PPO TYPE SUPPORT SPECIFICATION
PZD STW
0 to 2 Not used (1 is set)
Control
enable
3
0: Inverter output shutoff
1: Inverter output shutoff is cancelled
4 to 6 Not used (1 is set)
Fault reset
(Reset)
7
[At inverter error]
0: No action
1: When Pr. 349=0, error reset can be made in any operation mode.
When Pr. 349=1, error reset is enabled only in NET operation mode.
[When inverter is normal]
No action
8 to 9 Not used (0 is set)
PZD
enable
10
0: Command request of PZD is not processed.
*1
1: Command request of PZD is processed.
At power-on or inverter reset, set 1 once.
STF signal 11 0: OFF 1: ON (forward rotation command)
STR signal 12 0: OFF 1: ON (reverse rotation command)
RT
terminal
13
0: OFF 1: ON
Functions are changed according to the Pr. 183 setting.
MRS
terminal
14
0: OFF
1: ON (output is shut off)
Functions are changed according to the Pr.187 setting. However, do not change
the factory-set value "6".
RAM/
EEPROM
15
0: Set frequency (HSW) is written to RAM (Power-on reset returns the changed
set frequency to the setting before it was written to RAM.).
1: Set frequency (HSW) is written to EEPROM.
*1 PZD enable and command count request can be executed.
Name Bit Definition