Service manual

30
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start
operation.
· To operate the main unit, refer to the 11-1-2. and set the requet code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts.(2 units operation)
· When room temperature falls below set point -4:, standby unit stops.(1 unit operation)
System constraint
· This function is available only in rota-
tion operation and back-up function in
cooling mode.
SPECIAL FUNCTION
11
[2nd stage cut-in function]··· Request code number "322~324"
Start operation Sub unit start operation
Room temp. Set point
Sub unit stop
Run
Stop StopRun
Main
unit
IC-1
Sub
unit
IC-2
Room temp. < Set point -4
11-1. ROTATION FUNCTION(AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION)
For PKA-RP50FAL2#1,PKA-RP60/71/100FAL#1
11-1-1. Operation
(1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address.(Outdoor Dip switch setting)
Refrigerant address"00" Main unit
Refrigerant address"01" Sub unit
· When error occurrs to one unit, another unit will start operation.(Back-up function)
• System constraint
· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups.(Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line(TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit.(Dip switch on the outdoor unit···Refrigerant address 00/01)
Operation pattern
OC-1
OC-2
IC-1
IC-2
3(2)
3(2)
2
RC
2
Main
unit
Sub
unit
Refrigerant address
"01"
Refrigerant address
"00"
Fig. 1
[Back-up function only]··· Request code number "312"

[Rotation function] & [Back-up function]··· Request code number "313~318"
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Error occurs on main unit.
Start operation
Run
Abnormal condition
Stop
Run
Main
unit
IC-1
Sub
unit
IC-2
Error occurs on main unit.
Start operation
1~28 days 1~28 days
Run
Abnormal condition
Stop
Stop
Run
Run
Stop Run
Main
unit
IC-1
Sub
unit
IC-2
Main Sub
Main Sub
Sub Main
Main Sub
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
Downloaded from AC-Manual.com Manuals