Service manual

28
Check of indoor electronic control P.C. board
C
The unit doesn’t operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Replace the fuse.
Replace the indoor electronic
control P.C. board.
Replace the varistor.
Yes
No
Is varistor(NR11)burnt?
Yes
Is fuse(F11)blown?
Check of outdoor unit
D
<MUCFH-18TN - >
S1
Start
Press EMERGENCY OPERATION
switch. 3-minute time delay works.
Test run operation operates for 30
minutes.
Check the outdoor DEICER P.C.board and
compressor contactor at first, then check the
outdoor fan motor and compressor.
Check the continuity of indoor and outdoor
unit connection.
No
No
Yes
Yes
Check voltage to terminal
block of indoor unit. Is
there 220V AC to terminal
block between 2 - N ?
Check voltage to terminal
block of outdoor unit. Is
there 220V AC to termi-
nal block between 2 - N
?
No
Be sure to check both fuse
and varistor in any case.
Replace the indoor electronic control
P.C.board.
Check both “parts side” and
“pattern side” of indoor
electronic control P.C. board
visually.
Compressor and / or outdoor fan motor does not operate.
OB286-1.qxp 02.7.23 11:04 AM Page 28