AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS DATA BOOK Series : PE(H) Cooling only Heat pump Model PE-7MYC PE-8MYC PE-10MYC PE-15MYC PE-20MYC Service ref.
CONTENTS SAFETY FOR USE ------------------------------------------------------2 A COMPLETE LINE UP ------------------------------------------------4 FEATURES-----------------------------------------------------------------5 DESCRIPTIONS----------------------------------------------------------5 MECHANICAL SPECIFICATIONS ----------------------------------6 TYPICAL INSTALLATION EXAMPLE ------------------------------6 MODEL-DESIGNATION BREAKDOWN ---------------------------7 SPECIFICATIONS --------------------
SAFETY FOR USE Before conducting installation work, please read this ''SAFETY FOR USE'' carefully for correct installation. Since the caution items shown here contain important description relative to safety, please observe them without fail. Warning Erroneous handling gives a high possibility to induce serious results such as death or heavy injury. Caution Erroneous handling may induce serious injury depending on the situation.
Caution Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely. The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock. Never install on the place where a combustible gas might leak. The gas may ignite or explode when the gas leaks and collects in surround of the unit.
A COMPLETE LINE UP Cooling capacity Heating capacity (PEH only) PEH-5 PE(H)-7 PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20 kW 14.4 17.9 22.0 28.8 44.0 57.6 Btu/h 49,150 61,000 75,100 98,300 150,200 196,600 kcal/h 12,400 15,400 18,900 24,800 37,900 49,600 kW 14.4 18.8 22.0 28.8 44.0 57.6 Btu/h 49,150 64,100 75,100 98,300 150,200 196,600 kcal/h 12,400 16,200 18,900 24,800 37,900 49,600 Note: Cooling & heating capacities are based following conditions.
FEATURES High sensible cooling capacity. Labour saving installation. The sensible cooling capacity has been significantly improved through balanced optimised heat exchanger design. The unit operation can commence immediately after connecting to the power supply, refrigerant piping, drain piping, ducting and control system. Comfort heating. (PEH only) Wide electrical control capability. The PEH series are designed to provide effective heating even when the outside temperature is down to -10 .
MECHANICAL SPECIFICATIONS General Condenser Coils Unnecessary power input due to higher discharge pressure is avoided by high performance designs of cross-finned coil. Condenser coils are made of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick aluminium fins and factory pressure and leak tested at 3.3MPa. All units are factory assembled, piped, internally wired. They are also tested and checked under a strict quality control system in the factory.
MODEL-DESIGNATION BREAKDOWN P E - 10 M Y C 1 Service reference Design Sequence Electrical Supply Y = 3 phase 380~415V 50Hz 4 wires ( In case of PE(H)-7 Indoor unit Y = 1 phase 220~240V 50Hz 2 wires Compressor Horsepower 5 = 5 HP 7 = 7 HP 8 = 7.
SPECIFICATIONS Cooling only PE-7~20MYC Model name Service reference Power supply Indoor Outdoor Total cooling capacity Sensible cooling capacity Capacity step Refrigerant Refrigerant charge kW Btu/h kcal/h kW Btu/h kcal/h kg Service reference PE-10MYC PE-15MYC PE-20MYC PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU 1PH 2W220~240V 50Hz 3PH 4W 380~415V 50Hz 17.9 61,100 22.0 75,100 18,900 17.6 60,100 15,100 15,400 14.3 48,800 12,300 3PH 4W380 ~ 415V 50Hz 3PH 4W380 ~ 415V 50Hz 28.8 44.
PEH-5,7,8MYA Heat pump Model name Service reference Power supply Indoor Outdoor Total cooling capacity Sensible cooling capacity Sensible heating capacity Capacity step Refrigerant Refrigerant charge Refrigerant control Indoor Unit Model name kW Btu/h kcal/h kW Btu/h kcal/h kW Btu/h kcal/h % kg Service reference External finish Dimension Height Width Depth Net weight Indoor coil Indoor fan Indoor fan motor mm mm mm kg PEH-7MYA PEH-8MYA PEH-7MYA-EU PEH-8MYA-EU 3PH 4W380~415V 50Hz 1PH 2W220~24
PEH-10,15,20MYA Heat pump Model name Service reference Power supply Indoor Outdoor Total cooling capacity Sensible cooling capacity Sensible heating capacity Capacity step Refrigerant Refrigerant charge Refrigerant control Indoor Unit Model name PEH-20MYA PEH-20MYA-EU 3PH 4W380 ~ 415V 50Hz 44.0 150,200 37,900 35.2 120,200 30,200 44.0 150,200 37,800 28.8 98,300 24,800 23.0 78,500 19,800 28.8 98,300 kW Btu/h kcal/h kW Btu/h kcal/h kW Btu/h kcal/h 24,800 0-100 % 57.6 196,600 49,600 46.
ELECTRICAL DATA PE-7~20MYC-EU Cooling VOLT PE-7 240V TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT PERUN CURRENT 8 20 INDOOR FAN INPUT 415V RUN CURRENT OUTDOOR FAN INPUT RUN CURRENT PE-7 220V kW A kW A kW A PE-7MYC-EU PU-7MYC1-EU 7.2 14.6 74 6.0 10.7 0.8 3.2 0.4 0.7 kW A % A 7.2 15.9 81 7.8 15.5 74 91 10.1 20.7 74 90 17.6 32.3 83 131 22.0 42.7 78 152 kW A kW A kW A 6.0 11.6 0.8 3.5 0.4 0.8 6.8 13.4 0.6 1.3 0.4 0.8 8.6 17.6 1.0 2.1 0.5 1.0 2X7.65 2X13.65 1.7 3.
PEH-5,7,8MYA-EU Cooling VOLT kW A kW A kW A PEH-5MYA-EU PUH-5MYE-EU 5.5 9.5 80 69 4.7 8.1 0.54 0.9 0.25 0.5 PEH-7MYA-EU PUH-7MYC1-EU 7.2 14.6 74 6.0 10.7 0.8 3.2 0.4 0.7 kW A % A 5.5 10.4 80 69 7.2 15.9 81 7.8 15.5 76 91 7.9 16.0 75 91 kW A kW A kW A 4.7 8.85 0.54 1.0 0.25 0.55 6.0 11.6 0.8 3.5 0.4 0.8 6.8 13.4 0.6 1.3 0.4 0.8 6.77 13.4 0.6 1.3 0.53 1.3 kW A kW A kW A PEH-5MYA-EU PUH-5MYE-EU 4.5 8.5 73 69 3.7 7.1 0.54 0.9 0.25 0.5 PEH-7MYA-EU PUH-7MYC1-EU 6.3 13.6 74 5.1 9.7 0.8 3.2 0.4 0.
PEH-10,15,20MYA-EU Cooling VOLT ITEM TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR PEH-7 START CURRENT 240V COMPRESSOR INPUT PEHRUN CURRENT 8 20 INDOOR FAN INPUT 415V RUN CURRENT OUTDOOR FAN INPUT RUN CURRENT TOTAL INPUT TOTAL RUN CURRENT PEH-7 POWER FACTOR 220V START CURRENT COMPRESSOR INPUT PEHRUN CURRENT 8 20 INDOOR FAN INPUT 380V RUN CURRENT OUTDOOR FAN INPUT RUN CURRENT kW A % A kW A kW A kW A PEH-10MYA-EU PUH-10MYE-EU PUH-10MYC1-EU 10.1 10.2 18.9 19.1 74 74 82 82 8.57 8.67 15.9 15.9 1.0 1.0 2.0 2.
SELECTION PROCEDURE 1. Model Selection (With actual examples) First step, to select the approximate model: Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.
(Step-3) Calculation of net capacity Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages 16~35). Then, calculate the net capacity from the formula below by using the fan motor input obtained in Step-2. Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW) Example: PE-8MYC OUTDOOR DB˚C Condition: Indoor conditioned temp.
- 16 - 19.0 24 17.3 21 18.5 17.3 20 23 19.0 24 17.9 18.5 23 22 17.9 17.3 20 22 16.1 19 17.3 18.5 23 21 17.9 22 16.1 19 17.3 15.6 18 21 17.3 21 17.3 17.3 20 20 16.1 15.0 17 19 14.5 16 15.6 16.1 19 18 15.6 14.5 16 18 13.9 15 15.0 15.0 17 17 14.5 13.9 15 16 Q kW WB ˚C 10.7 11.5 12.2 12.9 14.0 8.9 9.8 10.7 11.4 12.7 13.0 8.1 9.0 9.8 10.9 11.3 12.1 8.1 9.3 9.8 10.6 11.5 12.3 8.3 9.1 9.9 10.6 11.3 8.3 9.1 9.
- 17 - 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.3 3.3 9.1 9.1 9.0 9.0 8.9 8.9 8.8 8.8 8.7 8.7 18 19 20 21 22 23 24 25 26 27 4.2 4.2 4.2 4.3 4.3 4.4 4.4 4.4 4.5 4.5 14.3 14.2 14.2 14.1 14.1 14.0 14.0 13.9 13.9 13.8 13.7 13.6 16 17 18 19 20 21 22 23 24 25 26 27 12.3 12.3 12.2 12.2 12.2 12.1 12.1 12.0 12.0 11.9 11.8 3.4 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.7 15.6 15.7 15.8 15.9 15.9 16.0 16.1 16.1 16.2 16.3 16.3 16.4 16.4 17.
- 18 - 10.8 9.6 17.7 18.4 16.9 17.7 16 17 15 16 10.9 9.7 19.3 19.9 17.7 18.4 18 19 16 17 10.9 9.7 21.2 22.0 19.3 19.9 20 21 18 19 11.0 9.9 22.8 23.7 19.9 21.2 22 23 19 20 13.1 12.0 10.9 22.8 23.7 24.7 21.2 22.0 22 23 24 20 21 15.1 14.2 13.2 22.8 23.7 24.7 22 23 24 16.2 17.2 14.1 22.0 21 15.3 15.9 12.1 22.0 21 13.1 21.2 20 13.9 15.0 11.8 19.9 19 12.9 19.3 18 14.0 15.0 11.8 18.4 17 12.8 13.5 11.7 16.
- 19 - 0.59 0.52 14.1 13.0 23.9 24.7 23 24 0.72 16.0 22.2 21 0.65 0.78 16.8 21.5 20 15.1 0.44 11.0 24.7 24 23.1 0.50 12.1 23.9 23 22 0.56 20 0.62 0.78 15.9 20.3 19 13.0 0.41 9.8 23.9 23 23.1 0.47 10.9 23.1 22 22 0.54 12.0 22.2 21 0.70 0.60 12.9 21.5 20 13.8 0.68 13.7 20.3 19 15.1 0.75 14.8 19.7 18 22.2 0.44 9.8 22.2 21 21.5 0.51 11.0 21.5 20 21 0.58 11.8 20.3 0.73 0.82 19 13.7 14.6 0.65 18.7 17 0.49 12.8 17.9 16 10.
- 20 - 15.0 13.5 27.9 28.8 25.2 26.1 23 24 20 21 17.6 16.2 27.0 27.9 28.8 22 23 24 18.8 20.3 21.6 16.4 17.7 18.9 27.0 25.2 20 20.1 22 24.4 19 11.9 26.1 27.9 23 13.4 14.9 16.2 17.6 18.7 12.1 13.7 15.1 16.4 17.7 18.9 12.5 13.6 14.7 16.1 17.5 12.4 13.7 14.9 SHCkW 21 27.0 22 24.4 19 26.1 23.5 18 21 26.1 21 25.2 25.2 20 20 24.4 22.7 17 19 22.0 16 23.5 24.4 19 18 23.5 22.0 16 18 21.3 15 22.7 22.7 17 17 22.0 21.
- 21 - 0.53 0.80 0.72 0.65 0.51 0.85 0.76 0.68 0.60 0.53 0.45 0.77 11.9 16.6 15.6 14.5 12.3 18.3 17.1 15.7 14.4 13.1 11.7 17.8 22.5 20.7 21.6 22.5 24.0 21.6 22.5 23.2 24.0 24.8 25.8 23.2 6.0 5.8 5.9 6.0 6.1 6.2 5.9 6.0 6.1 6.2 6.3 6.4 6.1 0.53 0.80 0.72 0.64 0.58 0.51 0.85 0.76 0.67 0.60 0.53 0.46 0.78 12.0 16.7 15.8 14.5 13.5 12.5 18.6 17.2 15.8 14.6 13.4 12.1 18.3 20.9 21.9 22.6 23.5 24.3 21.9 22.6 23.5 24.3 25.2 26.
- 22 - 15.0 13.5 27.9 28.8 25.2 26.1 23 24 20 21 17.6 16.2 27.0 27.9 28.8 22 23 24 18.8 20.3 21.6 16.4 17.7 18.9 27.0 25.2 20 20.1 22 24.4 19 11.9 26.1 27.9 23 13.4 14.9 16.2 17.6 18.7 12.1 13.7 15.1 16.4 17.7 18.9 12.5 13.6 14.7 16.1 17.5 12.4 13.7 14.9 SHCkW 21 27.0 22 24.4 19 26.1 23.5 18 21 26.1 21 25.2 25.2 20 20 24.4 22.7 17 19 22.0 16 23.5 24.4 19 18 23.5 22.0 16 18 21.3 15 22.7 22.7 17 17 22.0 21.
- 23 - 0.53 0.80 0.72 0.65 0.51 0.85 0.76 0.68 0.60 0.53 0.45 0.77 11.9 16.6 15.6 14.5 12.3 18.3 17.1 15.7 14.4 13.1 11.7 17.8 22.5 20.7 21.6 22.5 24.0 21.6 22.5 23.2 24.0 24.8 25.8 23.2 6.1 5.9 6.0 6.1 6.2 6.3 6.0 6.1 6.2 6.3 6.4 6.5 6.2 0.53 0.80 0.72 0.64 0.58 0.51 0.85 0.76 0.67 0.60 0.53 0.46 0.78 12.0 16.7 15.8 14.5 13.5 12.5 18.6 17.2 15.8 14.6 13.4 12.1 18.3 20.9 21.9 22.6 23.5 24.3 21.9 22.6 23.5 24.3 25.2 26.
- 24 - 18.0 16.3 35.8 36.9 32.1 34.6 23 19 20 19.7 17.9 36.9 38.0 34.6 34.6 23 24 20 21 23.0 21.4 35.8 36.9 38.0 22 23 24 24.5 25.8 28.0 21.3 35.8 22 22.8 34.6 21 25.4 26.0 19.6 21.8 22.6 24.2 22 32.1 19 34.6 31.1 18 16.1 21 34.6 21 18.6 34.6 34.6 20 19.6 21.3 23.0 24.6 16.5 18.3 19.8 21.3 22.5 16.7 18.2 19.6 SHCkW 20 32.1 30.0 17 19 28.9 16 31.1 32.1 19 18 31.1 28.9 16 18 27.8 15 30.0 30.0 17 17 28.9 27.
- 25 - 0.54 0.79 0.72 0.64 0.58 0.51 0.82 0.75 0.67 0.60 0.53 0.46 0.76 16.1 22.0 20.7 19.3 17.8 16.4 23.8 22.3 20.7 19.2 18.2 15.8 23.5 29.9 27.8 28.9 29.9 30.9 32.1 28.9 29.9 30.9 32.1 34.4 34.4 30.9 7.8 7.5 7.7 7.8 7.9 7.9 7.7 7.8 7.9 7.9 8.0 8.1 7.9 0.54 0.79 0.71 0.64 0.57 0.51 0.82 0.74 0.67 0.60 0.53 0.46 0.76 16.3 22.3 20.9 19.4 17.9 16.6 24.0 22.6 20.9 19.5 18.4 16.0 23.7 28.2 29.3 30.3 31.3 32.6 29.3 30.3 31.
- 26 - 18.0 16.3 35.8 36.9 32.1 34.6 23 19 20 19.7 17.9 36.9 38.0 34.6 34.6 23 24 20 21 23.0 21.4 35.8 36.9 38.0 22 23 24 24.5 25.8 28.0 21.3 35.8 22 22.8 34.6 21 25.4 26.0 19.6 21.8 22.6 22 32.1 19 24.2 34.6 31.1 18 16.1 21 34.6 21 18.6 34.6 34.6 20 19.6 21.3 23.0 24.6 16.5 18.3 19.8 21.3 22.5 16.7 18.2 19.6 SHCkW 20 32.1 30.0 17 19 28.9 16 31.1 32.1 19 18 31.1 28.9 16 18 27.8 15 30.0 30.0 17 17 28.9 27.
- 27 - 0.54 0.79 0.72 0.64 0.58 16.1 22.0 20.7 19.3 17.8 29.9 27.8 28.9 29.9 30.9 7.9 7.6 7.8 7.9 0.54 0.79 16.3 22.3 28.2 15 16 0.62 0.56 0.50 0.44 0.79 0.71 0.64 0.58 0.53 0.47 0.79 0.73 21.6 19.5 17.9 16.2 25.7 24.9 22.2 21.0 19.5 17.9 27.5 25.4 34.9 34.9 36.0 37.0 32.6 34.9 34.9 36.0 37.0 37.8 34.9 34.9 20 21 22 23 19 20 21 22 23 24 20 21 0.67 0.61 0.55 24.0 22.5 20.7 36.0 37.0 37.8 22 23 24 19 0.73 25.1 34.4 8.
- 28 - 57.6 24 52.2 21 55.8 50.4 20 23 57.6 24 54.0 55.8 23 22 54.0 50.4 20 22 48.8 19 52.2 55.8 23 21 54.0 22 48.8 19 52.2 47.0 18 21 52.2 21 50.4 50.4 20 20 48.8 45.4 17 19 44.0 16 47.0 48.8 19 18 47.0 44.0 16 18 42.6 15 45.4 45.4 17 17 44.0 42.6 15 16 Q kW WB ˚C 32.4 35.2 37.7 40.6 43.2 27.0 30.0 32.8 35.4 37.8 40.1 23.7 26.9 29.7 32.4 35.1 37.4 24.3 27.3 30.2 32.7 35.4 37.9 25.0 27.2 29.3 32.3 35.0 24.8 27.
- 29 - 52.4 46.9 21 18 48.6 50.4 19 20 14.1 0.46 14.8 0.44 14.8 15.0 0.62 0.55 34.4 32.1 55.7 58.0 24 56.2 54.2 52.5 COOLING CAPACITY TOTAL INPUT SHC AIR VOLUME 120 2,000 0.976 0.991 0.963 CMM L/S Factor for Various Air Flow PE-15MYC-EU 31.1 33.5 35.9 2,334 1.0 1.0 1.0 16.3 15.8 54.5 52.6 160 2,660 1.025 1.009 1.044 30.2 32.5 34.8 0.55 0.62 0.68 0.76 37.1 49.0 15.3 50.9 0.83 39.4 47.3 15.1 15.6 0.46 0.53 25.3 28.0 0.60 0.67 32.9 30.7 0.74 0.
- 30 - 52.2 47.0 21 18 55.8 57.6 24 52.2 21 23 50.4 20 54.0 57.6 24 22 55.8 50.4 20 23 48.8 19 54.0 55.8 23 22 54.0 22 52.2 52.2 21 21 50.4 20 48.8 50.4 20 19 48.8 45.4 17 19 44.0 16 47.0 48.8 19 18 47.0 44.0 16 18 42.6 15 45.4 45.4 17 17 44.0 42.6 15 16 Q kW WB ˚C 32.4 35.2 37.7 40.6 43.2 27.0 30.0 32.8 35.4 37.8 40.1 23.7 26.9 29.7 32.4 35.1 37.4 24.3 27.3 30.2 32.7 35.4 37.9 25.0 27.2 29.3 32.3 35.0 24.8 27.
- 31 - 52.4 46.9 21 18 0.43 0.80 0.73 0.67 0.60 0.47 0.83 0.76 23.3 37.8 35.9 33.8 31.5 26.2 40.4 38.3 54.2 47.2 48.8 50.7 52.5 56.2 48.8 50.7 13.7 14.2 13.1 13.3 13.5 13.7 14.2 14.4 13.3 13.5 0.44 0.80 0.73 0.66 0.60 0.53 0.47 0.82 0.75 24.4 39.0 36.9 34.8 32.4 29.7 27.1 41.4 39.5 55.7 48.6 50.4 52.4 54.2 55.7 58.0 50.4 52.4 19 20 21 22 23 24 20 21 COOLING CAPACITY TOTAL INPUT SHC AIR VOLUME 120 2,000 0.976 0.991 0.
- 32 - 76.0 24 69.2 21 73.8 69.2 20 23 76.0 24 71.6 73.8 23 22 71.6 69.2 20 22 64.2 19 69.2 73.8 23 21 71.6 22 64.2 19 69.2 62.2 18 21 69.2 21 69.2 69.2 20 20 64.2 60.0 17 19 57.8 16 62.2 64.2 19 18 62.2 57.8 16 18 55.6 15 60.0 60.0 17 17 57.8 55.6 15 16 Q kW WB ˚C 42.8 46.0 48.9 51.6 56.0 35.8 39.3 42.7 45.6 50.8 52.0 32.5 36.0 39.2 43.5 45.2 48.5 32.3 37.3 39.3 42.6 46.1 49.2 33.0 36.5 39.6 42.5 45.1 33.3 36.
- 33 - 69.7 62.5 21 18 0.61 0.55 44.9 41.4 73.9 75.6 23 24 0.61 0.55 43.7 40.4 72.0 73.8 17.8 18.0 COOLING PE-20MYC-EU CAPACITY TOTAL INPUT SHC AIR VOLUME 160 2,660 0.976 0.991 0.963 CMM L/S Factor for Various Air Flow 180 3,000 1.0 1.0 1.0 0.67 0.61 0.55 45.2 42.4 39.1 67.7 69.8 71.5 19.6 0.73 47.7 65.5 19.1 19.6 0.79 51.6 65.5 18.9 19.4 0.47 0.53 36.9 69.8 19.6 33.4 0.59 39.8 67.7 19.4 71.5 0.65 42.5 19.6 0.72 47.1 65.5 0.79 0.44 0.50 0.56 0.62 0.
- 34 - 33.3 60.0 55.6 57.8 17 15 16 33.0 64.2 57.8 60.0 19 16 17 37.3 32.3 69.2 69.2 62.2 64.2 20 21 18 19 36.0 32.5 71.6 73.8 64.2 69.2 22 23 19 20 42.7 39.3 35.8 71.6 73.8 76.0 69.2 69.2 22 23 24 20 21 48.9 46.0 42.8 71.6 73.8 76.0 22 23 24 51.6 56.0 45.6 69.2 21 50.8 52.0 39.2 69.2 21 43.5 69.2 20 45.2 48.5 39.3 64.2 19 42.6 62.2 18 46.1 49.2 36.5 62.2 18 39.6 60.0 17 42.5 45.1 36.4 39.2 57.8 55.
- 35 - 0.51 0.82 0.75 0.67 0.60 32.2 46.8 43.9 40.7 37.9 63.3 56.8 58.8 60.9 63.3 17.0 16.5 16.7 17.0 0.76 46.2 60.9 17.2 17.4 17.0 0.74 0.67 0.60 0.53 0.46 0.76 45.1 41.8 39.0 36.8 31.9 47.5 60.6 62.5 65.2 69.7 69.7 62.5 17 18 19 20 21 18 0.72 0.64 0.59 0.53 0.47 0.79 0.73 48.5 43.6 41.0 38.0 34.7 53.4 49.3 67.7 67.7 70.1 72.0 73.8 67.7 67.7 17.2 17.4 17.6 17.6 17.8 17.2 17.4 0.71 0.64 0.58 0.53 0.47 0.79 0.73 49.7 44.
OPERATION RANGE The range of working temperatures is as below. Make sure which unit you are using and confirm the range of application. Cooling Heating (PEH only) 15 40 30 20 Range for continuous operation 10 0 -5 -10 Range for continuous operation Use for low ambient Indoor temp.(˚CWB) cooling parts 10 15 20 24 25 30 Outdoor temp.(˚CWB) Outdoor temp.(˚CDB) 50 46 10 5 Range for continuous operation 0 -5 -10 -15 10 15 25 27 30 Indoor temp.
FAN PERFORMANCE PE-7MYC-EU PEH-7MYA-EU PEH-5MYA-EU Fan Performance Curve 50Hz (Pa) 450 Fan speed (rpm) Fan Performance Curve 50Hz (Pa) 450 Recommended Range 400 400 350 350 Fan speed (rpm) Recommended Range 1400 300 Total static pressure Total static pressure 1300 For connection operation line 250 1300 200 1200 For connection operation line 150 For Hi speed operation line 300 1200 250 For Low speed operation line 200 1100 1000 150 900 100 P al S 1100 rn Inte 100 r Inte 1
PE-15MYC-EU PEH-15MYA-EU Model Total static pressure (Pa) CMM L/S FAN SPEED rpm PULLEYSIZE (MOTOR SIDE) mm inch 200 Fan Performance Curve 50Hz (Pa) Recommended Range 1000 PULLEYSIZE 1300 Total static pressure 600 inch BELT SIZE inch MOTOR kw FAN SPEED rpm PULLEYSIZE mm (MOTOR SIDE) 300 Fan speed (rpm) 800 mm (FAN SIDE) inch PULLEYSIZE mm (FAN SIDE) inch BELT SIZE inch MOTOR kw FAN SPEED rpm PULLEYSIZE mm (MOTOR SIDE) 3.
Pulley outside dimensions are shown below: (Unit : mm) (1) Shape of belt groove e f w L0 K0 øP.C r3 K r1 a r2 r2 Shape of Nominal V-belt Dia. øP.C B Over 125 Under 160 Over 160 Under 200 Over 200 a (˚) W L0 36 16.07 12.5 5.5 38 16.29 11.0mm 16.5mm 40˚ B type (2) Shape of motor pulley boss (Unit : mm) C B A A +0.028 2.2, 3.7 28+ 0.007 31 5.5 38 +0.028 + 0.007 41 B C + 0.128 + 0.007 + 0.128 + 0.009 - 39 - K0 e f r1 r2 r3 V-belt thickness (Reference) 1~2 11 34 15.
SOUND DATA Indoor units Sound Levels MODEL PEH-5MYA-EU PE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PEH-8MYA-EU PE-10MYC-EU PEH-10MYA-EU PE-15MYC-EU PEH-15MYA-EU PE-20MYC-EU PEH-20MYA-EU PWL dB(A) OCTAVE BAND FREQ. Hz SPL dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 63 55 60.5 57.5 57.5 52.5 50.5 43 34.5 28.5 63 55 62 60 54 53 50 42.5 37 31.5 64 56 63 61 55 54 51 43.5 38 32.5 67 59 62 62.5 58.5 59.5 53 48 43.5 36 69 61 25 40 47 52 55 57.5 52 36.
OUTLINE DIMENSIONS PEH-5 POWER SUPPLY CABLE ENTRY ø27 104 (Bottom side) 135 66 CONTROL CABLE ENTRY ø27 105 782 130 130 34 130 130 130 HOLES:18-ø3.1 66 AIR INLET DUCT FLANGE 40 (Bottom side) 199 55 OPTIONAL PARTS CABLE ENTRY ø27 960 20 200 (Bottom side) 40 50 40 20 131 CONTROL BOX HOLES:14-ø3.1 55 130 130 130 55 HOLES:4-ø12 15 AIR OUTLET DUCT FLANGE 1095 650 50 40 920 15 33 40 210 250 98 500 14 428 382 210 REFRIGERANT PIPE ø19.05 (3/4) REFRIGERANT PIPE ø12.
PE(H)-10 POWER SUPPLY CABLE ENTRY 27 104 (Bottom side) 66 130 135 CONTROL CABLE ENTRY 1302 130 130 130 34 130 130 130 130 HOLES:26- 3.1 130 66 AIR INLET DUCT FLANGE 55 199 1480 20 20 HOLES:22- 3.1 45 130 45 HOLES:4- 12 40 98 220 250 REFRIGERANT PIPE 15.88 (5/8) 382 100 100 280 AIR OUTLET 25 130 130 1440 1000 220 REFRIGERANT PIPE 28.
PE(H)-20 70 1993 1648 193 44 49 1560=130X12 AIR INLET DUCT FLANGE 63 50 POWER SUPPLY CABLE ENTRY 27 (BOTTOM SIDE) 3.1 15 HOLES:38- 44 130 620 40 40 REFRIGERANT PIPE 15.88 (5/8) 190 55 CONTROL CABLE ENTRY 27 (BOTTOM SIDE) REFRIGERANT PIPE 28.6 OPTIONAL PARTS 25 (1-1/8) CABLE ENTRY 27 REFRIGERANT PIPE 15.88 (5/8) CONTROL BOX 25 1940 15 REFRIGERANT PIPE 28.6 (1-1/8) 130 44 AIR OUTLET DUCT FLANGE 21 1170=130X9 536 81 12 63 HOLES:4- 1212 21 142 HOLES:28- 3.
PUH-5 75 AIR INLET 400 AIR INLET 75 Holes :4-12X20 21 1040 550 AIR OUTLET 21 1000 131 126 CABLE ENTRY Holes : 2-ø15 21 Hole : ø15 400 75 18 PU(H)-7,8,10 (Upper blow) AIR INLET 275 275 13 75 42 84 75 REFRIGERANT PIPE ø19.05(3/4) 42 REFRIGERANT PIPE ø12.7 (1/2) 1175 SERVICE PANEL 200 CABLE ENTRY 25X40 1000 350 13 724 AIR INLET 700 AIR OUTLET Holes: 4-12X20 SERVICE PANEL 120 REFRIGERANT PIPE PU(H)- 7,8:ø25.4(1) PU(H)- 10:ø28.6(1-1/8) 980 875 REFRIGERANT PIPE ø15.
PUH-8,10 (Side blow) 400 75 AIR INLET Holes : 4-12X20 75 AIR INLET 21 1290 21 AIR OUTLET 550 1250 130 CABLE ENTRY Holes : 2-ø15 44 49 Hole : ø15 84 75 REFRIGERANT PIPE PUH-8:ø25.4(1) PUH-10:ø28.6(1-1/8) 400 75 56 42 75 42 REFRIGERANT PIPE ø15.88(5/8) 1175 SERVICE PANEL 275 275 PU-15 23 AIR INLET 23 1046 AIR INLET AIR INLET AIR OUTLET 998 998 HOLES: 4-Uø15 SERVICE PANEL 170 75 85 75 1070 REFRIGERANT PIPE ø25.4(1) 85 No.1 No.
PU-20 464 35 AIR INLET AIR INLET 17 No.2 2036 REFRIGERANT PIPE ø28.6(1-1/8) 998 17 REFRIGERANT PIPE ø15.88(5/8) SERVICE PANEL 1996 160 CONTROL CABLE ENTRY ø27 801 POWER SUPPLY CABLE ENTRY ø47 392 81 85 213 80 961 AIR OUTLET HOLES: 6-ø15 35 No.1 30 48 464 AIR INLET 756475 750 130 PUH-15,20 200 Holes : 4-12X20 27 830 2005 478.5 27 994 CONTROL BOX REFRIGERANT PIPE ø15.88 (5/8) 1042 1200 SERVICE PANEL REFRIGERANT PIPE PUH-15:ø25.4(1) PUH-20:ø28.6(1-1/8) No.1 68 No.
Note: In the case of installation are shown below, it is possible to use the unit by connecting the duct. However, the pressure loss must be 30Pa (3mmAg) or less. Duct work is local supply.
WIRING DIAGRAMS PE-7MYC-EU (STANDARD) Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 L3 CIRCUIT BREAKER PU-7MYC1-EU (FIELD SUPPLY) 100A N 52C RED RED 51C RED WHITE WHITE BLACK BLACK RED BLUE MC 51F2 1C4 RED 2 WHITE 3 BLACK WHITE F3(3.
PE-8,10MYC-EU (STANDARD) Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 RED RED L3 PU-8, 10MYC1-EU CIRCUIT BREAKER (FIELD SUPPLY) 100A N 52C 51C RED WHITE WHITE BLACK BLACK RED BLUE MC 51F2 1C4 RED 2 WHITE 3 BLACK WHITE F3(3.
PE-15MYC-EU (STANDARD) TB1 OUTDOOR UNIT L2 51C1 52C1 L1 Power supply, 3 Phase 380~415 Volt, 50Hertz RED L3 WHITE N BLACK BLUE RED RED WHITE WHITE BLACK BLACK CIRCUIT BREAKER (FIELD SUPPLY) PU-15MYC1-EU ---100A RED WHITE 51C2 52C2 PE RED RED WHITE WHITE BLACK BLACK MC1 52F2 BLACK 51F2 1 C1 RED 2 WHITE 3 BLACK MC2 F3 (3.
PE-20MYC-EU (STANDARD) TB1 OUTDOOR UNIT Power supply, 3 Phase 380~415 Volt, 50Hertz L1 RED L3 WHITE N BLACK BLUE 51C1 52C1 RED L2 51C2 52C2 RED PE RED WHITE WHITE BLACK BLACK RED WHITE F3 (3.
PE-7MYC-EU (SPECIAL ORDER : ANTI SHORT CYCLE TIMER) Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L3 CIRCUIT BREAKER PU-7MYC1-EU (FIELD SUPPLY) 100A N 52C RED RED L2 51C RED WHITE WHITE BLACK BLACK F3(3.
PE-8,10MYC-EU (SPECIAL ORDER : ANTI SHORT CYCLE TIMER) Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 L3 PU-8, 10MYC1-EU CIRCUIT BREAKER (FIELD SUPPLY) 100A N 52C RED RED BLUE 51C RED WHITE WHITE BLACK BLACK MC 51F2 RED 1C4 RED 2 WHITE 3 BLACK WHITE F3(3.
PE-15MYC-EU (SPECIAL ORDER : ANTI SHORT CYCLE TIMER) OUTDOOR UNIT TB1 L1 Power supply, 3 Phase 380~415 Volt, 50Hertz L2 L3 N WHITE RED WHITE WHITE BLACK BLACK MC1 BLACK CIRCUIT BREAKER (FIELD SUPPLY) PU-15MYC1-EU ··· 100A 51C2 52C2 RED RED WHITE WHITE BLACK BLACK 51F2 52F2 RED BLUE PE 51C1 52C1 RED RED 1C1 RED WHITE 2 WHITE BLACK 3 BLACK MF2 MC2 F3(3.
PE-20MYC-EU (SPECIAL ORDER : ANTI SHORT CYCLE TIMER) OUTDOOR UNIT TB1 L1 Power supply, 3 Phase 380~415 Volt, 50Hertz N BLACK BLACK BLACK BLUE WHITE BLACK BLACK 52F2 RED WHITE BLACK 49C1 51 F2 52 C2 52 C2 CZ2-1 CZ2-2 MC2 51F2 1C1 RED 2 WHITE MF2 3 BLACK 51F3 1C2 RED 2 WHITE MF3 3 BLACK TM (3min) 63H2 TM (3min) 52 C2 52 C1 51C2 51C1 CH1 CH2 52 C1 51 F3 63H1 RED WHITE BLACK 49C2 MC1 RED WHITE F3 (3.
PE-7MYC-EU (SPECIAL ORDER : LOW AMBIENT COOLING) Power supply, 3Phase 380 415Volt,50Hertz TB1 L1 L3 PU-7MYC1-EU CIRCUIT BREAKER (FIELD SUPPLY) 100A 52C RED RED L2 WHITE BLACK BLACK F3(3.
PE-8,10MYC-EU (SPECIAL ORDER : LOW AMBIENT COOLING) Power Supply, 3Phase 380 415Volt, 50Hertz TB1 L1 BLUE 51C RED WHITE WHITE BLACK BLACK L3 CIRCUIT BREAKER PU-8,10MYC1-EU (FIELD SUPPLY)100A N 52C RED RED L2 RED MC 51F2 1C4 RED 2 WHITE 3 BLACK WHITE F3(3.
PE-15MYC-EU (SPECIAL ORDER : LOW AMBIENT COOLING) OUTDOOR UNIT TB1 L1 Power supply, 3 Phase 380~415 Volt, 50Hertz WHITE MC1 BLACK BLACK BLACK N 51F2 BLUE PE RED WHITE WHITE L3 51C1 52C1 RED RED L2 CIRCUIT BREAKER (FIELD SUPPLY) PU-15MYC1-EU ··· 100A 51C2 52C2 RED RED WHITE WHITE BLACK BLACK RED 1 C1 RED WHITE 2 WHITE BLACK 3 BLACK RED MF2 C2 2 WHITE 3 BLACK 1 52F3 MC2 52F2 F3(3.
PE-20MYC-EU (SPECIAL ORDER : LOW AMBIENT COOLING) OUTDOOR UNIT Power supply, 3 Phase 380~415 Volt, 50Hertz TB1 L1 51C2 52C2 RED BLUE PE MC1 BLACK BLACK BLACK N 51F2 F3(3.
PEH-5MYA-EU (STANDARD) Power Supply, 3Phase 380~415Volt, 50Hertz TB1 L1 L2 RED RED 51C 51F2 RED PROTECTOR 1C4 RED 2 WHITE 3 BLACK X1 WHITE F3(3.
PEH-7MYA-EU (STANDARD) Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 L3 CIRCUIT BREAKER PUH-7MYC1-EU (FIELD SUPPLY) 100A N 52C RED RED 51C RED WHITE WHITE BLACK BLACK MC 51F2 RED BLUE 1C4 RED 2 WHITE 3 BLACK X1 WHITE F3(3.
PEH-8,10MYA-EU (STANDARD) Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 RED RED L3 CIRCUIT BREAKER (FIELD SUPPLY) N BLUE 52C 51C RED WHITE WHITE BLACK BLACK MC 51F2 RED 1C4 RED 2 WHITE 3 BLACK X1 WHITE F3(3.
PEH-15,20MYA-EU (STANDARD) L1 Power supply, 3 Phase 380~415 Volt, 50Hertz L2 RED L3 WHITE N BLACK BLUE RED RED WHITE WHITE BLACK BLACK PE CIRCUIT BREAKER (FIELD SUPPLY) PUH-15MYC1-EU---100A PUH-20MYC1-EU---125A RED WHITE RED BLACK BLACK RED RED WHITE WHITE BLACK BLACK F3 (3.
PEH-5MYA-EU SPECIAL WIRING : ANTI SHORT CYCLE TIMER., PROTECT FOR COOL AIR BLOW.
PEH-7MYA-EU SPECIAL WIRING : ANTI SHORT CYCLE TIMER., PROTECT FOR COOL AIR BLOW. ( Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 L3 CIRCUIT BREAKER PUH-7MYC1-EU (FIELD SUPPLY) 100A 52C RED RED WHITE BLACK BLACK F3(3.
PEH-8,10MYA-EU SPECIAL WIRING : ANTI SHORT CYCLE TIMER., PROTECT FOR COOL AIR BLOW. ( Power supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 L3 PUH-8, 10MYE-EU CIRCUIT BREAKER (FIELD SUPPLY) 100A N PUH-8, 10MYC1-EU 52C RED RED BLUE 51C RED WHITE WHITE BLACK BLACK MC 51F2 RED 1C4 RED 2 WHITE 3 BLACK X1 WHITE F3(3.
PEH-15,20MYA-EU (SPECIAL WIRING : ANTI SHORT CYCLE TIMER) OUTDOOR UNIT Power supply, 3 Phase 380~415 Volt, 50Hertz TB1 L1 WHITE L3 52C1 RED RED L2 WHITE BLACK BLACK BLACK N 51C1 RED WHITE MC1 51F2 X1 RED BLUE PE CIRCUIT BREAKER (FIELD SUPPLY) PUH-15MYC1-EU ··· 100A PUH-20MYC1-EU ··· 125A BLACK BLACK 51 F3 51C1 52 C1 52 C2 51C2 CZ2-1 30 CZ2 CR2 52 C2 52 C1 TM 21 S4-1 X4 C6 1 C7 26 D4 1 C4 1 C5 1 C4 3 C5 3 T1 2 30 CZ2 30 CZ1 3 26 D2 26 D1 X3 CR3 CZ2-2 C7
PEH-7MYA-EU (SPECIAL ORDER : LOW AMBIENT COOLING) Power supply, 3Phase 380 415Volt,50Hertz TB1 L1 L2 L3 PUH-7MYC1-EU CIRCUIT BREAKER (FIELD SUPPLY) 100A N 51C RED WHITE WHITE BLACK BLACK F3(3.
PEH-8,10MYA-EU (SPECIAL ORDER : LOW AMBIENT COOLING) Power Supply, 3Phase 380 415Volt, 50Hertz TB1 L1 L2 BLUE 51C RED WHITE WHITE BLACK BLACK L3 CIRCUIT BREAKER PUH-8,10MYC1-EU (FIELD SUPPLY)100A N PUH-8,10MYE-EU 52C RED RED MC 51F2 RED X1 1C4 RED 2 WHITE 3 BLACK WHITE F3(3.15A) BLACK PE HZ2 49C 52F3 WHITE C8 2 MF2 BLACK RED 3 1 52F2 HZ2 51F2 1 52C C4 4 49F2 X3 23C 3 X1 X2 C4 5 52 F3 T1 52F2 52F3 52F4 30 CZ 15 C6 1 26 D1 X3 CH MF3 is only PUH-8,10MYC1-EU.
PEH-15,20MYA-EU (SPECIAL ORDER : LOW AMBIENT COOLING) OUTDOOR UNIT TB1 L1 Power supply, 3 Phase 380~415 Volt, 50Hertz 52C1 RED RED L2 WHITE L3 WHITE BLACK BLACK MC1 BLACK N 51F2 BLUE PE 51C1 RED WHITE L1-1 RED WHITE L2-1 WHITE BLACK CIRCUIT BREAKER (FIELD SUPPLY) PUH-15MYC1-EU ··· 100A PUH-20MYC1-EU ··· 125A 52C2 RED CH2 T1 X2 X5 X2 X3 51 F2 51 F3 63H1 63H2 51C1 H 51C2 FZ2 CZ2-1 CR2 30 CZ2 52 C1 30 CZ1 FZ3 52 C2 52 F4 30 CZ2 FZ 6 52 F5 FZ5 FZ 7 C6 1 C4
ELECTRICAL OPERATION FLOW CHARTS PE-7,8,10MYC-EU START START POWER ON POWER ON CH ON CH ON 30FZ,30CZ ON (SELF HOLD) 30FZ,30CZ ON (SELF HOLD) SW1 ON? NO SW2 ON? NO YES YES FZ ON FZ ON 52F ON MF1 OPERATE 52F ON MF1 OPERATE 23WA ON? NO SW1 COOL? NO HZ1,2 ON 21S4 YES YES CZ1,2 PEH-5MYA-EU, PEH-7,8,10MYA-EU ON 23WA ON? NO NO YES 30CZ 52C MC MF1 MF2,3 CH CZ1 OFF OFF STOP Note STOP ON ON YES CZ1,2 52C ON MC OPERATE MF2, 3 OPERATE OFF SAFETY DEVICE OFF? 23WA ON? YES 52C ON
PE-15MYC-EU PE-20MYC-EU START START POWER ON POWER ON CH1,2 ON CH1,2 ON 30FZ,30CZ1,2 ON (SELF HOLD) 30FZ,30CZ1,2 ON (SELF HOLD) NO SW1 ON? YES YES FZ ON FZ ON 52F1 ON MF1 OPERATE 52F1 ON MF1 OPERATE NO 23WA ON? NO 23WA ON? YES YES CZ1-1,CZ2-1 ON CZ1-1,CZ2-1 ON 52C1 ON MC1 OPERATE MF2 OPERATE 52C1 ON MC1 OPERATE MF2 OPERATE CH 1 OFF CH 1 CZ1-2,CZ2-2 ON TIMER 2 ON NO PASS THE 3 MIN? 52C2 ON MC2 OPERATE CH2 OFF CH2 No.
PEH-15,20MYA-EU START POWER ON CH1,2 ON 30FZ,30CZ1,2 ON (SELF HOLD) NO SW2 ON? YES FZ ON 52F1 ON MF1 OPERATE NO SW1 COOL? HZ1,2 ON 21S4-1,2 ON T1,T2 ON YES NO 23WA ON? YES YES CZ1-1,CZ2-1 ON CZ1-1,CZ2-1 ON 52C1 MC1 MF2 52C1 MC1 MF2 CH 1 ON OPERATE OPERATE OFF CH 1 CZ1-2,CZ2-2 ON TIMER 2 ON NO 52C2 MC2 MF3 OFF CH 2 No.2 SAFETY DEVICE OFF? YES 30CZ1 OFF YES 30CZ2 OFF CH1 NO YES ON OPERATE OPERATE No.
REFRIGERANT SCHEMATICS PE-7,8,10,15,20MYC-EU INDOOR PE Evaporator OUTDOOR PU Condenser High pressure switch Service port Check joint Strainer Ball valve Interconnecting refrigerant piping (by others) COOL Muffler Accumulator Check joint Compressor Interconnecting refrigerant piping (by others) Capillary Tube Strainer Note:PE-15,20MYC-EU is comprised of two refrigerant cycles.
SAFETY & CONTROL DEVICES PE-7,8,10MYC-EU PE-15,20MYC-EU NO. PE-7MYC-EU PU-7MYC1-EU PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PU-10MYC1-EU COMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.0A 31.0A COMPRESSOR INTERNAL THERMOSTAT 49C HIGH PRESSURE SWITCH 63H INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 INDOOR FAN MOTOR INTERNAL THERMOSTAT - OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2 ITEM OUTDOOR FAN MOTOR INTERNAL THERMOSTAT FUSE 105 ± 5 ˚C OFF 2.94MPa OFF 5.0A 3.5A 150 ˚ C OFF 2.
PEH-7,8,10MYA-EU PEH-15,20MYA-EU NO. PEH-5MYA-EU PUH-5MYE-EU PEH-7MYA-EU PUH-7MYC1-EU PEH-8MYA-EU PUH-8MYC1-EU PUH-8MYE-EU COMPRESSOR OVER CURRENT RELAY 51C 15.0A 19.0A 22.0A COMPRESSOR INTERNAL THERMOSTAT 49C 110 ± 5˚C OFF 61 ± 9˚C ON HIGH PRESSURE SWITCH 63H ITEM 105 ± 5˚C OFF 83 ± 11˚C ON 2.
SPECIAL ORDER Cooling only Model - Service ref. - PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU Model PEH-5MYA PEH-7MYA PEH-8MYA PEH-10MYA PEH-15MYA PEH-20MYA PE-7MYC PE-8MYC PE-10MYC PE-15MYC PE-20MYC Description Heat pump Service ref.
PHYSICAL DATA PE-7,8,1015,20MYC-EU [ PRODUCT] Product type Product number : PACKAGE AIR COOLED HEATPUMP UNITS Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Basic temperature condition cooling Basic temperature condition cooling PE-7MYC-EU PU-7MYC1-EU 17.9 14.3 7.2 kW kW kW Indoor Outdoor PE SERIES PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PU-8MYC1-EU PU-10MYC1-EU PU-15MYC1-EU 44.0 22.0 28.8 17.6 23.0 35.2 7.8 10.1 16.
Product number Indoor unit Outdoor unit PE-7MYC-EU PU-7MYC1-EU PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PE-15MYC-EU PU-10MYC1-EU PU-15MYC1-EU PE-20MYC-EU PU-20MYC1-EU [INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive Fan motor output Fan motor run current Air quantity External static pressure Supply air dimensions(hxw) Return air dimensions(hxw) 2 mm mm kW A L/s Pa mm mm 250 380 245 270 374 275 Direct drive Belt drive 2.2 3.7 0.21 0.70 1.00 3.5 4.8 3.2 1.2 2.
Product number Indoor unit Outdoor unit PE-7MYC-EU PU-7MYC1-EU PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PE-15MYC-EU PU-10MYC1-EU PU-15MYC1-EU PE-20MYC-EU PU-20MYC1-EU [ENCLOSURE AND FRAME] Dimension Dimension Indoor unit Outdoor unit External finish (indoor unit) External finish (outdoor unit) Panel thickness Condense drain size Weight Indoor unit Weight Outdoor unit Sound pressure level (indoor unit) Sound pressure level (outdoor unit) Sound power level (indoor unit) Sound power level (outdoor unit) h
PEH-5,7,8MYA-EU [ PRODUCT] Product type Product number : PACKAGE AIR COOLED HEATPUMP UNITS Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Heating capacity (AS1861) Heating power consumption Basic temperature condition cooling Basic temperature condition cooling Basic temperature condition heating Basic temperature condition heating PEH-5MYA-EU PUH-5MYE-EU 14.4 11.5 6.0 14.4 4.
Product number Indoor unit Outdoor unit PEH-5MYA-EU PUH-5MYE-EU PEH-7MYA-EU PUH-7MYC1-EU PEH-8MYA-EU PUH-8MYE-EU PUH-8MYC1-EU [INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive Fan motor output Fan motor run current Nominal air quantity External static pressure Supply air dimensions(hxw) Return air dimensions(hxw) 1 mm mm 275 kW A L/s Pa mm mm 0.45 1.1/1.0 700 100 342X781 248X498 sq.m 0.3 2 250 245 Direct drive 0.21 3.2 1000 275 0.70 1.
Product number Indoor unit Outdoor unit PEH-5MYA-EU PUH-5MYE-EU PEH-7MYA-EU PUH-7MYC1-EU PE-8MYA-EU PUH-8MYE-EU PUH-8MYC1-EU [ENCLOSURE AND FRAME] Dimension Indoor unit Dimension Outdoor unit External finish (indoor unit) External finish (outdoor unit) Panel thickness Condense drain size Weight Indoor unit Weight Outdoor unit Sound pressure level (indoor unit) Sound pressure level (outdoor unit) Sound power level (indoor unit) Sound power level (outdoor unit) height width depth height width depth
PEH-10,15,20MYA-EU [ PRODUCT] Product type Product number : PACKAGE AIR COOLED HEATPUMP UNITS PEH SERIES PEH-15MYA-EU PEH-10MYA-EU PUH-15MYC1-EU PUH-10MYC1-EU PUH-10MYE-EU 28.8 44.0 23.0 35.2 10.1 16.8 28.8 44.0 8.3 14.
Product number Indoor unit Outdoor unit PEH-15MYA-EU PUH-15MYC1-EU PEH-10MYA-EU PUH-10MYC1-EU PUH-10MYE-EU PEH-20MYA-EU PUH-20MYC1-EU [INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive Fan motor output Fan motor run current Nominal air quantity External static pressure Supply air dimensions(hxw) Return air dimensions(hxw) 2 mm mm kW A L/s Pa mm mm 250 275 Direct drive 1.00 1.00 1.8 2.0 1500 1500 125 341X1302 342X1318 248X998 sq.m 1 0.
Product number Indoor unit Outdoor unit PEH-10MYA-EU PUH-10MYC1-EU PUH-10MYE-EU PEH-15MYA-EU PUH-15MYC1-EU 428 1615 650 1690 PEH-20MYA-EU PUH-20MYC1-EU [ENCLOSURE AND FRAME] Dimension Dimension Indoor unit Outdoor unit External finish (indoor unit) External finish (outdoor unit) Panel thickness Condense drain size Weight Indoor unit Weight Outdoor unit Sound pressure level (indoor unit) Sound pressure level (outdoor unit) Sound power level (indoor unit) Sound power level (outdoor unit) height wi
INSTALLATION 1. Space required around unit. Indoor unit Dimension of the unit and space necessary for sevicing.
PU(H)-7,8, 10 (Upper blow) (1) At a single installation 300 over The obstacle is on the outlet side. (Fig 1) The obstacle is in three directions. (Fig 2,3) The obstacle is in four directions. (Fig 4) ceiling 1200 over The right and left side and the back and forth side must be opened. 300 over 500 over However, the outlet side must be opened. Service Panel Fig 2 Fig 1 300 over A If this side is service panel, you need 500 over. If this side is inlet, you need 300 over.
PU-15 (1) At a single installation The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2) 300 over ceiling 1500 over 500 over The right and left side and the back and forth side must be opened. However, the outlet side must be opened. 300 over 300 over Service Panel Fig 1 Fig 2 300over (2) Relation of unit when many set up unit. (Fig 3,4) 500over Service-panel 500 over 300 over If this side is service panel, you need 500 over.
PUH-15, 20 (1) At a single installation The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2) The obstacle is in three directions. (Fig 3,4) ceiling 1500 over The right and left side and the back and forth side must be opened. However, outlet side 500 over must be opened. And the obstacle in 300 over two directions must be lower than the unit. 300 over Service Panel Fig 2 Fig 1 However, the outlet side must be opened.
3. Installation of the unit. Indoor unit Please carry the packed until parallelly to installed place. Please install the unit before construction of the ceiling -lined. PEH-5 PE(H)- 7, 8, 10 100 over 100 over U washer Nut 30 30 Washer Nut 100 over PE(H)- 15, 20 Nut (M10) Nut (M10) Washer 30 Washer Nut (M10) Ceiling Nut (M10) Outdoor unit Fix unit tightly with bolts as shown below so that unit will be securely fixed in place use concrete or angle foundation of unit.
Duct construction. Provide canvas flexible ducting between unit when connect to the duct-work. The duct unit must use a nonflammable material. Provide sufficient insulation for prevent dewdrop. Duct earth Duct earth Canvas Duct Canvas Duct Duct Duct Drain pan Inlet Outlet Duct-work length 850mm or more Lifting method. When the unit is to be lifted and moved, attach ropes to the suspension plates(3 p.c.s) provided on the top of the unit.
Piping connection Warning. Please follow the following procedures, during the piping connection work is carried out. If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve. It might cause the injury. In case of Brazing type 1. Open the ball valve cap before removing the by-pass tube. Then, turn the knob of the ball valve from ’close’ to ’open’ position. 2.
In case of Flare, Flange type 1. PROCEDURE TO CONNECT THE EXTENSION PIPE. Proceed with the connection as follows: (1) Open the ball valve cap before cutting the by-pass tube.(Fig.1) (2) Check the ball valve section is completely closed.(Fig.2) Fig. 1 (3) Cut two parts of the by-pass tube.(Fig.4) Caution There will be small amount of refrigerant gushed out of the by-pass tube at the moment. Valve knob Valve knob (4) Remove the connection pipe assy.(Fig.5) Throw away the packing.
4. Refrigerant piping. Extension piping and installation parts are field supply. Perform the work only after carefully reading the appropriate instructions. A Install the unit where the refrigerant piping is shortest, When the outdoor unit is lower. the difference between the indoor unit and outdoor unit is smallest. As pipes purchased in the market may contain dust, below them off with dry inlet gas. Take care not to allow dust and water content to enter the piping during pipe processing or installing.
Airtight test Airtight test should be made by pressurizing nitrogen gas to 3Mpa. For the test method, refer to the following figure. (Make a test with the valve closed. Be also sure to pressurize both liquid and gas pipe.) The test result can be judged good if the pressure has not been reduced after leaving for about one day after completion of nitrogen pressurization. a. b. c. d. e. f. g. h. i. j.
5. Drain piping •Incline the drain piping to the outside (drain side) as shown in the figure below. •The outlet of the indoor unit drain pipe is Rc1. •After completion of piping, confirm that drainage is good and that there are no leaks. Indoor unit drain piping Install thermal insulation to prevent dew The drain piping should have a drain trap. Slope 20mm/m C Drain piping A Drain pan B A >= 70mm B >= 2xC >= 70mm C => 35mm Drain trap The drain pipe should extend below this level.
6. Electric wiring Construct the earth connection. All electrical work must be carried out by a suitable qualified electrical trades-person and in accordance with local supply authority requirements and associated regulators. The outdoor unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse. Fix power source wiring to control box by using buffer bushing for tensible force (PG connection or the like).
Control module of outdoor unit PU-15 Control module of outdoor unit PU(H)-7, 8, 10 Upper blow PUH only Terminal block for power supply wires F3 T1 F3 52C & 51C 2 F3 3.
Method for connecting electric wire Please do the wiring after consulting the electric power company of jurisdiction beforehand in the instruction. (1) The entire wiring diagram of unit. a a b b PE PE j d c j In case of PE-7,8,10 In case of PE-15,20 PEH-5, 7, 8, 10 a. Power supply b. Main switch/fuse (field supply) c. Power supply wiring for outdoor unit d. Power supply wiring for indoor unit e. Outdoor unit f. Indoor unit g. Connection wiring for indoor / outdoor units (polarity) h.
(3) Indoor unit and remote controller.(OPTION:PAC-204RC) Connect the wires on the basis of the following wiring diagram. PE(H)-15,20 TB4 2 TB3 2 CZ 1-1 FZ CZ1 1 3 CZ 1-2 FAN HI COMP2 AC24V AC 220 240V 3 24VAC(N) FAN HI AC24V Tr COMP1 AC 220 240V 24VAC(N) Tr TB3 F2 (3.15A) 24VAC(L) F2 (3.
7. The putting condition of the belt. (PE(H)-15,20 only) 1.Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below. 2.Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1 below at the proper flexion. (A=4.5mm) 3.Adjust the suitable tension after the belt sit properly across the pulley (after more 24-28 hours working). When the new belt is used, adjust the suitable tension about the 1.
INSTRUCTIONS FOR USE 1.Check points for operation. Check the following points before you operate your air conditioner. (1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet. Indoor unit Inlet grille Outlet grille Ceiling Ceiling Obstacle blocking air inlet Obstacle blocking air outlet Outdoor unit Obstacle blocking air inlet. (2)Make sure the air conditioner is properly grounded by checking the ground terminal.
2.Caution for use. Keep the following points in mind to safeguard against failures and breakdowns. (1) This air conditioner does not restart within 3min. after shut down. (These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do not turn the power switch to OFF, but turn the operation switch to OFF.) 3 Minutes Shutdown Operation (2) If the air conditioner is shut down by a power failure, set the operation switch to OFF.
3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods, the outdoor heat exchanger will become dirty, impairing its function and reducing air conditioners performance. Consult your equipment supplier or air conditioning contractor on how to clean the heat exchanger. Heat exchanger 4.When beginning to use air conditioner again. Please turn on the power supply after confirming an following check is done and abnormality is not found.
6-2 Place for installation. Please do not use the unit in the following places. (1) Place where a lot of oil (The machine oil is contained), moistures, and dust exist. (2) Place where a lot of salinities such as beach districts exists. (3) Place where sulfur gas, volatile gas, and corroded gas are filled. (4) Place where acid solution is frequently used. (5) Place where special spray is frequently used. (6) Hot spring zone. (7) Never machine (high cycle welding machine etc.) generating highcycle.
7.Trouble shooting Before you ask for repair service, check the following points: Cause State of Machine It does not run. Air flows out but it does not cool or heat enough. Cool or warm air does not come out. Troubleshooting Power failure. Press the [ON/OFF] button after power restoration. The power supply is turned OFF. Turn the power supply ON. The fuse in the power supply is gone. Replace fuse. The earth leakage breaker is gone. Put in the earth leakage breaker.
HOW TO OPERATE (OPTION PAC-204RC) Display section C G B H D F A A B C E D E F G H [Current/start/ending time] Display Operation mode Displays the status of operation. [Checking] Display This displays indication when some abnormality occurs in the unit. [Set temperature] Display Displays the set temperature. [Operation] Lamp Lights up during operation, goes off during stop. [Room temperature] Display Displays the temperature of the air sucked in during operation.
1-2 Selecting operation When selecting operation A Press the [MODE] button Consecutive press of the [MODE] button switches the operation over to "FAN", "COOL", "HEAT" and "AUTO". For the contents of operation,check the display. For fan 1 Press the [MODE] button and bring up the "FAN" display. * The fan operation functions to circulate the air in the room. * The temperature of the room cannot be set by fan operation. Caution: A Never expose your body directly to cool air for a long time.
1-4 Time setting Clock key A 1 Press the key one time will activate set clock mode. Press the key again will disable set clock mode. 2 4 Under set clock mode, the real time clock and present day setting can be changed by pressing Day key, Hour key or Minute key. B 2 3 7-Days timer key 5 1 1 There are two keys for timer. One is ON Timer, another is Off Timer. Press the key one time will activate set timer mode. Press the key again will disable set timer mode.
1-6.Trouble shooting Before you ask for repair service, check the following points: State of Machine It does not run Air flows out but it does not cool enough or heat enough. Cool air or warm air does not come out. The liquid crystal display shows that it is in the state of operation. The liquid crystal display shows that it is in operation. Troubleshooting Cause Remote Controller "ON-OFF "display is not lit up No display appears even when the [ON/ OFF] button is pressed.
SPECIFICATION GUIDELINES Air to air reverse cycle split air conditioning system. The systems shall operate at out door ambient temperatures as high as . The system shall have a total cooling capacity of kW or greater with an indoor air quantity of L/s WB entering indoor coil temperature with a at DB and temperature entering the outdoor coil.