. ELECTRICAL WORK..........................................................................................................................................WR2SD-2 1-1. General Cautions......................................................................................................................................WR2SD-2 1-2. Power Supply for Indoor Unit and Outdoor Unit........................................................................................WR2SD-3 1-3. Power Cable Specifications........
1. ELECTRICAL WORK WR2-SERIES SYSTEM DESIGN 1-1. General Cautions Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations, and guidance of each electric power company. Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in] or more) apart from power source wiring so that it is not influenced by electric noise from power source wiring.
1. ELECTRICAL WORK 1-2.
WR2-SERIES SYSTEM DESIGN 1. ELECTRICAL WORK Model PCFY-P15NKMU-E PCFY-P24NKMU-E PCFY-P30NKMU-E PCFY-P36NKMU-E PKFY-P06NBMU-E PKFY-P08NBMU-E PKFY-P12NHMU-E PKFY-P15NHMU-E PKFY-P18NHMU-E PKFY-P24NKMU-E PKFY-P30NKMU-E PFFY-P06NEMU-E PFFY-P08NEMU-E PFFY-P12NEMU-E PFFY-P15NEMU-E PFFY-P18NEMU-E PFFY-P24NEMU-E PFFY-P06NRMU-E PFFY-P08NRMU-E PFFY-P12NRMU-E PFFY-P15NRMU-E PFFY-P18NRMU-E PFFY-P24NRMU-E Hz 60Hz 60Hz 60Hz 60Hz Symbols: MCA : Min.Circuit Amps (=1.
1. ELECTRICAL WORK 1-2-2. Electrical Characteristics of Water-source Unit PQRY-P-T(S)HMU Model Unit Combination PQRY-P72THMU-A PQRY-P96THMU-A PQRY-P120THMU-A PQRY-P144TSHMU-A PQRY-P168TSHMU-A PQRY-P192TSHMU-A PQRY-P216TSHMU-A PQRY-P240TSHMU-A Hz PQRY-P72THMU-A PQRY-P72THMU-A PQRY-P72THMU-A PQRY-P96THMU-A 60Hz PQRY-P96THMU-A PQRY-P96THMU-A PQRY-P96THMU-A PQRY-P120THMU-A PQRY-P120THMU-A PQRY-P120THMU-A Water-source unit Voltage range RLA(A) 12.6/11.4 18.0/16.2 23.6/21.4 12.6/11.4 12.6/11.4 12.6/11.
1. ELECTRICAL WORK 1-2-3. Electrical Characteristics of BC Controller WR2-SERIES SYSTEM DESIGN Symbols: MCA : Min.Circuit Amps (=1.25 x RLA) RLA : Rated Load Amps BC-Controller for PQRY-P-TGMU Model Hz CMB-P104NU-G CMB-P105NU-G CMB-P106NU-G CMB-P108NU-G CMB-P1010NU-G CMB-P1013NU-G CMB-P1016NU-G 60Hz CMB-P108NU-GA CMB-P1010NU-GA CMB-P1013NU-GA CMB-P1016NU-GA CMB-P104NU-GB CMB-P108NU-GB WR2SD-6 Volts Voltage range 208 / 230V 198 to 253V MCA(A) 0.36 / 0.34 0.45 / 0.40 0.53 / 0.48 0.68 / 0.61 0.
1. ELECTRICAL WORK 1-3. Power Cable Specifications Minimum wire thickness (mm2/AWG) Main cable Branch Ground PQRY-P72YHMU-A 2.1/14 2.1/14 Water-source PQRY-P96YHMU-A 2.1/14 2.1/14 unit PQRY-P120YHMU-A 3.3/12 3.3/12 Indoor unit 0.41/22 0.41/22 0.41/22 Model Breaker for current leakage 15A 30mA or 100mA 0.1sec. or less 15A 30mA or 100mA 0.1sec. or less 20A 30mA or 100mA 0.1sec. or less 15A 30mA or 100mA 0.1sec.
1. ELECTRICAL WORK WR2-SERIES SYSTEM DESIGN 1-4. Power Supply Examples The local standards and/or regulations is applicable at a higher priority. 1-4-1. PQRY-P72, 96, 120THMU/YHMU Note: 1 The transmission cable is not-polarity double-wire. 2 Symbol means a screw terminal for wiring. 3 The shield wire of transmission cable should be connected to the grounding terminal at Heat source unit.
1. ELECTRICAL WORK The local standards and/or regulations is applicable at a higher priority. 1-4-2. PQRY-P144, 168, 192, 216, 240TSHMU/YSHMU Note12 Central control transmission cable >=1.
2. M-NET CONTROL 2-1-1. Using MA Remote controller Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission. Max. length via Heat source (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker Max. length to Heat source (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thicker Max. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.
2. M-NET CONTROL 2-2. Transmission Cable Specifications Cable size ME Remote controller cables More than 1.25 Remarks Connected with simple remote controller. — [AWG16] MA Remote controller cables Sheathed 2-core cable (unshielded) CVV Shielding wire (2-core) CVVS, CPEVS or MVVS 0.3 1.25 (0.75 1.25 2 2 [AWG22 16] [AWG18 16]) 0.3 1.25 (0.75 1.25 When 10m [32ft] is exceeded, use cables with the same specification as transmission cables.
2. M-NET CONTROL WR2-SERIES SYSTEM DESIGN 2-3. System Configuration Restrictions 2-3-1. Common restrictions for the CITY MULTI system For each Heat source unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table. A) 1 Group of Indoor units can have 1-16 Indoor units; B) Maximum 2 remote controllers for 1 Group; C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
2. M-NET CONTROL 2-3-3. Ensuring proper power supply to System controller 2-3-3-A. When connecting to TB3 of the Heat source unit and receiving power from the Heat source unit. Maximum 3 System controllers can be connected to TB3. Fig.
2. M-NET CONTROL WR2-SERIES SYSTEM DESIGN 2-3-4. Power supply to LM adapter LMAP03U 1-phase 208-230V AC power supply is needed. The power supply unit is not necessary when connecting only the LMAP03U. Yet, make sure to change the power supply changeover connector CN41 to CN40 on the LM adapter. 2-3-5. Power supply to expansion controller 1-phase 100-240VAC power supply is needed. The power supply unit PAC-SC51KUA is not necessary.
2. M-NET CONTROL 2-4. Address Setting Unit address No. setting 01 9 7 8 7 8 01 2 3 9 2 3 45 6 D BC E F 0 12 3456 789A À Address No. of heat source unit, indoor unit and remote controller. The address No. is set at the address setting board. In the case of WR2 system, it is necessary to set the same No. at the branch No. switch of indoor unit as that of the BC controller connected. (When connecting two or more branches, use the lowest branch No.
2. M-NET CONTROL 2-4-2. Rule of setting address 7 8 4 5 6 10 1 7 8 7 8 7 8 7 8 7 8 4 5 6 4 5 6 7 8 7 8 45 6 45 6 7 8 7 8 45 6 45 6 1 7 8 9 45 6 10 The smallest address of indoor unit in the group + 100 The place of "100" is fixed to "1" The address of main remote controller + 50 The address automatically becomes "200" if it is set as "00" The smallest group No.
2. M-NET CONTROL WR2-SERIES SYSTEM DESIGN 2-4-3. System examples Factory setting Original switch setting of the heat sources, indoors, controllers and LMAP at shipment is as follows.
2. M-NET CONTROL WR2-SERIES SYSTEM DESIGN 2-4-3-2.
2. M-NET CONTROL 2-4-3-3.
2. M-NET CONTROL WR2-SERIES SYSTEM DESIGN 2-4-3-4.
2. M-NET CONTROL 2-4-3-6.
WR2-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-8. TG-2000A+AG-150A/GB-50A AG-150A/GB-50A can control max. 50 indoor units; TG-2000A can control max. 40 pieces of AG-150A*2 or GB-50A; TG-2000A can control max. 2000 indoor units.
2. M-NET CONTROL LMAP(01) LMAP can transmission for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
2-4-3-10. BM ADAPTER BM ADAPTER can transmission for max. 50 indoor units; Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected without the power supply unit.
3. PIPING DESIGN 3-1. R410 Piping Material The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Ta ble 3-1, or You shall follow the local industrial standard. Pipes of radical thickness 0.7mm or less shall not be used. Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.
3. PIPING DESIGN r 3-2-1. IF 16 ports or less are in use, I.e., if only one BC controller is in use with no sub BC controller. Note1. PQRY systems do not require headers. Note2. Indoor units sized P72-P96 should be connected to a BC controller using the Y-shaped CMY-R160-J joint adapter. These indoor units cannot use the same BC controller ports as other units. (They must use their own individual BC controller port.) Note3.
3. PIPING DESIGN 3-2-2. IF more than 16 ports are in use, or if there is more than one BC controller in use for one heat source unit HU IU e A Field supplied BC controller (Main BC) H a h1 b IU IU (P06-P18) IU (P24-P54) h1 BC controller (Sub BC) h3 C CMY-Y102S-G2 (Joint) Reducer (P06-P18) (attached with BC controller) H' D E BC controller (Sub BC) h2 B CMY-R160-J (Joint) (P72-P96) c d IU IU f Max.3 sets for 1 port.
3. PIPING DESIGN WR2-SERIES SYSTEM DESIGN 3-2-3. IF more than 16 ports are in use, or if there is more than one BC controller in use for two heat source units Note1. PQRY systems do not require headers. Note2. Indoor units sized P72-P96 should be connected to a BC controller using the Y-shaped CMY-R160-J joint adapter. These indoor units cannot use the same BC controller ports as other units. (They must use their own individual BC controller port.) Note3.
3. PIPING DESIGN 3-2-4.
3. PIPING DESIGN WR2-SERIES SYSTEM DESIGN 3-3. Refrigerant Charging Calculation Sample connection (with 3 BC controller and 6 indoor units) HU (Main unit) HU (Sub unit) H F Heat source Twinning kit (High/Low press.) CMY-Q100VBK: The Low press. kit must be placed in the heat source unit that has a larger capacity index of the two, regardless of the relative positions of the heat source units or their addresses.
4. INSTALLATION 4-1. PQRY-P-T(S)HMU/Y(S)HMU’s Installation Install indoors; avoid exposing the unit to outside elements. Do not install in an area where it could be subjected to direct heat. Avoid installing the unit in a location where the operating sound could be an annoyance. Install on a stable, load-bearing surface.
4. INSTALLATION WR2-SERIES SYSTEM DESIGN 4-3. Piping Direction 1. Insulation installation With City Multi WY/ WR2 Series piping, as long as the temperature range of the circulating water is kept to average temperatures year-round (29.4°C[85°F] in the summer, 21.1°C[70°F] in the winter), there is no need to insulate or otherwise protect indoor piping from exposure. You should use insulation in the following situations: • Any heat source piping.
5. CAUTIONS The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards. The following standard may be applicable if no local regulation or standard is available. R410A refrigerant is harmless and incombustible. The R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room has possibility to lead to a hypoxia situation.
WR2-SERIES SYSTEM DESIGN WR2SD-34 WR2-SERIES SYSTEM DESIGN (June 2010)