Installation manual

[ VIII Test Run Mode ]
- 185 -
HWE09130 GB
Operation
Outdoor unit model
PURY-P264TSJMU-A
PURY-P144TJMU-A PURY-P120TJMU-A
Model name of BC controller CMB-P1016NU-HA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80 °F/67 °F]
Outdoor 35°C/ [95 °F/]
Indoor unit
No. of connected units
Unit
8
No. of units in operation 8
Model - 24/24/36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 75 [229-5/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
44.6 [98]
Outdoor
unit
Electric current A 64.4
Voltage V 230
Compressor frequency Hz 87 75
LEV open-
ing
Indoor unit
Pulse
200/200/275/275/275/275/275/275
BC controller (1/2/3) 2000/2000/290
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.87/0.95
[416/138]
2.82/0.95
[409/138]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.75/2.75
[399/399]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180] 82 [180]
Heat exchanger outlet
(TH3)
43 [109] 43 [109]
Accumulator inlet 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50]
Compressor inlet 22 [72] 22 [72]
Compressor shell bottom 44 [111] 44 [111]
Indoor unit
LEV inlet 22 [72]
Heat exchanger inlet 13 [55]