Specifications

4 - 7
4 AUXILIARY AND APPLIED FUNCTIONS
(5) Forced output bit
(a) Set the "forced output bit" when you want to forcibly provide the limit switch
outputs during operation.
1) The following control is exercised.
Forced output bit Control description
Without setting
OFF
Limit switch outputs are turned
ON/OFF on the basis of the "output
enable/disable bit" and ON region
setting (ON Value, OFF Value).
With setting
ON Limit switch outputs are turned ON.
(b) Usable devices
Item Device No. setting range
Input relay X0 to X1FFF
Output relay Y0 to Y1FFF
Internal relay M0 to M8191
Latch relay L0 to L8191
Link relay B0 to B1FFF
Annunciator F0 to F2047
Special relay M9000 to M9255