Instruction manual

Table Of Contents
50
PPO TYPE SUPPORT SPECIFICATION
PZD ZSW
0 to 2 Not used (1 is returned)
Fault 3
0: Inverter normal
1: Inverter alarm occurrence
4 to 5 Not used (1 is returned)
Power-on
inhibit
6 0 is returned
Alarm 7
Command execution normal
Command execution error
8 Not used (0 is returned)
Control
request
9 1 is returned
FU signal 10
0: OFF
1: ON (output frequency being detected) (Refer to Pr. 42 and Pr. 43 in the inverter
manual.)
RUN
signal
11
0: OFF
1: ON (inverter running)
FWD 12
0: Other than forward running (during stop, reverse running)
1: Forward running
REW 13
0: Other than reverse running (during stop, forward running)
1: Reverse running
NET mode 14
0: Other than network operation mode
1: Network operation mode
Name Bit Definition
A7NP.book 50 ページ 2010年12月9日 木曜日 午前11時36分