QA6ADP QA Conversion Adapter Module User’s Manual QA6ADP Thank you for buying the Mitsubishi general-purpose programmable logic controller MELSEC-Q Series Prior to use, please read both this manual and detailed manual thoroughly and familiarize yourself with the product.
Revisions Print Date Aug., 2007 Mar., 2008 * The manual number is noted at the lower right of the top cover. *Manual Number Revision IB(NA)-0800402-A First printing IB(NA)-0800402-B Partial correction Section 2.2, 6.1 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
CONTENTS 1. OVERVIEW....................................................................................................3 1.1 Overview ...............................................................................................3 1.2 Included Parts .......................................................................................3 2. SYSTEM CONFIGURATION .........................................................................4 2.1 System Configuration ................................................
1. OVERVIEW 1.1 Overview This user’s manual describes the specifications, configuration device, part names and setting, and implementation and installation of the QA6ADP QA conversion adapter module. For contents that are not described in this manual such as safety precautions, EMC and low voltage directives, or error code list, refer to QCPU User’s Manual (Hardware Design, Maintenance and Inspection) (SH-080483).
2. SYSTEM CONFIGURATION 2.1 System Configuration This section describes the system configuration and restrictions when the QA6ADP is used. (1) The QA6ADP+A5 B/A6 B is only applicable for the High Performance model QCPU (Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU). (2) Mount the Q5 B/Q6 B, QA6 B, and QA6ADP+A5 B/A6 B in order from the nearest position of the main base unit. The QA6ADP cannot be used in combination with the QA1S6 B.
2.2 Configuration Device List (1) Extension base unit mountable on the QA6ADP The following shows extension base units that can be mounted on the QA6ADP.
Product name High-speed counter module A/D converter module Model AD61S1 AD61, A68AD, A68AD-S2, A616AD D/A converter module A62DA, A62DA-S1, A68DAI-S1, A616DAV, Temperature-digital A68RD3N, A68RD4N, converter module A60MX, A60MXRN, Interrupt module AI61, AI61-S1 Positioning module AD70, AD72 AD75M1, AD75M2, AD75P1-S3, AD75P2-S3, A-A1S module conversion A1ADP-XY, A1ADP-SP adapter MELSECNET/MINI-S3 AJ71PT32-S3, master module AJ71T32-S3 Intelligent communication AD51, AD51-S3, module AD51H-S3 PC fault detec
3. SPECIFICATIONS 3.1 General Specifications This section describes general specifications of the QA6ADP. Item Operating ambient temperature Storage ambient temperature Operating ambient humidity Storage ambient humidity Specifications 0 to 55 -20 to 75 10 to 90 % RH, No-condensing 10 to 90 % RH, No-condensing Accelera Sweep Amplitude -tion count Conforming Under 10 to 57 Hz ---0.075 mm 10 times to intermittent each in 57 to 150 Hz 9.8 m/s2 ---JIS B 3502, vibration X, Y, Z IEC 61131-2 Under 00.
3.2 Performance Specifications This section describes performance specifications of the QA6ADP. Item Specifications 5VDC internal current 110 mA consumption 130 mm (5.11 inch) (H) 73.5 mm (2.89 inch) External dimensions *1 (W) 74 (2.91 inch) mm (D) Weight 0.2 kg Adapter mounting screw 0.36 to 0.48 N•m (M3) torque Board fixing screw 0.61 to 0.82 N•m torque *1: The external dimensions show values in a status where the QA6ADP is mounted on the extension base unit.
4. PART NAMES AND SETTING 4.1 Part Names This section describes part names of the QA6ADP. 9) 8) 3) 1) 7) 6) 4) 2) 5) No.
4.2 Extension Stage Number Setting Set the number of extension stages to both the QA6ADP and the extension base unit. The same stage number should be set to both the stage number setting connector of the extension base unit and that of the QA6ADP. POINT Set any number of 1 to 7 which matches to the number of extension stages for the stage number setting connector setting.
5. LOADING AND INSTALLATION 5.1 Mounting/Removal of QA6ADP (1) Mounting of the QA6ADP The following shows procedures for mounting the QA6ADP on the extension base unit. Disconnect the A series extension cable from the extension base unit. A) Remove a base cover from the extension base unit. Set the stage number setting connector of the extension base unit. Set the stage number setting connector of the QA6ADP.
(2) Removal of the QA6ADP The following shows procedures for removing the QA6ADP from the extension base unit. Board fixing screw Disconnect an extension cable form the QA6ADP. Remove the adapter module mounting screws of the QA6ADP at two parts (top and bottom). Remove the QA6ADP main body from the extension base unit. Mounting guide Extension base unit IN side connector Adapter module mounting bracket Remove a board fixing screw and an adapter module mounting bracket of the QA6ADP.
5.2 Connection/Disconnection of Extension Cable (1) Precautions for handling an extension cable • Do not step on an extension cable. • When laying an extension cable, the minimum bend radius of the cable should be 55 mm (2.17 inch) or more. If it is less than 55 mm (2.17 inch), malfunction may occur due to characteristic deterioration, wire break etc. • When connecting or disconnecting an extension cable, do not hold ferrite cores mounted at both ends of the cable.
• To connect an extension cable to the QA6ADP, remove a sticker on the IN side connector. Base cover IN side Extension base unit QA6ADP Sticker • To connect an extension cable to the OUT side connector of the QA6ADP, remove the portion (lid) under the characters "OUT" by tools such as a flathead screwdriver (5.5 75, 6 100).
• Hold the connector part of an extension cable when connecting the extension cable to the QA6ADP. Extension base unit QA6ADP Connector Extension cable • Make sure to tighten fixing screws of the extension cable connector after connecting the extension cable. (Tightening torque: 0.
6. PRECAUTION FOR USING QA6ADP 6.1 Current Consumption of QA6ADP Since 5VDC is supplied to the QA6ADP from the power supply module of the main base unit, take the current consumption of the QA6ADP into consideration when selecting the power supply module for the main base unit.
6.2 Voltage Drop of Extension Cable Since 5VDC is supplied to the QA6ADP from the power supply module mounted on the main base unit, the voltage drop will be caused in the extension cable. If the specified voltage (4.75VDC or more) is not supplied to the IN side connector of the QA6ADP+A5 B/A6 B, wrong input/output may occur. When using the QA6ADP, check that the IN side connector of the QA6ADP+A5 B/A6 B has 4.75VDC or more. The following shows an example regarding how to calculate the voltage drop.
7. COMPATIBLE MODELS LIST This chapter describes external dimensions of the QA6ADP. A series extension base unit that you have already had 2 6-M4 screw (for mounting module) QA6ADP QA conversion adapter module 4- 6mounting hole (M5 mounting screw) Handle I/O I/O I/O I/O I/O 200 (7.87) 130 (5.11) POWER 9 (0.35) 74 (2.91) 73.5 (2.89) Power supply module, Extension cable Power supply module 250 (9.84) Extension cable 121 (4.76) 172 (6.
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.