Datasheet

14
c
Power Supply Specications
Item
Specications
FX5U-32M FX5U-64M FX5U-80M
Rated voltage 100 to 240 V AC
Allowable supply voltage range 85 to 264 V AC
Frequency rating 50/60 Hz
Allowable instantaneous power failure time Operation can be continued upon occurrence of instantaneous
power failure for 10 ms or less.
Power fuse 250 V, 3.15 A
Time-lag fuse
250 V, 5 A Time-lag fuse
Rush current 25 A max. 5 ms or
less/100 V AC
50 A max. 5 ms or
less/200 V AC
30 A max. 5 ms or less/100 V AC
60 A max. 5 ms or less/200 V AC
Power consumption
[1
30 W 40 W 45 W
5 V DC power supply capacity 900 mA 1100 mA 1100 mA
24 V DC service power
supply capacity
[2
When service power
supply is used for input
circuits
400 mA 600 mA 600 mA
When external power
supply is used for input
circuits
480 mA 740 mA 770 mA
CPU module specication
c
Number of device points
Item Base Max. number of points
No. of user
device points
Input relay (X) 8
1024 points
The total number of input/output
points must not exceed 256 points.
Output relay (Y) 8
1024 points
Internal relay (M) 10 32768 points (can be changed with parameter)
[1
Latch relay (L) 10 32768 points (can be changed with parameter)
[1
Link relay (B) 16 32768 points (can be changed with parameter)
[1
Annunciator (F) 10 32768 points (can be changed with parameter)
[1
Link special relay (SB) 16 32768 points (can be changed with parameter)
[1
Step relay (S) 10 4096 points (xed)
Timer system Timer (T) 10 1024 points (can be changed with parameter)
[1
Accumulation
timer system
Accumulation
timer (ST)
10 1024 points (can be changed with parameter)
[1
Counter
system
Counter (C) 10 1024 points (can be changed with parameter)
[1
Long counter (LC)
10 1024 points (can be changed with parameter)
[1
Data register (D) 10 8000 points (can be changed with parameter)
[1
Link register (W) 16 32768 points (can be changed with parameter)
[1
Link special register (SW) 16 32768 points (can be changed with parameter)
[1
No. of system
device points
Special relay (SM) 10 10000 points (xed)
Special register (SD) 10 12000 points (xed)
Item Base Max. number of points
Module access
device
Intelligent function
module device
10 65536 points (designated by U
c
\G
c
)
No. of index
register points
Index register(z)
[2
10 24 points
Long index register (LZ)
[2
10 12 points
No. of le
register points
File register (R) 10 32768 points (can be changed with parameter)
[1
No. of nesting
points
Nesting (N) 10 15 points (xed)
No. of pointer
points
Pointer (P) 10 4096 points
Interrupt pointer (I) 10 178 points (xed)
Others Decimal
constant (K)
Signed 16 bits: -32768 to 32767,
32 bits: -2147483648 to 2147483647
Unsigned 16 bits: 0 to 65535, 32 bits: 0 to 4294967295
Hexadecimal constant (H) 16 bits: 0 to FFFF, 32 bits: 0 to FFFFFFFF
Real constant
(
E)
Single precision E-3.40282347+38 to E-1.17549435-38, 0,
E1.17549435-38 to E3.40282347+38
Character string Shift-JIS code max. 255 single-byte characters
(256 including NULL)
[
1 : Can be changed with parameters within the capacity range of the CPU built-in memory.
[
2 : Total of the index register (Z) and long index register (LZ) is maximum 24 words.
c
Generic Specications
Item Specications
Operating ambient
temperature
[1
0 to 55°C (32 to 131°F)
[2
Storage ambient temperature
-25 to 75°C(-13 to 167°F )
Operating ambient humidity
5 to 95%RH, non-condensation
Storage ambient humidity 5 to 95%RH, non-condensation
Vibration resistance
[2
Frequency Acceleration Half amplitude Sweep count
Installed on
DIN rail
5 to 8.4 Hz
1.75 mm
10 times each in
X, Y, Z directions
(80 min in each
direction)
8.4 to 150 Hz
4.9 m/s
2
Direct
installing
5 to 8.4 Hz
3.5 mm
8.4 to 150 Hz 9.8 m/s
2
Shock resistance
[3
147 m/s
2
, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
Noise durability By noise simulator at noise voltage of 1000 Vp-p,
noise width of 1 μs and period of 30 to 100 Hz
Grounding Class D grounding (grounding resistance: 100 Ω or less) <Common grounding with a
heavy electrical system is not allowed.>
[4
Operating atmosphere Free from corrosive or ammable gas and excessive conductive dust
Operating altitude
[5
0 to 2000 m
Installation location Inside a control panel
Overvoltage category or less
Pollution degree
[6
2 or less
Equipment class Class 2
c
Performance Specications
Item Specications
Control system Stored-program repetitive operation
Input/output control system Refresh system
(Direct access input/output allowed by specication of direct access input/output [DX, DY])
Programming specications Programming language Ladder diagram (LD), structured text (ST)
Programming extension function Function block (FB), structured ladder, label programming (local/global)
Constant scan 0.2 to 2000 ms (can be set in 0.1 ms increments)
Fixed cycle interrupt 1 to 60000 ms (can be set in 1 ms increments)
Timer performance specications 100 ms, 10 ms, 1 ms
No. of program executions 32
No. of FB les 16
Operation
specications
Execution type Standby type, initial execution type, scan execution type, event execution type
Interrupt type Internal timer interrupt, interrupt from input, high-speed comparison match interrupt
Command
processing time
LD X0 34 ns
MOV D0 D1 34 ns
Memory capacity Program capacity 64 K steps (128 Kbytes)
SD memory card Memory card capacity (SD/SDHC memory card: Max. 4 Gbytes)
Device/label memory 120 Kbytes
Data memory/standard ROM 5 Mbytes
Flash memory write count Maximum 20000 times
File storage capacity Device/label memory 1
Data memory
P: No. of program les/FB: No. of FB les
P: 32, FB: 16
Clock function Display data Year, month, day, hour, minute, second, day of week (leap year automatic detection)
Precision -2.96 to +3.74 s (TYP.+1.42 s/d at 0°C (32°F))
-3.18 to +3.74 s (TYP.+1.50 s/d at 25°C (77°F))
-13.20 to +2.12 s (TYP.-3.54 s/d at 55°C (131°F))
No. of input/
output points
(1) No. of input/output points 256 points or less
(2) No. of remote I/O points 384 points or less
Total No. of points of (1) and (2) 512 points or less
Power failure
retention
[1
Retention method Large-capacity capacitor
Retention time 10 days
Data retained Clock data
[1
: The retention period of a fully charged capacitor (electricity is conducted across the PLC for at least 30 minutes) is 10 days (ambient temperature: 25°C (77°F)).
[1
: The simultaneous ON ratio of available PLC inputs or outputs changes with respect to the ambient temperature, refer to
manuals of each product.
[
2 : For details on Intelligent function modules, refer to manuals of each product.
[
3 : The criterion is shown in IEC61131-2.
[
4 : Ground the PLC independently or jointly.
[
5 : The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
[
6 : This index indicates the degree to which conductive material is generated in the environment in which the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be
expected occasionally.
[
1 : This value is for when all 24 V DC service power supplies are used in the maximum conguration in which they can be
connected to the CPU module.
The input current is included.
[
2 : When I/O modules are connected, they consume current from the 24 V DC service power.