ADVANCE AND EVER ADVANCING 2000 SPLIT-TYPE, AIR CONDITIONERS TECHNICAL & SERVICE MANUAL This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC149B and this manual as a set. PU-2VJA2.UK PU-2.5VJA2.UK Service ref. Models PED-2EJA1.UK PED-2.5EJA1.UK CONTENTS INDOOR UNIT 1. FEATURES ················································· 1 2. PART NAMES AND FUNCTIONS ·············· 2 3.
1 FEATURES lndoor unit Remote controller Models Cooling capacity (240V) W Btu/h 18,800 5,500 22,200 6,500 PED-2EJA1.UK PED-2.5EJA1.UK 1. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILING The totally hidden indoor unit that lies above the ceiling surface enables you to utilize full floor space while allowing for flexible interior design. This new feature is recommended for stores and offices where the user's own imagination is allowed to be incorporated. 2.
5. ADVANCED MICROPROCESSOR CONTROL (1) Ultra - thin 12mm(1/2" )remote controller. (2) Attractive LED display . Every operation condition is indicated on the LED display. (3) Simultaneous display of set temperature and room temperature. (4) Convenient 12 - hour ON-OFF timer. This convenient timer allows the unit to be switched on and off automatically,at the time you set. Once the timer is set,the remaining time is shown on the LED display..
● Remote controller ● Settings remain in effect until changed. Air conditioner can be operated by simply pushing ON/OFF button once settings have been made. ● Operation buttons (Example display readings are for explanations only ;actual display readings will differ.
3 SPECIFICATION Model Item Cooling capacity ✻4 OUTDOOR UNIT INDOOR UNIT Total input ✻4 Power supply Input Running current Starting current External finish Heat exchanger Fan (drive) ~No. Fan motor output ✻1 Airflow (Low-High) External static pressure ✻2 Operation control & Thermostat Noise level (Low-High) ✻ 3, ✻5 Cond. drain conn. O.D.
4 DATA 1. PERFORMANCE DATA 1) COOLING CAPACITY Service Ref. PED2EJA1.UK PED2.5EJA1.UK Indoor intake air WB˚C 16 18 20 22 16 18 20 22 20 CA 5,599 5,957 6,320 6,688 6,617 7,039 7,468 7,904 Outdoor intake air DB˚C 30 35 CA P.C. CA P.C. 2.54 4,989 2.38 5,225 2.61 5,324 2.44 5,566 2.66 5,676 2.49 5,929 2.72 6,050 2.54 6,309 2.60 5,896 2.43 6,175 2.66 6,292 2.49 6,578 2.72 6,708 2.54 7,007 2.79 7,150 2.60 7,456 25 P.C. 2.13 2.17 2.21 2.25 2.18 2.22 2.26 2.
3. FAN PERFORMANCE AND CORRECTED AIR FLOW PED-2EJA1.UK Fan Performance <30Pa> Corrected Air Flow 120 Correction factor 100 80 60 40 20 6 160 External static pressure (Pa) (1Pa 0.1mmAg) 1.1 8 1.0 0.9 0.8 10 10 12 14 16 18 20 Air Flow (CMM) Fan Performance <70Pa> 12 14 16 18 Air flow (CMM) 20 22 12 14 16 18 Air flow (CMM) 20 22 Heating 1.3 140 120 100 80 60 40 1.2 1.1 1.0 0.9 0.8 8 10 20 8 Capacity input Cooling 8 Correction factor External static pressure (Pa) (1Pa 0.
4. ELECTRICAL DATA Indoor ······220V 50Hz 1phase Outdoor ··· 220V 50Hz 1phase Indoor PED-2EJA1.UK PED-2.5EJA1.UK Outdoor PU-2VJA PU-2.5VJA Capacity(W) 5,400 6,300 Total input(kW) 2.57 2.61 Input(kW) 0.13 0.15 Current(A) 0.60 0.69 Starting current(A) 1.05 1.53 Input(kW) 2.44 2.46 Current(A) 11.3 11.4 48 48 Indoor PED-2EJA1.UK PED-2.5EJA1.UK Outdoor PU-2VJA PU-2.5VJA Capacity(W) 5,450 6,400 Total input(kW) 2.60 2.65 Input(kW) 0.14 0.16 Current(A) 0.61 0.
5. STANDARD OPERATION DATA (COOLING) Total Models W 5,500 6,500 Input kW 2.63 2.69 PED-2EJA PED-2.5EJA 1, 50 1, 50 Refrigerant circuit Electrical circuit Phase Hz Outdoor Indoor side side PED-2.5EJA1.UK Capacity Indoor unit model 5 PED-2EJA1.UK Volts 240 240 Amperes 0.63 0.72 PU-2VJA PU-2.5VJA 1, 50 1, 50 Outdoor unit-model Phase,Hz Volts 240 240 Amperes 10.8 10.7 Discharge pressure MPa 1.98 2.00 Suction pressure MPa 0.46 0.51 Discharge temperature ˚C 77.3 78.
6 OUTLINES & DIMENSIONS 1. INDOOR UNIT PED-2EJA1.UK PED-2.5EJA1.UK 55 Access door 8 B 81 197 355 Lifting bolt hole (14✕22) 18 56 Refrigerant piping flare connection (liquid ø9.52 copper tube):HP Refrigerant piping flare connection (gas ø15.88 copper tube):LP Drain R1(External thread) Electrical parts box Electric Heater···Only PEHD-EKHA Type Drain Pump (Option) Set Drain Pipe (Option)···Use VP25(O.D.
7 WIRING DIAGRAM MODELS:PED-2,2.5EJA1 WIRING DIAGRAM I.B 4321 SW1 OFF ON 321 SW3 OFF ON CN51 CN31 CND MULTIPLE HEATER POWER CN30 CN120 ZNR OUTDOOR TO RC OFF ON 321 X6 X5 CNT TRANS DS 2 DP RED 25 3 41 6 3 1 GRN/YLW 1 1 3 7 BLK BLU WHT BRN YLW 3 GRN/YLW WHT 31 BRN WHT BRN AC10.6V RED 1 T ORN RED GRY GRY BLK BLK 432 1 AC14.
8 DISASSEMBLY INSTRUCTIONS Figure1. Disconnect the fan motor connecter (and the booster heater connector) Drain pan catches (Hidden) 1 Heat exchanger 2 Bottom plate assembly Filter Drain pan catches (Hidden) Bottom plate A 1. Removing the fan motor 1. Removing the 9 screws that fix the bottom plate A, and remove it. 2. Removing the drain pan as follows: (1) Remove the screw that fixes the drain pan.
Figure3.
Figure4. Drain socket Pump cover assembly Drain pan cover Drain pump assembly Drain hose 1 2 Rubber plug Drain pan 2. Removing the drain water lift-up pump 1. Remove the drain pan. (Refer 1- 2.) 2. Disconnect the drain pump connector and drain sensor connector from the controller box. 3. Remove the two screws of the pump cover assembly. 4. Remove the drain hose from drain socket. 5. Remove the three screws of the drain pump assembly. 6.
9 PARTS LIST PED-2EJA1.UK PED-2.5EJA1.UK EXTERNAL PARTS 5, 6 3, 4 9, 10 7, 8 1.2 Qt’y/set No. Part No. Part Name Drawing No. PED- PED- 2EJA1 2.5EJA1 1 S70 031 669 Bottom plate 1 W638939Z03 2 S70 011 669 Bottom plate 1 W638917Z03 3 S70 081 669 Bottom plate 2 ass’y W638940G02 4 S70 091 669 Bottom plate 2 ass’y W638918G02 5 S70 020 480 H.EX.General ass’y W268511G02 6 S70 021 480 H.EX.
PED-2EJA1.UK PED-2.5EJA1.UK BLOWER PARTS 2, 3 5, 6 9, 10 7, 8 11 4 4 1 5, 6 1 7, 8 Qt'y/set No. Part No. Part Name Drawing No. PED- PED- 2EJA1 2.
PED-2EJA1.UK PED-2.5EJA1.UK CONTROL BOX PARTS 4 3 7 6 2 5 1 7 Qt’y/set No. Part No. Part Name 1 S70 918 717 Terminalbed Drawing No. P436109X01 PED- Spec. PED- 2EJA1 2.5EJA1 1 1 2 S70 979 717 Terminalbed P436110X01 1 1 3 S70 010 310 Controller BG00L760G22 1 1
PED-2EJA1.UK PED-2.5EJA1.UK ELECTRICAL PARTS 1 3 2 Qt’y/set No. Part No. Part Name Drawing No. PED- Spec. PED- 2EJA1 2.5EJA1 1 S70 010 713 Remote controller BC00C006G34 1 1 J controller 2 S70 A00 305 Remote controller cable BG00K507G02 1 1 10m 3 S70 010 304 Cable ( for board ) 1 1 0.
PED-2EJA1.UK PED-2.5EJA1.UK DRAIN WATER LIFT-UP PUMP PARTS (OPTIONAL PARTS) 3 4 1.2 5 Qt’y/set No. Part No. Part Name Drawing No. PED- PED- 2EJA1 2.5EJA1 1 1 1 S70 11K 355 Drain pump-94 BG56J144G13 2 S70 010 533 DB26F111H03 4 4 3 S70 K01 523 Drain socket ass’y BB00P145G17 1 1 4 S70 W28 266 Drain sensor ass’y DE00H343G21 1 1 5 S70 E69 558 Rubber plug P312040X01 1 1 18 Cushion Spec.
10 MICROPROCESSOR CONTROL 19
l 20
l 21
l l after 22
23
24
11 TROUBLE SHOOTING 25
26
12 OPTIONAL PARTS 1. REFRIGERANT PIPES Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E 5m 7m 10m 15m Pipe length Pipe size OD Liquid:/ø9.52 Gas:/ø15.88 Connection method Indoor unit:Flared Outdoor unit:Flared Note 1.How to connect refrigerant pipes. Factory supplied optional piping contains refrigerant at above atmospheric pressure. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
3-3 HOW to connect program timer (1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below. NOTE: While the program timer is connected to the remote controller, the 24 hour ON/OFF timer on the remote controller will not operate.
4. CENTRALIZED REMOTE CONTROLLER Allows individual or combined control of up to 16 units. Part No. PAC-805RC 4-1 Dimensions 113 12 23.5 56.5 11 8 113 117 Unit:mm 117 4-2 Functions "ENGAGED" indicator When this indicator is lit, transmisson is in progress and all swiches are inoperative. DUAL / CENTRAL switch This change-over switch governs the operation of the accessory remote controller. "DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid.
4-3 Connection method (1) Connection in the power supply cord. 1. Connect the power supply cord to the power supply terminal-block and fix in-place with a tie-wrap. Connect a single phase 200V AC(220, 230, 240V)to AN . As E is the GND terminal,be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a ø1.6 (AWG14)or above two-wire cable for the transmission line.
5. PROGRAM TIMER ADAPTER This adapter is needed when a program timer(PAC-815PT)or a centralised remote controller(PAC-805RC)is used. Part No.
6. TIMER ADAPTER This adapter is needed for system control and for operation via external contacts. Part No. PAC-SA89TA-E ORN 1 BRN 2 RED 3 7. REMOTE INDICATION ADAPTER This adapter is used for remote indication(operation/check.) Part No. BRN RED ORN YRW GRN JST XHP3 PAC-559AD BRN RED CN51 ORN connector(5P) GRN ± 25 Applied model 32 PED-2EJA1.UK, PED-2.5EJA1.UK X1 RL X2 GL X1 X2 insulation is needed.
TM HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO MEE00K028 Issued in Nov. 2000 Printed in Japan New publication, effective Nov. 2000 Specifications subject to change without notice.