M A G N E T IC M O T O R D R IV E U N IT S E R IE S IN S T R U C T IO N M A N U A L S E R IE S H ig h P e r fo r m a n c e & H ig h F u n c tio n M D -C X 5 2 2 -0 .4 K to 3 .
Please read here first Thank you for choosing the Mitsubishi Magnetic Motor Drive Unit. This instruction manual gives handling information and precautions for use of the drive unit. Incorrect handling of the equipment may cause an unexpected fault. To optimize the unit capability, please read this manual carefully before using the equipment. General precautions Please forward this instruction manual to the end user.
Please read here first (Continued) Safety Instructions This section is specifically about safety matters Do not attempt to install, operate, maintain or inspect the drive unit until you have read through this instruction manual and appended documents carefully and can use the equipment correctly. Do not use the drive unit until you have a full knowledge of the equipment, safety information and instructions.
1. Usage WARNING The MELIPM series motor is a synchronous motor with high-performance magnets built in its rotor. Therefore, after the drive unit is powered off, there are high voltages at the motor terminals while the motor is running. Before starting wiring or maintenance and inspection, make sure that the motor has stopped.
4. Wiring WARNING Any person who is involved in the wiring of this equipment should be fully competent to do the work. Otherwise, an electric shock or fire can occur. Install a no-fuse breaker or earth leakage circuit breaker. Otherwise, a drive unit failure can cause large currents to flow, resulting in a fire. Always install the unit before wiring. Otherwise, an electric shock or fire can occur.
5. Operation WARNING Always replace the front cover before switching input power on. While power is on, do not remove the front cover. Doing so can cause an electric shock. Operate the switches with dry hands. Not doing so can cause an electric shock. Prepare an emergency stop switch separately. The "STOP/RESET" key of the parameter unit is valid for stopping only when the function setting has been made. Not using a separate emergency stop switch can cause accidents.
6. Maintenance, Inspection and Part (Cooling Fan) Replacement WARNING Any person who is involved in maintenance, inspection or part replacement should be fully competent to do the work. Otherwise, an electric shock or injury can occur. Before starting maintenance, inspection or part replacement, make sure that the motor is at a stop, wait for more than 10 minutes after switching power off, and confirm that the DC voltage across the DC terminals P/+ and N/- is low enough to do the work.
CONTENTS Page 1. PRE-OPERATION INFORMATION 1.1 Checking the Product 1-1 1-1 1.1.1 Contents .................................................................................. 1-1 1.1.2 Type ........................................................................................ 1-1 1.1.3 Drive units to be used with motors .......................................... 1-1 1.2 Parts Identification 1-2 1.3 Handling of Covers and the Like 1-3 1.3.
3.2.4 Wiring of the motor connection terminals U, V, W................... 3-4 .......................................... 3-4 3.2.5 Wiring of the ground terminals 3.2.6 Wiring of the DC reactor connection terminals P/+, P1 ........... 3-5 3.2.7 Wiring of the brake resistor connection terminals P/+, PR ...... 3-5 3.2.8 Wiring of the DC terminals P/+, N/- ......................................... 3-5 3.3 Wiring of the Control Circuit Terminals 3-6 3.3.1 Terminals.............................................
6.3 Maintenance and Inspection 6-7 6.3.1 Inspection ................................................................................ 6-7 6.3.2 Wear parts............................................................................... 6-9 6.3.3 Cooling fan replacement method ...........................................6-10 7. SPECIFICATIONS 7-1 7.1 Standard Specifications 7-1 7.1.1 Rating specifications ............................................................... 7-1 7.1.2 Common specifications .....
1. PRE-OPERATION INFORMATION 1. PRE-OPERATION INFORMATION 1.1 Checking the Product Unpack the drive unit, inspect the contents, and check the name plate to ensure that the product agrees with your order. 1.1.1 Contents Contents Drive unit Instruction manual Quantity 1 1 1.1.2 Type Locations of the capacity plate and name plate and definitions of their descriptions Capacity plate MITSUBISHI MODEL MD-CX522-0.
1. PRE-OPERATION INFORMATION 1.
1. PRE-OPERATION INFORMATION 1.3 Handling of Covers and the Like 1.3.1 Removal and reinstallation of the front cover (Lower) The front cover is fastened by the latches in positions A and B. Push either A or B in the direction of arrow, and using the other end as a support, pull the front cover toward you to remove. 1) A 2) 3) B 1 To reinstall the front cover, fasten it with the latches securely. 1.3.
1. PRE-OPERATION INFORMATION 1.3.3 Removal and reinstallation of the operation panel Hold down the arrow part A, and using the arrow part B as a support, pull the right hand side of the operation panel toward you and remove the panel rightward. 2) 1) 3) B A If the operation panel is removed in any other method, force will be applied to the internal connector, damaging the panel.
1. PRE-OPERATION INFORMATION 1.4 Transportation When carrying, always support the whole drive unit. 1.5 Storage Store the drive unit in the following environment. No corrosive gas, flammable gas, oil mist, dust and dirt. No exposure to direct sunlight. No salt. Ambient temperature -10°C to +50°C (non-freezing) Storage temperature -20°C to +65°C (applies to short-time transit) 90%RH or less (non-condensing) Ambient humidity Vibration 5.
2. INSTALLATION 2. INSTALLATION This chapter gives preparatory information on installation and wiring of the drive unit. NOTICE The Japanese harmonic suppression guidelines for suppression of harmonics were established by the Ministry of Economy, Trade and Industry (formerly Ministry of International Trade and Industry) in September, 1994.
2. INSTALLATION 2.1.2 Installation in control box When installing the drive unit in a control box, the internal temperature of the control box must not exceed the permissible value due to drive-unit generated heat and peripheral-generated heat. Placing a heat sink outside the control box can reduce the heat generated inside the control box.
2. INSTALLATION 2.2 Preparation of Peripheral Devices 2.2.1 Basic configuration Power equipment capacity As the power equipment capacity, select the kVA value not less than the one given in the specifications. Refer to: Chapter 7, 7.1.1 Rating specifications No-fuse breaker or earth leakage circuit breaker Always connect either of the above for circuit (wiring) protection. Make selection in accordance with the selection table. Choose the earth leakage circuit breaker which has harmonic suppression.
2. INSTALLATION 2.2.2 Selection of peripheral devices (1) Wire size AC power input terminals R, S, T, motor connection terminals U, V, W, DC reactor connection terminals P/+, P1, DC terminals P/+, N/-, ground terminals Capacity (K) Terminal Screw Size R, S, T M3.5 2 M4 2 to 5.5 0.4 0.75 1.5 2.2 3.7 Wire Sizes, Unit: mm2 Wire Type U, V, W P/+, P1, N/- Connection Power 2 2 2 cable 600V vinyl wire or 2 to 5.5 2 to 5.5 2 to 5.
2. INSTALLATION (3) No-fuse breakers, magnetic contactors Capacity (K) 0.4 0.75 1.5 2.2 3.
2. INSTALLATION 2.3 Installation Method 1) Remove the front covers. (Upper and lower) 2) Remove the wiring cover. 3) Pass screws or bolts into the four mounting holes and secure the drive unit. (Three mounting holes for 0.75K or less) CAUTION Prevent screws, metal pieces and other conductive foreign matter and oil and other flammable foreign matter from entering the drive unit. Securely screw or bolt the unit to the mounting surface vertically without looseness.
3. WIRING 3. WIRING This chapter describes the wiring of the drive unit. WARNING Any person who is involved in the wiring of this equipment should be fully competent to do the work. Otherwise, an electric shock or fire can occur. Always install the unit before wiring. Otherwise, an electric shock or fire can occur.
3. WIRING 3.1 Pre-Wiring Instructions 3.1.1 Terminal connection diagram The following shows the wiring of all terminals. After confirming the function of each terminal, wire necessary terminals according to your application. When the Parameter unit is used to perform operation, merely doing the main circuit wiring enables the motor to run.
3. WIRING 3.2 Wiring of the Main Circuit Terminals 3.2.1 Terminals Symbols R, S, T U, V, W P/+, PR Name AC power input terminals Motor connection terminals Brake resistor connection terminals P/+, P1 DC reactor connection terminals P/+, N/- DC terminals Ground terminals Description Connect to the commercial power supply. Connect to a dedicated variable-speed synchronous motor. Connect the brake resistor (option).
3. WIRING 3.2.4 Wiring of the motor connection terminals U, V, W Connect these terminals to the motor. Match the phase sequence of the motor connection terminals U, V, W with that of the motor cables. Incorrect phase sequence will run the motor in reverse. Ground terminal U V W U V W Motor Ground CAUTION The wiring length between the drive unit and motor should be 100m maximum. Long wiring may cause torque to be insufficient or the overcurrent protection function to be activated.
3. WIRING 3.2.6 Wiring of the DC reactor connection terminals P/+, P1 These terminals are designed for connection of the power factor improving reactor (FR-BEL). Remove the jumper across the terminals P/+-P1 and connect the DC reactor. CX522-0.4K,0.75K N/- P1 P/+ PR FR-BEL CX522-1.5K to 3.7K P/+ Remove jumper. P1 FR-BEL Remove jumper. NOTICE MEMO The wiring distance (overall length) should be within 5m. Without removal of the jumper, the reactor will not be active. 3.2.
3. WIRING 3.3 Wiring of the Control Circuit Terminals CAUTION Use shielded or twisted cables for wiring the control circuit input terminals. Also run them away from the main circuit wiring and other power cables. Not doing so can cause a malfunction due to noise. 3.3.1 Terminals (1) Contact input terminals Turning the signal across any terminal and common terminal "ON" (closing those terminals)/"OFF" (opening those terminals) provides the corresponding function as described below.
3.
3. WIRING Ratings of transistor output terminals Max. permissible voltage: 27VDC, max. permissible current: 0.1ADC MEMO NOTICE When driving a coil load, connect a diode. Refer to: 3.3.5 Wiring of the transistor output terminals (4) Contact output terminals When the protective function is activated, the relay contact connected to the terminal opens/closes. Refer to: Chapter 6, 6.1.1 Protective function activated Symbol Contact Capacity A, B, C MEMO 200VAC 0.3A or 30VDC 0.
3. WIRING 3.3.2 Terminal layout and connection specifications Layout Terminal layout of control circuit RH RM RL MRS RES SD FM PC SE RUN FU Screw size M2.5 A B C 10 2 5 4 SD STF STR SD Tightening torque 0.25N•m to 0.49 N•m Wiring method 1) For wiring the control circuit, use cables after stripping their sheaths. Refer to the gauge printed on the drive unit and strip the sheaths to the following dimensions. If the sheath is stripped too much, its cable may be shorted with the adjoining cable.
3. WIRING 3.3.3 Wiring of the contact input terminals Use shielded or twisted shielded cables for wiring. Connect one shield sheath to the common terminal. Leave the other shield sheath open. When using contact signals The following shows the wiring of the terminals STF, STR. The same wiring also applies to the other terminals. The terminal SD is a common terminal.
3. WIRING 3.3.4 Wiring of the speed command input terminals Use shielded or twisted shielded cables for wiring. Connect one shield sheath to the terminal 5. Leave the other shield sheath open. The following diagram shows the wiring of the terminal 2. The same wiring also applies to the other terminals. Drive unit 10 2 5 3.3.5 Wiring of the transistor output terminals The terminal SE is a common terminal.
3. WIRING 3.3.6 Wiring of the contact output terminals The following wiring example assumes that when the protective circuit is activated, the magnetic contactor (MC) on the power supply side is opened to switch off the main circuit power. NFB MC Drive unit R Power supply S T Stop F Operation-ready MC B C MC 3.3.
3. WIRING 3.4 Wiring of the PU Connector 3.4.1 Pin layout As seen from the drive unit (receptacle side) front 1) SG 2) P5S 3) RDA 4) SDB 5) SDA 6) RDB 7) SG 8)P5S 8) to 1) NOTICE Pins No. 2 and 8 (P5S) provide power to the operation panel. Do not use them when making RS-485 communication. 3.4.2 Using the cable to connect the parameter unit Use the optional "FR-CB2 parameter unit connection cable" or commercially available connector and cable for wiring.
3. WIRING Parts used (Use commercially available parts for wiring) Connector Cable RJ45 connector Example: 5-554720-3, Tyco Electronics Corporation Cable conforming to EIA568 (such as 10BASE-T cable) Example: SGLPEV 0.5mm × 4P (Twisted pair cable, 4 pairs), Mitsubishi Cable Industries, Ltd. (Do not use the No. 2 and 8 pins (P5S).) 2) For RS-232C communication operation Computer RS-232C connector RS-232C cable RS-485 terminal Max. 15m Station No. 1 Station No. 2 Station No.
3. WIRING 3.4.4 Wiring methods for communication operation 1) Wiring of one computer and one drive unit for RS-485 Computer Side Terminals Signal name Description RDA Receive data RDB Receive data SDA Send data SDB Send data RSA Request to send Request to send RSB Clear to send CSA CSB Clear to send SG Signal ground FG Frame ground Drive unit Cable connection and signal direction PU connector 10 BASE-T cable SDA SDB RDA RDB *1 0.
4. HOW TO USE THE FR-PU04 PARAMETER UNIT 4. HOW TO USE THE FR-PU04 PARAMETER UNIT For the way to use the FR-PU04 parameter unit, refer to the instruction manual of the FR-PU04 parameter unit. When the FR-PU04 parameter unit (option) is used, some of the FR-PU04 functions are unavailable. (1) Data may be displayed in Japanese only. It cannot be changed to any other language. (2) The parameter names (katakana characters) do not appear. (Except Pr. 900, Pr.902, Pr.
5. OPERATION 5. OPERATION 5.1 Power On CAUTION If the machine should become out of control, perform test operation after ensuring safety. Start operation after performing test operation under light load at low speed to ensure that operation is performed safely. Check that the machine has no damage. Securely set the parameter values to match the operating machine system environment. Switch power on after making sure that the unit has been installed and wired properly and that the start signal is OFF.
5. OPERATION 5.3 Starting operation The drive unit detects the magnetic pole of the motor at every start. The magnetic pole detection time is approx. 0.1s (85ms±15ms) after the start signal and speed signal are input. During this period, the motor remains stopped and starts running after magnetic pole detection is finished. When inputting the speed command from the parameter unit or as a contact signal ON Start signal Speed command Motor speed RUN signal Approx. 0.
6. TROUBLESHOOTING 6. TROUBLESHOOTING This chapter describes how to remedy a fault which occurred in your drive unit or motor and the maintenance and inspection of the drive unit. NOTICE If you have found any fault, immediately perform inspection and take action to remove its cause. If you cannot identify the cause and resolve the malfunction, contact your sales representative. WARNING At occurrence of an alarm, turn off the operation signal before resetting the alarm.
6. TROUBLESHOOTING Table 6-1 Parameter Unit Display Protective Function Name Detection Level Acceleration-time overcurrent Output current is more than 200% of motor rating. Constant speedtime overcurrent Output current is more than 200% of motor rating. Deceleration-time overcurrent Output current is more than 200% of motor rating. Acceleration-time overvoltage Main circuit DC voltage is more than 400V. Constant speedtime overvoltage Main circuit DC voltage is more than 400V.
6. TROUBLESHOOTING Table 6-1 (Continued) Parameter Unit Display Protective Function Name Detection Level Possible Cause ( ) and Corrective Action (•) The motor and drive unit are operated under overload. • Reduce the load. • Increase the capacities of the motor and drive unit. An instantaneous voltage drop in the AC input power supply from the starting of a large capacity equipment, for example. NOTICE Do not switch the AC input power off while the motor is running at high speed.
6. TROUBLESHOOTING If any of the messages in Table 6-2 appears, the drive unit is assumed to have failed. If the same message reappears after an alarm reset, immediately replace the drive unit. Table 6-2 Parameter Unit Display Protective Function Name CPU fault Storage device fault Brake circuit fault Possible Cause ( ) and Corrective Action (•) The CPU malfunctioned or failed. The storage device failed. The regenerative brake circuit failed. • If E.
6. TROUBLESHOOTING 6.1.3 Others Table 6-4 Parameter Unit Display Possible Cause ( ) and Corrective Action (•) Name Parameter changing operation was performed during external operation. The value that was set is outside the parameter setting range. Operation error The RES signal remains ON. The parameter unit is in a connection fault. • Check the fitting status. MEMO An operation error does not activate the relay contact output.
6. TROUBLESHOOTING 6.2 Motor operation out of ordinary If any of the following faults has occurred in the motor, find out its cause and take adequate measures. Event Check Point Check the main circuit. Check the control signals. Motor remains stopped. Check the parameter settings. Check the load. Others Check the main Motor rotates in circuit. opposite direction. Check the control signals. Check the control signals. Speed differs from the setting. Check the parameter settings.
6. TROUBLESHOOTING 6.3 Maintenance and Inspection WARNING When performing inspection by removing the front cover or the like, switch power off, wait 10 or more minutes, then check that the voltage across the DC terminals P/+-N/- is less than 30VDC with a tester or like before starting inspection. Not doing so can cause an electric shock. Any person who is involved in inspection should be fully competent to do the work. Otherwise, an electric shock can occur. Do not disassemble or repair the unit. 6.3.
6. TROUBLESHOOTING Table 6-5 Periodic Inspection List Area of Inspection Inspection Items Methods Cooling system Control circuit Main circuit 1) Check ambient temperature, humidity, vibration, ambience (for dust, dirt, gas, oil mist, Surrounding water drops, etc.) environment 2) Check for tools, foreign matter and dangerous articles in the periphery. Check for unusual vibration and Overall unit unusual noise. 1) Check for loose screws and bolts.
6. TROUBLESHOOTING Insulation resistance test using megger Where possible, do not conduct an insulation resistance test using a megger since an insulation test has been done before shipment from the factory. When it is inevitable to make an insulation resistance test using a megger, disconnect all cables from the control circuit to prevent a test voltage from leaking into the control circuit. The drive unit will fail if the test voltage is applied to the control circuit.
6. TROUBLESHOOTING 6.3.3 Cooling fan replacement method Removal 1) Remove the wiring cover. 2) Unplug the fan connector. The cooling fan is connected with the cooling fan connector on the drive unit terminal block side. Unplug the connector and remove the drive unit and cooling fan. 3) Remove the cooling fan cover. Push the cover in the direction of arrows and pull it down. 4) Remove the cooling fan and cooling fan cover. The cooling fan is secured by latches.
7. SPECIFICATIONS 7. SPECIFICATIONS 7.1 Standard Specifications 7.1.1 Rating specifications Power supply Output MD-CX522Applicable motor capacity (kW) Overload capacity Regenerative braking torque (Note 1) Rated input AC voltage Permissible AC voltage fluctuation Permissible frequency fluctuation Power supply system capacity (kVA) Protective structure Cooling system Approx. weight (kg) 0.4K 0.4 0.75K 1.5K 2.2K 3.7K 0.75 1.5 2.2 3.
7. SPECIFICATIONS 7.1.2 Common specifications (1) Control specifications Control system Carrier frequency Max. output speed Speed setting Analog input resolution Digital input Speed output resolution Analog input Speed accuracy Digital input Starting torque Speed control range Initial magnetic pole detection time Acceleration/deceleration time setting range Stall prevention operation level Sensor-less PWM control 7.5kHz fixed 7200r/min (output frequency 240Hz) 1/1000 of the max.
7.
7. SPECIFICATIONS 7.1.3 Outline drawings CX522-0.4K, 0.75K 5 6 56 68 5 118 128 5 5 hole 4 11 6 55 D D1 Drive Unit Type Wiring holes D D1 0.4K 108 42 0.75K 128 62 (Unit: mm) 5 CX522-1.5K, 2.
7. SPECIFICATIONS CX522-3.7K 118 128 5 2-5 hole 6 5 5 82.5 55.5 68 114.5 11 19.5 55 72 5 138 6 158 170 Wiring holes Cooling fan 1 (Unit: mm) Parameter unit (FR-PU04) 16.5 24 13 80 125 11.75 40 1.5 5- 4 hole 13 1.5 17 5-M3 threads Effective depth 4.5 81.5 48 20 10.5 14.5 18.5 15 21.5 72 23.75 1.25 7 40 (Unit: mm) Select the mounting screws so that their length will not exceed the mounting threads' effective depth.
8 PARAMETER FUNCTIONS 8. PARAMETER FUNCTIONS Refer to Appendix 1 for the parameter list. MEMO The minimum increment of the setting is 0.1 in the setting range 0.0 to 60.0, or 1 in the range 0 to 60. The value having a 0 on the right of the decimal point can be entered as an integer. (Example: 10.0 10) If any parameter cannot be set, check that: • The start signal (STF or STR) is not "ON". • The parameter write disable selection (Pr. 77) setting has not been made.
8 PARAMETER FUNCTIONS 8.2 Parameter Unit Operation Selection Pr. 75 "disconnected PU detection/PU stop selection" Disconnected PU detection function You can make selection between continued operation or an alarm stop " indication) when the FR-PU04 parameter unit has come off (" the drive unit during operation. MEMO This function is invalid if power is switched on with the FR-PU04 parameter unit removed.
8 PARAMETER FUNCTIONS 8.3 Selection of the Speed Command 8.3.1 Selection of the analog speed command specifications Pr. 73 "speed command range selection" You can select the value of the voltage signal entered to terminal 2. Setting Terminal 2 Input Voltage 0 0 to 10V 1 0 to 5V Pr. 74 "filter time constant" You can set the filter time constants of the speed command input terminals (terminals 2).
8 PARAMETER FUNCTIONS 8.3.2 Variable-speed operation using contact input signals Pr. 4 "three-speed setting (high speed)" Pr. 5 "three-speed setting (middle speed)" Pr. 6 "three-speed setting (low speed)" Pr. 24 to 27 "multi-speed setting (speed 4 to 7)" Pr. 4 to 6 24 to 27 Setting Range 0 to 7200 0 to 7200 9999 Unit r/min Combining "ON"/"OFF" of the contact signals allows you to choose the preset running speed (any of up to seven different speeds).
8 PARAMETER FUNCTIONS 8.4 Selection of the Control Circuit Contact Input Terminal Functions Pr. 188 "RES terminal operation selection" Select the reset operation of the RES terminal. Reset operation is performed when RES-SD are shorted more than 0.1s. Setting Name 0 CPU reset 1 CPU reset at alarm MEMO Pr. 189 Function The cumulative thermal value of the electronic overcurrent protection stored during operation is initialized. The alarm status is canceled.
8 PARAMETER FUNCTIONS 8.5 Setting of the Operation Pattern 8.5.1 Running speed region Pr. 1 "maximum speed" Pr. 2 "minimum speed" Pr. Setting Range 1 0 to 7200 2 0 to 7200 Unit Operation If the speed command entered is more than the maximum r/min speed set in Pr. 1, the running speed is clamped at the maximum speed. If the speed command entered is less than the minimum speed set in Pr. 2, the running speed will not fall below the r/min minimum speed.
8 PARAMETER FUNCTIONS Pr. 31 to 36 "speed command jumps 1A to 3B" Pr. 31 to 36 Setting Range 0 to 7200, 9999 Unit r/min You can set three speed areas where continuous operation will be disabled. You can avoid continuous operation at the speed at which resonance will occur due to the natural frequency of a mechanical system. When the speed command within the setting range is input, continuous operation is performed at the preset speed of value A.
8 PARAMETER FUNCTIONS 8.5.2 Acceleration time and deceleration time Pr. 7 Pr. 8 Pr. 20 "acceleration time" "deceleration time" "acceleration/deceleration reference speed" Pr. Setting Range Unit 7, 8 0.00 to 60.00 s 20 1 to 7200 r/min In Pr. 7, set the time required to increase the speed from a start to the speed set in Pr. 20. In Pr. 8, set the time required to decrease the speed from the speed set in Pr. 20 to a stop. Pr.20 Speed Running speed Coasting Pr.7 MEMO Pr.
8 PARAMETER FUNCTIONS 8.5.3 Selection of regenerative brake unit Pr. 30 "regenerative brake option selection" Pr. 70 "regenerative brake duty" Pr. 30 70 Setting Range 0, 1 0.0 to 15.0 Unit % Set Pr. 30 and Pr. 70 according to the regenerative brake unit used. At the setting of Pr. 30 = 0, the Pr. 70 "regenerative brake duty" value is fixed at 3% and Pr. 70 cannot be read. When Pr. 30 = 1, set the value given in the following table since Pr. 70 setting is enabled.
8 PARAMETER FUNCTIONS 8.5.5 Other settings Pr. 84 "rated motor speed" The rated speed of the motor used with the drive unit is displayed. This parameter is for read-only and its value cannot be changed. Pr. 244 "cooling fan operation selection" When the drive unit has a built-in cooling fan, you can select the operation of the cooling fan. Setting Operation 0 While the drive unit power is on, the cooling fan keeps running. While the motor is operating, the cooling fan keeps running.
8 PARAMETER FUNCTIONS 8.6 Communication operation from the PU connector Pr. 117 Pr. 118 Pr. 119 Pr. 120 Pr. 121 Pr. 122 Pr. 123 Pr. 124 "station number" "communication speed" "stop bit length/data length" "parity check presence/absence" "number of communication retries" "communication check time interval" "waiting time setting" "CR-LF presence/absence selection" Make settings necessary for performing RS-485 communication operation from the PU connector using a personal computer or similar equipment.
8 PARAMETER FUNCTIONS (1) Communication specifications Communicati on data Conforming standard Number of units connected Communication speed Control protocol Communication method Character system Stop bit length Terminator Parity check Sumcheck Waiting time setting RS-485 Standard conformance 1 : N (max. 32 units) Selected between 19200, 9600 and 4800bps Asynchronous Half-duplex ASCII (7 bits/8 bits) selectable Selectable between 1 bit and 2 bits.
8 PARAMETER FUNCTIONS NOTICE Communication operation is performed in response to the communication request from the personal computer. Therefore, if communication is suspended due to a communication cable break or computer failure during operation, the drive unit cannot detect a fault and stop operation. However, operation is brought to an alarm stop (E. PUE) if the time set as the communication check time interval has elapsed.
8 PARAMETER FUNCTIONS Approximately 12ms plus waiting time after the drive unit has completed receiving the data sent by the computer, the drive unit sends the drive unit returning data to the computer. Set the waiting time in Pr. 123 to match the answerable time of the computer. MEMO The waiting time may also be set using the computer sending data. In this case, set 9999 in Pr. 123.
8 PARAMETER FUNCTIONS The above format assumes that the data code has two characters. The number of characters in the data code changes with the communication data. When using the computer sending data to set the "waiting time", insert the "waiting time" data (one character) in the position next to the instruction code. Set it within the range 0 to 150ms in 10ms increments.
8 PARAMETER FUNCTIONS (5) Explanation of communication data structure 1) Control codes The following table lists the ASCII codes and their definitions of the control code names which are set at the beginning, end and like of the format.
8 PARAMETER FUNCTIONS ii) Setting the operation items Setting Item Start Mode Write Instruction Code HFA Data Codes and Definitions H00: Stop H02: Forward rotation H04: Reverse rotation b7 b0 0 0 0 0 0 0 1 0 Character count 2 (For forward rotation) Speed setting (RAM) Speed setting (E2PROM) Speed Motor current Output voltage HEE H6E H6F H0000 to H1C20: 1r/min increments (hexadecimal) To change the running speed consecutively, write to the drive unit RAM.
8 PARAMETER FUNCTIONS iii) Parameter write and read Parameter write and read require the setting of the extension codes given in Appendix 1 Parameter List (Numerical Order). After setting the extension code, set the instruction code given in Appendix 1 Parameter List (Numerical Order) and perform write or read. This function is performed as set in Pr. 77. Setting Item Instruction Code Mode Data Codes and Definitions Character count H00: Parameter of extension code 0 can be accessed for read/write.
8 PARAMETER FUNCTIONS Set the bias and gains in Pr. 902 to 905 [Section 8.3.1]. Setting Item Bias/gain MEMO Instruction Code Mode Write HEC Read H6C Data Codes and Definitions H00: Bias/gain H01: Any analog A/D value H02: Analog A/D value of terminal Character count 2 Once written, the setting of the HEC instruction code is held, but is cleared to "0" when the drive unit is reset or all clear is performed. Clear the parameters.
8 PARAMETER FUNCTIONS 4) Sumcheck As a sumcheck value, set the lower 1 byte (8 bits) of the sum derived from ASCII data (station number, instruction code, waiting time, data code) except the control code. The communication data is converted into ASCII automatically.
8 PARAMETER FUNCTIONS (6) Program example (Switching the operation mode to communication operation) Initial setting of input file : Communication file opening : Circuit control signal (RS (ON in data-receivable status), ER (unit ready signal)) ON/OFF setting : Interrupt definition at data receive : Interrupt enable Transmission data setting 10 OPEN "COM1 : 9600,E,8,2,HD" AS #1 20 COMST1,1,1:COMST1,2,1 30 ON COM(1)GOSUB REC 40 COM(1)ON 50 D$= "01FB10002" 60 S=0 70 FOR I=1 TO LEN(D$) 80 A$=MID$(D$,I,1) Sum
8 PARAMETER FUNCTIONS 8.7 Monitoring of Operation Status 8.7.1 Selection of paremeter unit display data Pr. 37 "speed unit switch-over 1" Change the display unit of the FR-PU04 parameter unit. Setting Range 0 1 to 9998 Function The motor speed is displayed. The unit is r/min. By setting a value corresponding to the rated speed, a machine operation amount equivalent can be displayed.
8 PARAMETER FUNCTIONS 8.7.2 Selection of the control circuit output terminal functions Pr. 190 Pr. 194 "RUN terminal function selection" "FU terminal function selection" You can select/change the functions of the control circuit output terminals. At the initial values, the terminal names and signal names match. Setting Signal Name 0 RUN 3 OL 4 FU 12 Y12 21 UVT 25 FAN 98 LF 99 ABC 9999 Operation "ON" during motor operation, "OFF" during voltage braking operation or stop.
8 PARAMETER FUNCTIONS Once the motor speed has reached or exceeded the speed set in the corresponding parameter, it is exported from the control circuit output terminals where the FU signal has been assigned. Pr. 43 is valid for only the operation performed using the reverse rotation signal (terminal STR or REV key). Setting the Pr. 43 value makes the Pr.
8 PARAMETER FUNCTIONS 8.7.5 Selection of the instrument connection terminal functions Pr. 54 "FM terminal function selection" You can select the signals output to the FM terminal designed for instrument connection. Setting 1 2 5 MEMO Display Data Motor speed Motor current Preset speed Unit r/min A r/min Full-Scale Value set in Pr. 55 Value set in Pr. 56 Value set in Pr. 55 The maximum number of pulses of the terminal FM is 2400 pulses/s.
8 PARAMETER FUNCTIONS APPENDIX 1 PARAMETER LIST (NUMERICAL ORDER) No.
8 PARAMETER FUNCTIONS APPENDIX 1 PARAMETER LIST (NUMERICAL ORDER) No.
8 PARAMETER FUNCTIONS APPENDIX 1 PARAMETER LIST (NUMERICAL ORDER) No.
REVISIONS *The manual number is given on the bottom left of the back cover. Print Date *Manual Number Jan.