initial setting, Pr. 240 Soft-PWM operation selection is No carrier frequency noises (metallic noises) are generated. enabled to change motor noise to an unoffending complex tone. Therefore, no carrier frequency noises 192 (metallic noises) are generated. Set Pr. 240 = "0" to disable this function. Set Pr. 31 to Pr. 36 (Frequency jump).
Check first when you have a trouble 6.5.5 Motor rotates in the opposite direction Refer Check Possible Cause points circuit Parameter Phase sequence of output terminals U, V and W is Connect phase sequence of the output cables (terminal incorrect. U, V, W) to the motor correctly Frequency command with sign (Pr. 541 = "1") is selected Check the Pr. 541 Frequency command sign selection (CC- for CC-Link communication. Link) setting. Pr.
Check first when you have a trouble 6.5.8 Speed varies during operation When Advanced magnetic flux vector control or the slip compensation is selected, the output frequency varies between 0 and 2Hz as load fluctuates. This is a normal operation and not a fault. Refer Check Possible Cause points Countermeasures to page Load Load varies during an operation. Input Frequency setting signal is varying.
Check first when you have a trouble 6.5.10 Operation panel display is not operating Refer Check Possible Cause points Countermeasures to page Check for the wiring and the installation. Main Wiring or installation is improper. circuit Make sure that the connector is fitted securely across 14 terminals P/+ and P1. Main circuit Power is not input. control Input the power. 14 circuit Command sources at the PU operation mode is not at Parameter setting the operation panel.
Check first when you have a trouble 6.5.12 Speed does not accelerate Refer Check Possible Cause points Countermeasures to page Check the settings of Pr. 1 Maximum frequency and Pr. 2 Pr. 1, Pr. 2, Pr. 18 settings are improper. Minimum frequency. If you want to run the motor at 120Hz 124 or higher, set Pr. 18 High speed maximum frequency. Torque boost (Pr. 0, Pr. 46) setting is improper under V/F Increase/decrease Pr.
7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION This chapter provides the "PRECAUTIONS FOR MAINTENANCE AND INSPECTION" of this product. Always read the instructions before using the equipment. 7.1 7.2 1 2 Inspection items............................................................................ 252 Measurement of main circuit voltages, currents and powers ..
Inspection items The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors. zPrecautions for maintenance and inspection For some short time after the power is switched OFF, a high voltage remains in the smoothing capacitor.
Inspection items Daily and periodic inspection Area of Inspection General Inspection Item Alarm Occurrence Improve environment Overall unit Check for unusual vibration and noise. Check alarm location and retighten Power supply voltage Check that the main circuit voltages are normal.∗1 Inspect the power supply (1) Check with megger (across main circuit terminals and earth (ground) terminal). Contact the manufacturer (2) Check for loose screws and bolts.
Inspection items 7.1.4 Display of the life of the inverter parts The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan and each parts of the inrush current limit circuit is near its end. It gives an indication of replacement time. The life alarm output can be used as a guideline for life judgement.
Inspection items 7.1.6 Cleaning Always run the inverter in a clean status. When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol. NOTE Do not use solvent, such as acetone, benzene, toluene and alcohol, as they will cause the inverter surface paint to peel off. The display, etc. of the operation panel are vulnerable to detergent and alcohol. Therefore, avoid using them for cleaning. 7.1.
Inspection items (1) Cooling fan The replacement interval of the cooling fan used for cooling the parts generating heat such as the main circuit semiconductor is greatly affected by the surrounding air temperature. When unusual noise and/or vibration is noticed during inspection, the cooling fan must be replaced immediately. zRemoval 1) Push the hooks from above and remove the fan cover. 3.7K or lower 5.5K or higher 2) Disconnect the fan connectors. 3) Remove the fan. 5.5K or higher 3.
Inspection items zReinstallation 1) After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up. AIR FLOW 2) Reconnect the fan connectors. 3) When wiring, avoid the cables being caught by the fan. 5.5K or higher 3.7K or lower 5.5K or higher 3.7K or lower 2. Insert hooks until you hear a click sound. 1. Insert hooks into holes. Example for FR-E740-3.7KNC 1. Insert hooks into holes. 2. Insert hooks until you hear a click sound.
Inspection items (2) Smoothing capacitors A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum electrolytic capacitor is used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the adverse effects of ripple currents, etc. The replacement intervals greatly vary with the surrounding air temperature and operating conditions.
Measurement of main circuit voltages, currents and powers 7.2 Measurement of main circuit voltages, currents and powers Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data depends on the instruments used and circuits measured. When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments given on the next page. When installing meters etc.
Measurement of main circuit voltages, currents and powers Measuring Points and Instruments Item Power supply voltage V1 Measuring Point R/L1 and S/L2 S/L2 and T/L3 T/L3 and R/L1 ∗3 Power supply side current I1 Power supply side power P1 Measuring Instrument Moving-iron type AC voltmeter ∗4 R/L1, S/L2, T/L3 line Moving-iron type AC current ∗3 ammeter ∗4 R/L1, S/L2, T/L3 and Digital power meter R/L1 and S/L2, (designed for inverter) or S/L2 and T/L3, electrodynamic type single- T/L3 and R/L1 ∗3
Measurement of main circuit voltages, currents and powers 7.2.1 Measurement of powers Use electro-dynamometer type meters (for inverter) for the both of inverter input and output side. Alternatively, measure using electrodynamic type single-phase wattmeters for the both of inverter input and output side in two-wattmeter or threewattmeter method. As the current is liable to be imbalanced especially in the input side, it is recommended to use the threewattmeter method.
Measurement of main circuit voltages, currents and powers 7.2.3 Measurement of currents Use a moving-iron type meter on both the input and output sides of the inverter. However, if the carrier frequency exceeds 5kHz, do not use that meter since an overcurrent losses produced in the internal metal parts of the meter will increase and the meter may burn out. In this case, use an approximate-effective value type.
Measurement of main circuit voltages, currents and powers 7.2.7 Insulation resistance test using megger For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test on the control circuit. (Use a 500VDC megger.
MEMO 264
8 SPECIFICATIONS This chapter provides the "SPECIFICATIONS" of this product. 1 Always read the instructions before using the equipment. 8.1 Rating............................................................................................. 266 8.2 Common specifications ............................................................... 268 8.3 Outline dimension drawings........................................................
Rating 8.1 Rating Three-phase 200V power supply 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 Applicable motor capacity (kW) ∗1 Model FR-E720- KNC 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 Rated capacity (kVA) ∗2 0.3 0.6 1.2 2.0 3.2 4.4 7.0 9.5 13.1 18.7 23.9 0.8 (0.8) 1.5 (1.4) 3 (2.5) 5 (4.1) 8 (7) 11 (10) 17.5 (16.5) 24 (23) 33 (31) 47 (44) 60 (57) 20 28 6.5 6.
Rating Single-phase 200V power supply 0.1 0.2 0.4 0.75 1.5 2.2 0.1 0.2 0.4 0.75 1.5 2.2 Rated capacity (kVA)∗2 0.3 0.6 1.2 2.0 3.2 4.4 0.8 (0.8) 1.5 (1.4) 3.0 (2.5) 5.0 (4.1) 8.0 (7.0) 11.0 (10.
Common specifications Operation specifications Control specifications 8.2 Common specifications Control method Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control, General-purpose magnetic flux vector control, Optimum excitation control are available) Output frequency range 0.2 to 400Hz Frequency setting resolution (Digital 0.01Hz input) Frequency accuracy (Digital input) Within 0.
Outline dimension drawings 8.3 Outline dimension drawings 5 FR-E720-0.1KNC to 0.75KNC FR-E720S-0.1KNC to 0.4KNC 128 118 5 hole Rating plate Capacity plate 4 5 5 D1 56 68 D Inverter Model FR-E720-0.1KNC, 0.2KNC FR-E720S-0.1KNC, 0.2KNC FR-E720-0.4KNC FR-E720-0.75KNC FR-E720S-0.4KNC D D1 108 10 140 160 170 42 62 42 (Unit: mm) 5 FR-E720-1.5KNC, 2.2KNC FR-E720S-0.75KNC, 1.5KNC FAN Capacity plate Rating plate 128 118 2- 5 hole 5 D1 108 D Inverter Model FR-E720-1.5KNC, 2.
Outline dimension drawings 5 FR-E720-3.7KNC FAN Capacity plate Rating plate 128 118 2- 5 hole 5 5 5 158 170 66.5 170 (Unit: mm) FR-E720-5.5KNC to 15KNC 8 2- 6hole 260 244 FAN Rating plate D2 8 6 D1 W1 W Capacity plate D Inverter Model W W1 W2 D D1 FR-E720-5.5KNC, 7.5KNC 180 164 180 192.5 71.5 D2 10 FR-E720-11KNC, 15KNC 220 195 211 217.5 84.5 10.
Outline dimension drawings 2- 5 hole 6 FR-E740-0.4KNC to 3.7KNC FR-E720S-2.2KNC *1 150 138 FAN Rating plate Capacity plate 128 140 6 5 5 D1 D *1 FR-E740-0.4KNC, 0.75KNC are not provided with the cooling fan. Inverter Model D D1 FR-E740-0.4KNC, 0.75KNC 141.5 39 FR-E740-1.5KNC to 3.7KNC 162.5 FR-E720S-2.2KNC 183 60 (Unit: mm) FR-E740-5.5KNC, 7.5KNC 6 2- 5 hole Rating plate 10 6 208 220 68 174.
Outline dimension drawings 2- 6 hole 8 FR-E740-11KNC, 15KNC 260 244 FAN Rating plate 10.5 8 6 84.5 195 220 Capacity plate 217.
APPENDIX This chapter provides the "APPENDIX" of this product. Always read the instructions before using the equipment.
Appendix 1 Main differences with the FR-E500(N) CC-Link model Item Control method Shape Connectable units FR-E500 (N) FR-E700 (NC) V/F control General-purpose magnetic flux vector control V/F control General-purpose magnetic flux vector control Advanced magnetic flux vector control Optimum excitation control Terminal block connection (removable from the inverter front) Two one-touch connectors dedicated to CC-Link communication Up to 42 units (one unit occupies one station).
Appendix 2 Specification change Appendix 2-1 SERIAL number check Check the SERIAL number indicated on the inverter rating plate or package. (Refer to page 2) Rating plate example Symbol Year Month Control number SERIAL (Serial No.) The SERIAL consists of one symbol, two characters indicating production year and month, and six characters indicating control number. Last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (November), and Z (December).
Appendix 3 Index Numerics Cumulative energization time................................................. 176 Cumulative power .................................................................... 176 Cumulative power 2 ................................................................. 176 Current average value monitor signal (Pr. 555 to Pr. 557) 218 Current average value monitor signal (Y93 signal) .... 167, 218 15-speed selection (combination with three speeds RL, RM, RH)(REX signal) .......................
544 = "18") .................................................................................. 59 I/O signal when CC-Link Ver.2 quadruple setting is selected (Pr. 544 = "14")........................................................................... 58 Input phase loss (E.ILF).................................................. 190, 239 Input terminal function selection (Pr. 180 to Pr. 184)......... 163 Input to the inverter from the network.....................................
Program example for reading the inverter status ..................69 Program example for resetting the inverter at inverter error ................................................................................73 Program example for setting the operation commands .......70 Program example for setting the operation mode .................69 Program example for setting the running frequency.............72 PU stop (PS) .....................................................................
MEMO 279
REVISIONS *The manual number is given on the bottom left of the back cover. Print Date Nov. 2011 ∗Manual Number IB(NA)-0600402ENG-A Revision First edition For Maximum Safety • Mitsubishi inverters are not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life.
BCN-C22005-659.fm 1 ページ 2013年8月29日 木曜日 午後12時59分 FR-E700-NC Series Instruction Manual Supplement 1 For the terminating resistor selection switch Please make corrections to the following error in this manual. Connection of several inverters Instruction Manual (Basic) : page 17 Instruction Manual (Applied): page 50 (Incorrect) Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.
BCN-C22005-659.fm 2 ページ 2013年8月29日 木曜日 午後12時59分 2 Additional notes for instructions for UL and cUL Instruction Manual (Basic) : page 43 General precaution CAUTION - Risk of Electric Shock The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes. Motor overload protection When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 "Electronic thermal O/L relay".
FR-E700-NC INVERTER FR-E700 INSTRUCTION MANUAL (Applied) CC-Link communication function INVERTER FR-E720-0.1KNC to 15KNC FR-E740-0.4KNC to 15KNC FR-E720S-0.1KNC to 2.2KNC OUTLINE 1 WIRING 2 PRECAUTIONS FOR USE OF THE INVERTER 3 CC-LINK COMMUNICATION FUNCTION IB(NA)-0600402ENG-A (1111)MEE Printed in Japan Specifications subject to change without notice.