SPECIFICATIONS
Rating
Single-phase 200V power supply
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
∗2 The rated output capacity indicated assumes that the output voltage is 230V.
∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or
power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.
∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply.
∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large.
(Option brake resistor cannot be used for 0.1K and 0.2K.) A brake unit (FR-BU2) may also be used.
∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation with the surrounding air temperature exceeding 40°C, the
rated output current is the value in parentheses.
Model FR-E720S-KNC 0.1 0.2 0.4 0.75 1.5 2.2
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75 1.5 2.2
Output
Rated capacity (kVA)∗2 0.3 0.6 1.2 2.0 3.2 4.4
Rated current (A)∗7
0.8
(0.8)
1.5
(1.4)
3.0
(2.5)
5.0
(4.1)
8.0
(7.0)
11.0
(10.0)
Overload current rating∗3 150% 60s, 200% 3s (inverse-time characteristics)
Rated voltage∗4 Three-phase 200 to 240V
Regenerative braking torque ∗5 150% 100% 50% 20%
Power supply
Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz
Permissible frequency fluctuation Within ±5%
Power supply capacity (kVA)∗6 0.5 0.9 1.5 2.5 4.0 5.2
Protective structure (JEM1030) Open type (IP00)
Cooling system Self-cooling Forced air cooling
Approximate mass (kg) 0.6 0.6 0.9 1.4 1.5 2.0