Table of Contents Physical Characteristics..................................................................... 2 Installation instructions...................................................................... 2 Operating instructions........................................................................ 3 Remote Monitor Closed (Figure 1.0)…............................................. 4 Remote Monitor Closed Hardwired (Figure 1.1)............................... 5 Terminal Block Description (Figure 2.0)..
Physical Characteristics Weight: 10lbs (4.5 kgs.) Height: 81/4 inches (210 mm) Width: 8 5/16 inches (211 mm) Depth: 4 5/16 inches (110 mm) Installation 1. Locate the area where the Remote Status Alarm Panel (RSAP) will be installed. The monitor should be within 300 feet (91 meters) of the UPS. 2. Mount the monitor to the wall using the four pre-drilled holes in the back. Use appropriate hardware for the installation. 3. Wiring requirements are: 7 twisted pair 16 AWG cable run in metal conduit.
Operating Instructions ALARM SILENCE pushbutton is used to silence the alarm. MONITOR RESET pushbutton is used to reset the RSAP’s UPS FAULT alarm. The monitor will alarm again if the alarm condition is still present following the RESET. Monitor TEST pushbutton is used to check the operation of all LED's and the audible alarm. All LED’s that are illuminated will go off and all lights that are off will illuminate. Horn will also sound.
10/13/04 4 93120-MAN07 6' CORD FEMALE MIC PLUG INPUT CONFIGURATION (SEE OPTIONS) INPUT TRANSFORMER 12. INTERNAL MONITOR BATTERY OK (YELLOW LED) 11. ALARM SILENCE (RED LED) 10. BATTERY LOW VOLTAGE (RED LED) 9. INPUT FAILURE (RED LED) 8. OVERLOAD (RED LED) 7. UPS FAULT (RED LED) 6. AC INPUT ON (GREEN LED) 1. RECTIFIER ON (GREEN LED) INTERNAL MONITOR BATTERY TEST ALARM SILENCE MONITOR TEST MONITOR RESET OUTPUT FIGURE 1.
10/13/04 5 93120-MAN07 12. INTERNAL MONITOR BATTERY OK (YELLOW LED) 11. ALARM SILENCE (RED LED) 10. BATTERY LOW VOLTAGE (RED LED) 9. INPUT FAILURE (RED LED) 8. OVERLOAD (RED LED) 7. UPS FAULT (RED LED) 6. AC INPUT ON (GREEN LED) 1. RECTIFIER ON (GREEN LED) INTERNAL MONITOR BATTERY TEST INTERNAL MONITOR BATTERY OK (INTERNAL POWER SUPPLY / HARDWIRE OPTION) FIGURE 1.
TB1 1 -AC INPUT L1 (OPTION) 2 -AC INPUT L1 (OPTION) 3 -BYPASS (CLOSES WHEN ON BYPASS) 4 -BYPASS COMMON 5 -INVERTER (CLOSES WHEN INVERTER IS RUNNING) 6 -INVERTER COMMON 7 -ON BATTERIES (CLOSES WHEN ON BATTERIES) 8 -BATTERY COMMON 9 -RECTIFIER (CLOSES WHEN RECTIFIER IS RUNNING) 10 -RECTIFIER COMMON 11 -UPS FAILURE (CLOSES ON UPS FAILURE) 12 -UPS COMMON 13 -LOW BATTERY (CLOSES WHEN BATTERIES ARE LOW) 14 -LOW BATTERY COMMON 15 -OVERLOAD (CLOSES WHEN IN OVERLOAD) 16 -OVERLOAD COMMO
1 -AC LINE INPUT L1 2 -AC NEUTRAL INPUT 3 -GROUND 4 -NOT USED 5 -BYPASS 6 -BYPASS COMMON 7 -INVERTER (CLOSES WHEN INVERTER IS RUNNING) 8 -INVERTER COMMON 9 -ON BATTERIES (CLOSES WHEN ON BATTERIES) 10 -BATTERY COMMON 11 -RECTIFIER (CLOSES WHEN RECTIFIER IS RUNNING) 12 -RECTIFIER COMMON 13 -UPS FAILURE (CLOSES ON UPS FAILURE) 14 -UPS COMMON 15 -LOW BATTERY (CLOSES WHEN BATTERIES ARE LOW) 16 -LOW BATTERY COMMON 17 -OVERLOAD (CLOSES WHEN IN OVERLOAD) 18 -OVERLOAD COMMON TERMI
10/13/04 8 93120-MAN07 INPUT TRANSFORMER (12 VOLT DC OUTPUT) BATTERY ARRANGEMENT INPUT PLUG BATTERY HOLDER CIRCUIT BOARD FIGURE 3.0 LABELS 16 OVERLOAD COMMON 15 OVERLOAD 14 LOW BATTERY COMMON 13 LOW BATTERY 12 UPS COMMON 11 UPS FAILURE 10 RECTIFIER COMMON 9 RECTIFIER 8 BATTERY COMMON 7 ON BATTERIES 6 INVERTER COMMON 5 INVERTER 4 BYPASS COMMON 3 BYPASS 2 AC INPUT L1 (OPTION) 1 AC INPUT L1 (OPTION) TERMINAL BLOCK 6" .
/13/04 9 93120-MAN07 TERMINAL BLOCKS FIGURE 3.1 LABELS 18 OVERLOAD COMMON 17 OVERLOAD 16 LOW BATTERY COMMON 15 LOW BATTERY 14 UPS COMMON 13 UPS FAILURE 12 RECTIFIER COMMON 11 RECTIFIER 10 BATTERY COMMON 9 ON BATTERIES 8 INVERTER COMMON 7 INVERTER 6 BYPASS COMMON 5 BYPASS 4 NOT USED 3 GROUND (INTERNAL POWER SUPPLY / HARDWIRE OPTION) BATTERY ARRANGEMENT BATTERY HOLDER CIRCUIT BOARD 2 AC NEUTRAL INPUT 1 AC LINE INPUT L1 6" .
10/13/04 10 93120-MAN07 INTERNAL MONITOR BATTERY TEST INTERNAL MONITOR BATTERY OK FRONT VIEW ALARM SILENCE MONITOR TEST MONITOR RESET OUTPUT ALARM SILENCE BATTERY LOW VOLTAGE INPUT FAILURE OVERLOAD UPS FAULT BYPASS INPUT TOP VIEW 1.50" FIGURE 4 4.00" 1.50" 1.00" KNOCKOUT FOR 1/2" EMT CONDUIT TYP. TOP AND BOTTOM. 1.50" REAR VIEW KNOCKOUT FOR 1/2" EMT CONDUIT Ø 0.312 MOUNT HOLES 6.00" 1.00" 6.