Specifications

12
Model Name
208/230V PURY-P72THMU-A (-BS) PURY-P96THMU-A (-BS) PURY-P120THMU-A (-BS)
460V PURY-P72YHMU-A (-BS) PURY-P96YHMU-A (-BS) PURY-P120YHMU-A (-BS)
Power Source 208/230V, 3-phase, 60Hz / 460V, 3-Phase, 60Hz
Capacity *1
Cooling
Btu/h 72,000 96,000 120,000
kW 5.55 8.35 / 8.27 10.59
A 15.4 / 7.7 23.2 / 11.6 29.5 / 14.7
Heating
Btu/h 80,000 108,000 120,000
kW 6.04 8.66 10.16
A 16.8 / 8.4 24.1 / 12.0 28.3 / 14.1
Fan
Type x Quantity Propeller Fan x 1
Airflow Rate CFM 6,550 7,750 7,950
Direct-drive
INVERTER
Motor Output
kW 0.92
External Static Pressure Selectable; 0, 0.12 or 0.24 W.G.; factory set to 0 W.G.
Compressor
Type INVERTER-driven Scroll Hermetic x1
Operating Range 19% to 100% 17% to 100%
Motor Output kW
4.4 7.0 8.1
Crankcase Heater W
51 57
Lubricant MEL32
Refrigerant Type R410A
External Finish Pre-coated Galvanized-steel Sheets (Plus Powder-coating for -BS types) <Munsell No. 5Y 8/1 or Similar>
Dimensions
Height In. 65
Width In. 36-1/4 48-1/16
Depth In. 29-15/16
Net Weight
Pounds
519 / 552 585 / 618
Sound Pressure Level (As
Measured in an Anechoic Room)
dB(A)
58 60
Protection Devices
High Pressure Protection High-pressure Sensor, High-pressure Switch
Compressor/Fan
Overheat Protection, Thermal Switch
Inverter Overheat and Overcurrent Protection
Refrigerant Pipe
Dimensions
Low Pressure
(Brazed)
In.
3/4 7/8 1-1/8
High Pressure
(Brazed)
In.
5/8 3/4
Indoor Unit
Total Capacity 50 to 150% of Outdoor Unit Capacity
Quantity P06-P96/1-18 P06-P96/1-24 P06-P96/1-30
Operating
Temperature
Range
Cooling Outdoor: 23º F DB to 109º F DB
Heating
Outdoor: -4º F WB to +60º F WB
Note: Rating Conditions: *1 Cooling: Indoor: 80˚F (27˚C) DB / 67˚F (19˚C) WB; Outdoor: 95˚F (35˚C) DB.
Heating: Indoor: 70˚F (21˚C) DB; Outdoor: 47˚F (8˚C) DB / 43˚F (6˚C) WB.
-BS indicates Seacoast Protection option.
LIMITED WARRANTY | Five-year warranty on compressor. One-year warranty on parts.
Specifications Are Subject to Change.
R2-SERIES SPECIFICATIONS