June 2008 Air to Water (ATW) Heat pump, Interface (I/F) and Flow temp. controller (FTC) Technical manual CONTENTS 1. What is ATW heat pump?.......................................................2 2. Heat pump unit_General information ...................................4 3. System design ......................................................................15 4. Interface (I/F) ........................................................................23 5. Flow temp. controller (FTC) ........................
1 What is ATW heat pump? 1-1. Compare with conventional fossil fuel boiler • Heat pumps produce water at 30°C – 60°C • Ideal for underfloor heating • Average underfloor heating circuit 35°C • Fossil fuel boilers heat water to 80°C • Flow temp in rads design temp approx 70°C • Heat pumps can still be used with radiators • Larger surface area to emit heat from lower temp water 1-2. Points to notice 1-2-1.
Hex for PUHZ-W85VHA (ACH30-40Plates) Flow rate (L/min) Pressure Loss (kPa) 5 1.0 Secondary (Water - side) 10 15 3.6 7.5 20 12.5 25 18.8 30 26.2 Pressure loss (kPa) 30.0 25.0 20.0 15.0 10.0 5.0 0.0 5 10 15 20 25 30 Flow rate (L/min) Hex for PUHZ-W112, 140VHA / YHA (ACH50-50Plates) Flow rate (L/min) Pressure Loss (kPa) 15 1.3 Secondary (Water - side) 30 45 4.9 10.9 60 19.3 75 29.9 90 42.8 Pressure loss (kPa) 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 5.0 0.
2 Heat pump unit_General information 2-1. Line-up 2-1-1.
2-1-3. Reference manual Outdoor unit PUHZ-W50VHA PUHZ-W85VHA PUHZ-HW112YHA PUHZ-HW140VHA PUHZ-HW140YHA PUHZ-RP60VHA3#1 PUHZ-RP71VHA3#1 PUHZ-RP100VHA3#1 PUHZ-RP125VHA2#2 PUHZ-RP140VHA2#2 PUHZ-RP100YHA3#1 PUHZ-RP125YHA2#2 PUHZ-RP140YHA2#2 PUHZ-HRP71VHA(2) PUHZ-HRP100VHA(2) PUHZ-HRP100YHA(2) PUHZ-HRP125YHA(2) Service manual Parts catalog I/F FTC OCH439 OCB439 OC374 OC374 OCH425 OCB425 Type cased PCB only cased PCB only 2-2. Data 2-2-1. Packaged type Refer to each model's service manual. 2-2-2.
(1) PUHZ-HRP • V/YHA2 Outdoor unit Model name PUHZ-HRP71VHA2 Power supply (Phase, Voltage, Frequency) Breaker size Nominal water flow Capacity Heating COP (A2/W35) Power input Capacity Heating COP (A7/W35) Power input Capacity Heating COP (A7/W45) Power input Plate heat exchanger ALFA LAVAL ACH50 1[, 230V, 50Hz A L/min kW A: 50 mm B: 466 mm 32 22.9 8.00 3.24 2.47 8.00 4.40 1.82 8.00 3.24 2.
(2) PUHZ-RP • VHA3/YHA3(2) Outdoor unit Model name PUHZ-RP60VHA3#1 Power supply (Phase, Voltage, Frequency) Breaker size Nominal water flow Capacity Heating COP (A2/W35) Power input Capacity Heating COP (A7/W35) Power input Capacity Heating COP (A7/W45) Power input A L/min kW A: 50 mm B: 466 mm 25 20.1 6.80 2.94 2.31 7.00 4.29 1.63 7.00 3.27 2.14 kW kW kW kW kW Model name W:112 mm H: 526 mm D: 82 mm 30 plates kW kW kW Guaranteed operating range (Outdoor) : : H A Ref.
Plate heat exchanger ALFA LAVAL ACH50 Outdoor unit PUHZ-RP100VHA3#1 / PUHZ-RP100YHA3#1 Model name Power supply (Phase, Voltage, Frequency) Breaker size Nominal water flow Capacity Heating COP (A2/W35) Power input Capacity Heating COP (A7/W35) Power input Capacity Heating COP (A7/W45) Power input 1[, 230V, 50Hz / 3[, 400V, 50Hz A L/min kW A: 50 mm B: 466 mm 32 / 16 32.1 10.50 2.90 3.62 11.20 4.21 2.66 11.20 3.20 3.50 kW kW kW kW kW 65 32/16 40.1 11.50 2.70 4.26 14.00 4.15 3.37 14.00 3.10 4.
[2] Standard operation data Reference data (connect to Plate HEX) (1) PUHZ-HRP • V/YHA2 Capacity W Cooling (A35/W7) 7,100 Input kW 2.20 Outdoor Water conditions conditions Refrigerant circuit Electrical circuit Total Mode Outdoor unit Heating (A7/W35) 8,000 1.82 3.67 2.61 Cooling (A35/W7) 12,500 Heating (A7/W35) 14,000 4.80 3.
(2) PUHZ-RP • VHA3/YHA3(2) Capacity W Cooling (A35/W7) 6,000 Input kW 2.31 Outdoor Water conditions conditions Refrigerant circuit Electrical circuit Total Mode Outdoor unit ACH50-30 plates Heating Cooling (A7/W35) (A35/W7) 7,000 6,600 1.63 Heating (A7/W35) 8,000 2.59 1.90 ACH50-50 plates Cooling Heating (A35/W7) (A7/W35) 9,100 11,200 3.31 2.
Outdoor Water conditions conditions Refrigerant circuit Electrical circuit Total Mode Capacity Input W kW Outdoor unit Phase, Hz Voltage Current Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Evaporating temperature Evaporator inlet temperature Evaporator outlet temperature Condenser inlet temperature Condenser outlet temperature Flow volume V A MPa MPa : : : : : : : : Cooling (A35/W7) 12,000 5.
[4] Capacity correction curves (Refrigerant pipng length) Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. Cooling Heating 100 Heating 95 Capacity ratio [%] Cooling 60 models 90 Cooling 71 model 85 Cooling 100 model 80 Cooling 125 model Cooling 140 model 75 Note: The permitted pipe length is up to 55m for RP 60, 71 model. The permitted pipe length is up to 80m for HRP71 and 100~ 140 model.
[6] Notification to design/select HEX (Refrigerant - Water) Warranty for SPILIT solution • Specifications of AHU and compatibility with regulations must be confirmed by your company. • Selection of an apporopriate AHU (with appropriate specifications to match those of units connected to the AHU such as configuration, dimension, life-span, vibration, noise level, or features) must be made by your company.
• The water velocity in pipes should be kept within certain limits of material to avoid erosion,corrosion and excessive noise generation. Be aware, and take care of , that local velocities in small pipes, bends and similar obstructions can exceed the values of previous page. e.g.) Copper : 1.5m/s Warning • Use clean enough water which meets water quality standards. The deterioration of water quality may result in the system breakdown or the water leakage. • Never use anything other than water as a medium.
3 System design 3-1. System type * with step I/F * with FTC Application by digital/analog signals simple/basic/analog temp.
By our FTC FTC Heat Pump switch ON/OFF and the operation mode change is done… By remote controller Your system is SIMPLE SYSTEM. (FTC) By remote controller Your system is BASIC SYSTEM. (FTC) By external signals from local controller (non-voltage contact signals) ‘Target flow temperature’ is set… By external signals from local controller (Analog signal:4-20mA/ 1-5V/ 0-10V) Your system is ANALOG TEMP. SYSTEM. (FTC) SIMPLE SYSTEM BASIC SYSTEM ANALOG TEMP.
ATA application start IF Variable capacity request signals for Heat Pump is calculated... By local controller (your side) capacity signals protocol is...
( Wired Remote Controller (For Maintenance) 18 TB141 1-2 3-4 5-6 7-8 9-10 11-12 13-14 TB142 10-12 (COM-IN6) OFF OFF ON ON OFF OFF ON ON OFF TB142 10-11 (COM-IN5) OFF ON OFF ON OFF ON OFF ON OFF table 3 OFF ON ON ON ON OFF OFF OFF OFF TB142 10-13 (COM-IN7) Forced Comp.
。 TB142 1 2 3 4 5 6 7 8 9 10 11 12 13 14 FTC TB61 8 LED1 At site 8 1 SW3 U 1 2 3 4 5 6 7 8 9 10 11121314 X1 X2 X3 X4 X5 X6 X7 ZNR01 DSA TB141 TB6 S1 S2 S3 L N TB6 *2 Remove the short-circuited connector CNS2. S1 S2 S3 L N CNS2 (RED) 1 2 ZNR02 FUSE U Refer to Table 2. 2 4 6 8 10 12 14 1 3 5 7 9 11 13 DC311∼ 339V (External Output) FTC 8 RECTIFICATION 2 4 6 8 10 12 14 1 3 5 7 9 11 13 Refer to Table 1.
3-5.
(2) PAC-IF021B-E(FTC), PAC-IF020-E CN20 Thermistor (TH1) TB6 FTC/outdoor unit connecting LED2,3 TB61 1-2 Thermistor (TH1) TB61 3-4 Thermistor (TH2) CN21 Thermistor (TH2) TB62 3-4 4-20mA/1-5V/0-10V CN2A 4-20mA/1-5V/0-10V TB62 5-6 Wired remote controller CN22 Wired remote controller CN82 External input CN53 External input TB142 External input CNX2 Error Output CNX1 Operation Output CNX4 Defrost Output CNX3 Comp.
3-6. Specification of connectors Please connect wiring with either of the terminal bed or the connector. Parts on the PCB are different depending on the model.
4 Inter face (I / F) CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. System outline .................................................................................. 24 System structure ............................................................................... 24 Power supply .................................................................................... 28 Connecting thermistor....................................................................... 30 Interface controller switch setting ......
1. System outline With PAC-IF011B-E, local units can be connected with the outdoor units manufactured by MITSUBISHI ELECTRIC. The commands, such as Remote switch, Varistor, 4-20mA/1-5V/0-10V and etc., allow the inverter outdoor unit to operate, to stop and to switch capacity. By outputting the operation state, the interface can be connected with the local unit.Also, the interface can be connected with wired remote controller for maintenance so that the maintenance information is obtained.
Note: • REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting) TB142 TB142 TB142 TB142 10-11 10-12 10-13 10-14 (COM-IN5) (COM-IN6) (COM-IN7) (COM-IN8) Step for capacity setting * OFF ON OFF ON OFF ON OFF ON OFF [OFF] [ON] OFF OFF ON ON OFF OFF ON ON OFF OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF ON TypeA TypeB OFF 0% Step1 10% Step2 20% Step3 30% Step4 50% Step5 70% Step6 80% Step7 100% Auto step [OFF] [ON] OFF Step1 Step4 0% 10% 50% Step7 100% Remark Type A
System structure(2) Outdoor unit capacity switch System diagram Power supply specifications 4-20mA Capacity switch of outdoor unit according to the signal of 4-20mA Power supplied from outdoor unit A transmission line/Power line Intake temp. Liquid pipe temp. Local unit Local controller 4-20mA Local controller 1-5V Capacity switch of outdoor unit according to the signal of 1-5V Outdoor unit Power line Intake temp. Liquid pipe temp.
Attachment of sensor Refer to 4. Pipe-thermistor/ 2-phase might be neccessary depending on the type of the outdoor unit. Interface controller switch setting SW1-1:ON SW1-2:ON SW1-3:OFF SW6-1:ON SW6-2:ON Interface controller specifications Input and wiring Output and wiring Other functions/setting Maintenance Connection with BMS/MELANS Refer to 6. Refer to 7. Refer to 8, 9. Not available Refer to 6. Refer to 7. Refer to 8, 9. Not available Refer to 6. Refer to 7. Refer to 8, 9.
3. Power Supply Interface controller is applicable to both methods of interface unit power supplied from outdoor unit, and of separate interface unit/outdoor unit power supplies. Choose one according to the site. (Photo. 3-1) A Inlet for control cable B Inlet for power C Clamp D Interface / Outdoor unit connecting terminals E Earth terminal D C C Photo.3-1 E A B 3.1. Interface unit power supplied from outdoor unit (Photo 3-2) The following connection patterns are available.
3.2. Separate interface unit/outdoor unit power supplies The following connection patterns are available. The outdoor unit power supply patterns vary on models. D A B C L N F G B S1 S2 S3 A B C D E F G L N C S1 S2 S3 E Outdoor unit power supply Earth leakage breaker Wiring circuit breaker or isolating switch Outdoor unit Interface unit/outdoor unit connecting cables Interface unit Interface unit power supply Photo.
4. Connecting thermistor 4.1 Connecting thermistor cable Connect the thermistor for the interface controller. When the thermistor cables are too long, cut it to the appropriate length. Do not bind it in the interface unit. TB61 TH1 TH2 TH5 1. Target temp. thermistor (TH1) Connect the thermistor for the target temp. to 1 and 2 on the terminal block (TB61) on the interface controller. 2. Pipe temp. thermistor / Liquid (TH2) Connect the thermistor for the pipe temp.
< Thermistor for lower temperature > 50 Target temperature thermistor (TH1) Thermistor for lower temperature Pipe temperature thermistor/liquid (TH2) Pipe temperature thermistor / 2-phase (TH5) Resistance (k ) Thermistor R0 =15k" ± 3% Fixed number of B =3480 ± 2% Rt =15exp { 3480 ( 0: 10: 20: 25: 30: 40: 40 1 – 1 )} 273+t 273 15k" 9.6k" 6.3k" 5.4k" 4.3k' 3.0k" 30 20 10 0 -20 -10 0 10 20 30 40 50 Temperature ( ) 5.
6. Input specifications Demand control is available by external input. It is possible to set the outdoor unit’s power consumption by setting the switch of the interface controller.
• External function setting This function is to set operation mode or to stop compressor by the external signal. TB142 Item OFF ON 1-2 (IN1) Forced Comp. OFF Normal Forced Comp. OFF 3-4 (IN2)Item Fixed operation mode Cooling Heating Cable length : Maximum 10m Remote switch : Minimum applicable load DC12V, 1mA Remark Available when SW2-1 and SW2-2 are ON Caution: The external input signals are separated by basic insulation from power supply for the unit.
8. LED Display detail Setting SW3 allows to switch the LED display. LED1 : Power supply LED2~4 : Setting SW3 switches the display SW3-1 OFF ON OFF ON OFF ON OFF SW3-2 OFF OFF ON ON OFF OFF ON SW3-3 OFF OFF OFF OFF ON ON ON Display detail A B C D E F G [Display detail A] Details of LED display LED LED display LED2 Power supply for remote controller OFF : Power is not supplied.
9. Maintenance information Connecting wired remote controller(PAR-21MAA) enables to display the error information. Note: In case of using for ATW, the refrigerant leakage defection function of the outdoor unit is not available. 9.1. Connecting wired remote controller Turn off the power supply. TB62 : Connect the wired remote controller wire to No. 5, 6(non-polar). Note : Be sure to turn off the power supply before disconnecting the wired remote controller wire.
9.3. How to proceed "self-diagnosis" 9.3.1. When a Problem Occurs During Operation If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display. [CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below. (If the outdoor unit is malfunctioning, the unit number will be “00”.
Press the ON/OFF button twice within 3 seconds. The self-diagnosis address or refrigerant address will blink. When the error history is reset, the display will look like the one shown below. However, if you fail to reset the error history, the error content will be displayed again. Cancel self-diagnosis. Self-diagnosis can be cancelled by the following 2 methods. Press the CHECK button twice within 3 seconds. Press the ON/OFF button.
9.3.3. Malfunction-diagnosis method by remote controller Refer to the following tables for details on the check codes.
• If the unit cannot be operated properly after test run, refer to the following table to find the cause. Symptom Cause Wired remote controller LED 1, 2 (PCB in outdoor unit) For about 2 After LED 1, 2 are lighted, LED 2 is • For about 2 minutes following power-on,opPLEASE WAIT minutes after turned off, then only LED 1 is eration of the remote controller is not possible due to system start-up. (Correct operation) lighted.
Error code indication SELF-DIAGNOSIS ACTION TABLE Error Code P1 Abnormal point and detection method Target Temperature thermistor (TH1) 1 The unit is in 3-minute resume prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.) 2 Constantly detected during cooling, drying, and heating operation.
Error Code Abnormal point and detection method Freezing/overheating protection is working 1 Freezing protection (Cooling mode) The unit is in 6-minute resume prevention mode if pipe temperature stays under -15: for 3 minutes, 3 minutes after the compressor started. Abnormal if it stays under -15: for 3 minutes again within 16 minutes after 6-minute resume prevention mode.
Error Code E0 or E4 E1 or E2 Abnormal point and detection method Case Remote controller transmission error 1 Contact failure at transmission (E0)/signal receiving error (E4) wire of remote controller 1 Abnormal if main or sub remote controller 2 All remote controllers are set cannot receive any transmission normally as “sub” remote controller. In from Interface unit of refrigerant address this case, E0 is displayed on “0” for 3 minutes.
Error Code E6 E8 E9 EF Ed Abnormal point and detection method Case Judgment and action Interface unit/outdoor unit communication error (Signal receiving error) 1 Abnormal if Interface controller board cannot receive any signal normally for 6 minutes after turning the power on. 2 Abnormal if Interface controller board cannot receive any signal normally for 3 minutes. * Check LED display on the outdoor control 1 Contact failure, short circuit or, miswiring (converse wiring) circuit board.
9.3.4. HOW TO "MONITOR THE OPERATION DATA" • Turn on the [Monitoring the operation data] Example) Request code "004" Discharge temperature 69 Refrigerant address "00" (7) (3) (5) (1) (2) (6) (4) (1) Press the TEST A: Maintenance mode B: Refrigerant address C: Data display area D: Request code display area button for 3 seconds so that [ Maintenance mode] appears on the screen (at ). (2) Press the CHECK button for 3 seconds to switch to [Maintenance monitor].
9.4. Request code list Request code * Certain interface/outdoor combinations do not have the request code function; therefore, no request codes are displayed. Description Request content (Display range) Unit 0 Operation state Refer to 9.4.1. Detail Contents in Request Code.
Request code Description Request content (Display range) Unit 50 Interface unit-Control state Refer to 9.4.1.Detail Contents in Request Code. – 51 Outdoor unit-Control state Refer to 9.4.1.Detail Contents in Request Code. – 52 Compressor-Frequency control state Refer to 9.4.1.Detail Contents in Request Code. – 53 Outdoor unit-Fan control state Refer to 9.4.1.Detail Contents in Request Code. – 54 Actuator output state Refer to 9.4.1.Detail Contents in Request Code.
Request code Description Request content (Display range) Unit 103 Error history 1 (latest) Displays error history. (" - - " is displayed if no history is present.) Code 104 Error history 2 (second to last) Displays error history. (" - - " is displayed if no history is present.) Code 105 Error history 3 (third to last) Displays error history. (" - - " is displayed if no history is present.
9.4.
[Fan control state] (Request code :" 53 ") Data display 0 0 Fan step correction value by heatsink temperature overheat prevention control Fan step correction value by cool condensation temperature overheat prevention control Display - (minus) 0 1 2 Correction value –1 0 +1 +2 [Actuator output state] (Request code :"54") Data display 0 0 Actuator output state Actuator output state Actuator output state Actuator output state Display SV1 0 1 ON 2 3 ON 4 5 ON 6 7 ON 8 9 ON A b ON C d E F
[Contact demand capacity] (Request code "61") Data display 0 0 Setting content 0 Setting content Display Setting value 0 1 2 3 0% 50% 75% 100% Setting SW7-1 SW7-2 ON ON ON ON Silent mode input Spare 1 input [External input state] (Request code "62") Data display 0 0 Input state 0 Input state Display Contact demand input 0 1 2 3 4 5 6 7 8 9 A b C d E F [Outdoor unit - Capacity setting display] (Request code : "70") Data display 9 10 11 14 20 25 28 40 50 Capacity 35 50 60 71 100 125 14
[Outdoor unit switch setting display (SW1 to SW10, except SW3)] Request codes: 73 to 82 0: Swich OFF 1: Swich ON SW1, SW2, SW6, SW7 1 2 3 4 5 6 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1
10. Central control When connected with the outdoor unit, M-NET converter and A-control sub Interface can be connected to MELANS and BMS, which enables the central control available. As for the demand control setting, the central control is not available in the fixed capacity mode. However, with the wired remote controller method(Auto step mode), the central control is available. Operation with MELANS / BMS Set the switch from the following setting according to the specifications of the local unit. Ex.
11. Outlines and dimensions Unit : mm 336 313 69 Ø5 Ø12 22 (11.5) TB61 10 11.
12. Troubleshooting A flowing water sound or occasional hissing sound is heard. ■ Thease sounds can be heard when refrigerant is flowing in the indoor unit, refrigerant pipe or when the refrigerant is chaging. Water does not heat or cool well. ■ Clean the filter of water piping. (Flow is reduced when the filter is dirty or clogged.) ■ Check the temperature adjustment and adjust the set temperature. ■ Make sure that there is plenty of space around the outdoor unit.
5 Flow temp. controller (FTC) CONTENTS 1. 2. 3. 4. 5. 6. System .............................................................................................. 56 Electrical work................................................................................... 58 Before test run .................................................................................. 65 Remote controller operation ............................................................. 66 Initial setting by remote controller .............
1. System To start, check your system type by following the flow chart below.(FTC can be used for 3 types of systems.) Start Heat Pump switch ON/OFF and the operation mode change is done… By remote controller Your system is SIMPLE SYSTEM. By remote controller Your system is BASIC SYSTEM. By external signals from local controller (non-voltage contact signals) ‘Target flow temperature’ is set… By external signals from local controller (Analog signal:4-20mA/ 1-5V/ 0-10V) Your system is ANALOG TEMP.
Refer to the relevant sections for details according to your system type. System BASIC Outdoor unit SPLIT type TH1 TH2 Local controller ON/OFF MODE TH1 TH2 Local controller ON/OFF MODE PACKAGED type TH1 Local controller ON/OFF MODE TH1 Local controller ON/OFF MODE ANALOG TEMP. SPLIT type TH1 TH2 Local controller ON/OFF Temp. TH1 TH2 Local controller ON/OFF Temp. PACKAGED type FTC FTC Local controller ON/OFF Temp. TH1 Local controller ON/OFF Temp.
2. Electrical work 2.1. FTC (Photo. 2-1) 1. Remove the cover. 2. Wire the power cable and control cable separately through the respective wiring inlets given in the photo. • Make sure to put screws tightly. A Inlet for control cable B Inlet for power C Clamp D FTC / Outdoor unit connecting terminals E Earth terminal D C C Photo.2-1 B E A 2.1.1. FTC unit power supplied from outdoor unit The following connection patterns are available. The outdoor unit must be powered properly.
2.1.2. Separate FTC unit/outdoor unit power supplies The following connection patterns are available. The outdoor unit power must be powered properly(Details are shown in its installation manual).
2.2. Connecting thermistor cable TB61 Connect the thermistor 2 for the FTC controller. 2.2.1. Connecting the actual flow water temp. thermistor (TH1) TH1 Connect the thermistor for the actual flow water temp. to 1 and 2 on the terminal block (TB61) on the FTC controller. TH2 When the thermistor cables are too long, cut them at the appropriate length. Do not bind them in the FTC unit. Put TH1 on water piping (water outlet side).
2.3. Connecting the wired remote controller 2.3.1. Connecting the wired remote controller cable to FTC 30 Connect the wired remote controller cable to 5 and 6 on the terminal block (TB62) on the FTC controller.(Photo. 2-4) Wiring wire No.×size(mm2) : 2×0.3(Non-polar) The 5m wire is attached as an accessory. Max. 500 m Wiring size must comply with the applicable local and national codes. Circuit rating: DC12V Circuit rating is NOT always against the ground. 30 30 83.
2.4. Switch setting of FTC Set the dip switch on the FTC (PCB) according to the following table. System BASIC ANALOG TEMP. BASIC and SIMPLE SIMPLE *1: *2: *3: *4: ON/OFF Input External input (non-voltage contact) Change mode Input External input (non-voltage contact) Change TEMP.
SW2-1~8 SW3-1~3 Fixed set temperature with DIP switch of FTC (Available when SW1-6 is ON) SW2-1~3 Fixed set temperature for Heating mode (Table1~2 depends on SW1-7,8.) SW2-1 OFF ON OFF ON OFF ON OFF ON SW2-2 OFF OFF ON ON OFF OFF ON ON SW2-3 OFF OFF OFF OFF ON ON ON ON Table1 25 ºC 30 ºC 35 ºC 40 ºC 45 ºC 50 ºC 55 ºC 60 ºC *1 Table2 25 ºC 30 ºC 35 ºC 40 ºC 45 ºC 50 ºC 55 ºC 60 ºC *1 The selectable temperature range for Heating mode depends on outdoor unit type.
2.5.2 EXTERNAL INPUT ( analog signal ) 4-20mA / 1-5V / 0-10V Connect the transmission cables to No. 3 and 4 on the terminal block (TB62). No. 3 on the terminal block(TB62) : Plus side No.
2.7. Wiring specification of External output / External input Locally supplied parts Item External output function Name External output signal wire Display lamp, etc. External input function External input signal wire Switch Model and specifications Use sheathed vinyl coated cord or cable. Max. 50m Wire type : CV, CVS or equivalent Wire size : Stranded wire 0.5mm2 to 1.25mm2 Solid wire: {0.65mm to {1.
4. Remote controller operation 4.1 Parts name ■ Wired Remote-Controller Display Section For purposes of this explanation, all parts of the display are shown. During actual operation, only the relevant items will be displayed. Identifies the current operation Shows the operating mode, etc. * Multi language display is supported. Day-of-Week Shows the current day of the week. Time/Timer Display “Locked” indicator Shows the current time, unless the simple or Auto Off timer is set.
Function Selection of remote controller For details on setting the language for the remote controller display, refer to 4.6. Function Selection. The initial language setting is English. Set Day/Time TIME SUN ● Function Selection of remote controller: Set the functions and ranges available to the remote controller (timer functions, operating restrictions, etc.) ● Set Day/Time: Set the current day of the week or time.
4.3.2. Mode select Press operation mode ( ) button2 and select operation mode. Heating mode (Space heating) Heating ECO mode (Space heating with weather compensation *1) Hot water mode (Sanitary hot water) Anti freeze mode (Heating to prevent water pipe from freezing) Cooling mode (Space cooling) *1 Target flow temp. varies according to the outdoor temperature. (Refer to 5. for setting.) 2 3 ˚C ˚C TEMP. ON/OFF 3 2 4.3.3.
4.4.2. Error Codes indication ERROR CODE ON/OFF ON lamp (Blinking) Indoor Unit’s Error Code Indoor Unit No. Refrigerant Address Alternating Display If you have entered contact number to be called in the event of a problem, the screen displays this number. (You can set this up under Function Selection of remote controller. For information, refer to 4.5.
[Function selection flow chart] Setting language(English) Hold down the ( ) button and press the ( ) button for 2 seconds. Normal display Hold down the ( ) button and press the ( ) button for 2 seconds. Change Language Dot display English Germany Spanish Russian Swedish French TEMP. ON/OFF Italian Function selection OFF No1 OFF … Operation lock setting is not used.
[Detailed setting] [4]-3 Mode selection setting [4]-1 CHANGE LANGUAGE setting The language that appears on the dot display can be selected. • Press the [ MENU] button G to change the language. 1 English (GB), 2 German (D), 3 Spanish (E), 4 Russian (RU), 5 Italian (I), 6 French (F), 7 Swedish (SW) Refer to the dot display table. [4]-2 Function selection setting (1) Operation function limit setting (operation lock) • To switch the setting, press the [ ON/OFF] button D.
[Dot display table] Selecting language English German Spanish Russian Italian French Swedish English German Spanish Russian Italian French Swedish Waiting for start-up Operation mode Heating Heating ECO Hot water Anti-freeze Cooling Stand by (Hot adjust) Defrost Not use button Check (Error) Test run Self check Change language Language selection Display change Temperature display ˚C/˚F setting Water temperature display setting Function selection Operation function limit setting Selecting la
[Dot display table] Selecting language English German Spanish Auto off timer Function selection Check (Error) Test run Self check Colective setting Water temperature Heating (Initial setting) Heating ECO Hot water Anti-freeze Cooling Option setting(Heating) Option setting(Cooling) Water circuit check Waiting for response Waiting for setting Not dealt with Maintenance 73 Russian Italian French Swedish
5. Initial setting by remote controller ˚C ˚C TEMP. ON/OFF (1) Press the INITIAL SETTING button for 3 seconds to activate the initial setting mode. (2) [DISPLAY ] WATER TEMP HEATING WATER TEMP HEATING ECO WATER TEMP HEATING ECO No. 1* No. 2* WATER TEMP HOT WATER WATER TEMP ANTI-FREEZE WATER TEMP COOLING TEMP OFFSET HEATING TEMP OFFSET COOLING * No.1 or No.2 is indicated in display . Press MODE button to switch to the next parameter setting.
This setting is to adjust the difference between the actual flow water temperature at the refrigerant-water heat exchanger outlet and the temperature sensed by TH1 which tends to be lower due to heat leakage from water piping. HEATING mode T(a)=Actual Flow water temp.(outlet side) ӠT(h) =T(a)-T(s) FTC Outdoor unit TH1 *1 T(s)=sensed flow water temp. Water piping *1 Refrigerant-water HEX COOLING mode T(a)=Actual Flow water temp.
6. Definition of analog signal by remote controller (Required only for ANALOG TEMP. system) Set following 2 parameters to assign the target temperature value to analog signal figures. (1) Press INITIAL SETTING button for 3 seconds to activate this setting mode. (2) [DISPLAY ] AD INPUT HEATING FLOW TEMP. AD INPUT COOLING No.2 Press MODE button to switch to the next parameter setting. No.1 AD INPUT HEATING Set flow temp. for No.1 and No.2 with [TEMP] buttons ( and ) .
7. Troubleshooting A flowing water sound or occasional hissing sound is ■ Thease sounds can be heard when refrigerant is flowing in the indoor unit, refrigerant pipe or when the refrigerant is chaging. heard. Water does not heat or cool well. ■ Clean the filter of water piping. (Flow is reduced when the filter is dirty or clogged.) ■ Check the temperature adjustment and adjust the set temperature. ■ Make sure that there is plenty of space around the outdoor unit.
Error code indication [1] SELF-DIAGNOSIS ACTION TABLE Error Code P1 You can check an error code on both 1 and 2. 1 LCD display on remote controller 2 2-digit LED indicator on outdoor unit PCB (For SPLIT type outdoor unit, this LED indicator is optional parts.PAC-SK52ST) * The 2-digit LED indicator on outdoor unit PCB can display indoor side error as well.
Error Code E0 or E4 E1 Abnormal point and detection method Cause Countermeasure Remote controller transmission error 1 Contact failure at transmission (E0)/signal receiving error (E4) wire of remote controller 1 Abnormal if main or sub remote con2 All remote controllers are set troller cannot receive any transmission as “sub” remote controller. In normally from FTC of refrigerant address this case, E0 is displayed on “0” for 3 minutes.
Error Code E8 E9 EF Ed Abnormal point and detection method Case Judgment and action FTC/outdoor unit communication error (Signal receiving error) (Outdoor unit) (1) Abnormal if outdoor controller circuit board could not receive anything normally for 3 minutes. 1 Contact failure of FTC/outdoor 1 Check disconnection or looseness of FTC/ unit connecting wire outdoor unit connecting wire of FTC or out2 Defective communication circuit door unit.
[2] HOW TO "MONITOR THE OPERATION DATA" • Turn on the [Monitoring the operation data] Example) Request code "004" Discharge temperature 69 Refrigerant address "00" (7) (3) (5) (1) (4) (1) Press the TEST PAR-W21MAA (2)(6) A: Maintenance mode B: Refrigerant address C: Data display area D: Request code display area button for 3 seconds so that [ Maintenance mode] appears on the screen (at ). (2) Press the CHECK button for 3 seconds to switch to [Maintenance monitor].
[3] Request code list Request code * Certain FTC/outdoor combinations do not have the request code function; therefore, no request codes are displayed. Description Request content (Display range) Unit 0 Operation state Refer to Detail Contents in Request Code.
Request code Description Request content (Display range) Unit 50 FTC unit-Control state Refer to Detail Contents in Request Code. – 51 Outdoor unit-Control state Refer to Detail Contents in Request Code. – 52 Compressor-Frequency control state Refer to Detail Contents in Request Code. – 53 Outdoor unit-Fan control state Refer to Detail Contents in Request Code. – 54 Actuator output state Refer to Detail Contents in Request Code.
Request code Description Request content (Display range) Unit 103 Error history 1 (latest) Displays error history. (" - - " is displayed if no history is present.) Code 104 Error history 2 (second to last) Displays error history. (" - - " is displayed if no history is present.) Code 105 Error history 3 (third to last) Displays error history. (" - - " is displayed if no history is present.
Detail Contents in Request Code [Operation state] (Request code ":0") Data display A: Maintenance mode display B: Refrigerant address C: Data display area D: Request code display area Relay output state Display C 4 0 1 2 3 4 5 6 7 8 A Relay output state Operation mode Operation mode Display 0 C H d Example) Request code "004" Discharge temperature 69 Refrigerant address "00" Operation mode STOP • FAN COOL • DRY HEAT DEFROST Power currently supplied to compressor – Compressor 4-way valv
[Fan control state] (Request code :" 53 ") Data display 0 0 Fan step correction value by heatsink temperature overheat prevention control Fan step correction value by cool condensation temperature overheat prevention control Display - (minus) 0 1 2 Correction value –1 0 +1 +2 [Actuator output state] (Request code :"54") Data display 0 0 Actuator output state Actuator output state Actuator output state Actuator output state Display SV1 0 1 ON 2 3 ON 4 5 ON 6 7 ON 8 9 ON A b ON C d E F
[Contact demand capacity] (Request code "61") Data display 0 0 Setting content 0 Setting content Display Setting value 0 1 2 3 0% 50% 75% 100% Setting SW7-1 SW7-2 ON ON ON ON Silent mode input Spare 1 input [External input state] (Request code "62") Data display 0 0 Input state 0 Input state Display Contact demand input 0 1 2 3 4 5 6 7 8 9 A b C d E F [Outdoor unit - Capacity setting display] (Request code : "70") Data display 9 10 11 14 20 25 28 40 50 Capacity 35 50 60 71 100 125 14
[Outdoor unit switch setting display (SW1 to SW10, except SW3)] Request codes: 73 to 82 0: Swich OFF 1: Swich ON SW1, SW2, SW6, SW7 1 2 3 4 5 6 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1
8. Outlines and dimensions Unit : mm 336 313 69 Ø5 Ø12 22 (11.5) TB61 10 11.5 2-HOLES (FOR INSTALLATION) 200 278 TB62 TB142 TB6 TB141 2-Ø5 HOLES (FOR INSTALLATION) 3-ELECTRIC WIRE INLET WIRED REMOTE CONTROLLER 43.
6 Requirements 6-1. For functional parts 6-1-1. Thermistor position Refer to section 4. Interface or 5. Flow temp. controller for detail. (1) I / F : PAC-IF011B-E (cased), PAC-IF010-E (PCB only) Application Air to Water Air to Air Capacity Control Water HEX Terminal "TH1" target temp. Terminal "TH2" Pipe temp./Liquid Terminal "TH5" Pipe temp.
7 System example 1. Air to Water application (1) Domestic Hot Water + Space heating by radiator with packaged outdoor unit + FTC *variable capacity request signals for Heat Pump is calculated by FTC. 1) System outline * DHW cylinder unit * TRV(Thermostatic Radiator Valve) *Radiator Immersion heater Room thermostat: installed in the coldest room * Time switch FTC *pump *valve Packaged O/U * Flow sensor (to prevent pipes from freezing) Flow temp.
(2)-1. Space heating by under floor heating with split outdoor unit+HYDROBOX + FTC *variable capacity request signals for Heat Pump is calculated by FTC. 1) System outline * Under Floor Heating HYDRO BOX (locally supplied) *system controller FTC (PCB) Refrigerant pipe (Gas) Split O/U * *pump * *Valve Refrigerant pipe (Liquid) Auxiliary heater Flow sensor (to prevent pipes from freezing) Flow temp. thermistor (outlet side) Refrigerant pipe temp.
(2)-2. Domestic Hot Water + space heating by under floor heating with split outdoor unit+HYDROBOX + IF *variable capacity request signals for Heat Pump is calculated by local system controller. 1) System outline * Under Floor Heating HYDRO BOX(locally supplied) *system controller IF (PCB) Refrigerant pipe (Gas) Split O/U *Valve *pump * Refrigerant pipe (Liquid) *Flow sensor (to prevent pipes from freezing) *Flow temp. thermistor (outlet side) Refrigerant pipe temp.
2. Air to Air application Air-Handling Unit with split outdoor unit + IF *variable capacity request signals for Heat Pump is calculated by IF. 1) System outline Air-Handling Unit (locally supplied) PAR-21MAA Remote Controller (for user interface) Refrigerant pipe (Gas) Split O/U *system controller IF (PCB) * Outlet Air *FAN Refrigerant pipe (Liquid) Return Air *Auxiliary heater Refrigerant pipe temp.themistors (Liquid / 2phase) Return Air temp.
Air to Water (ATW) Heat pump, Interface (I/F) and Flow temp. controller (FTC) Technical manual HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Issued in Jun. 2008 M-P0398 SIZ Printed in Japan New publication effective Jun.