Special operation and frequency control
5
PARAMETERS
4)Reverse operation
Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is positive, and
decreases the manipulated variable if deviation is negative.
5)Forward operation
Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is negative, and
decreases the manipulated variable if deviation is positive.
Relationships between deviation and manipulated variable (output frequency)
(3) Connection diagram
Deviation
Positive Negative
Reverse action
Forward action
Pr. 128 = 60
∗1 The power supply must be selected in accordance with the power specifications of the detector used.
Set point
X>0
X<0
Feedback signal
(measured value)
+
-
[Heating]
Deviation
Set point
Measured value
Decrease
Cold
Increase
Hot
Set point
X>0
X<0
Feedback signal
(measured value)
+
-
[Cooling]
Deviation
Set point
Measured value
Too cold
Decrease
Hot
Increase