FDU-H CONTENTS 15.1 GENERAL INFORMATION ...................................................................... 581 15.1.1 Specific features ................................................................................ 581 15.1.2 How to read the model name............................................................ 581 15.2 SELECTION DATA ................................................................................... 582 15.2.1 Specifications ...........................................................
FDU-H 15.1 GENERAL INFORMATION 15.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in the indoor unit.
FDU-H 15.2 SELECTION DATA 15.2.1 Specifications Model FDU308HEN-SA FDU308HEN-SA Model Item FDU308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC308HEN3 7100 8000 Power source Cooling input Operation data(3) Running current (Cooling) Power factor (Cooling) 1 Phase, 220/240V, 50Hz kW 3.20/3.40 A 14.8/15.4 % 98/92 kW 3.06/3.22 Running current (Heating) A 14.2/14.7 Power factor (Heating) % 98/91 Inrush current (L.R.
FDU-H Model FDU308HES-SA FDU308HES-SA Model Item FDU308-A Nominal cooling capacity(1) Nominal heating capacity(1) Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Inrush current (L.R.
FDU-H Model FDU408HES-SA FDU408HES-SA Model Item FDU408-A Nominal cooling capacity(1) Nominal heating capacity(1) Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Inrush current (L.R.
FDU-H Model FDU508HES-SA FDU508HES-SA Model Item FDU508-A Nominal cooling capacity(1) Nominal heating capacity(1) Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Inrush current (L.R.
FDU-H Model FDU808HES-SA FDU808HES-SA Model Item FDU808-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC808HES3 20000 21200 Power source Cooling input Operation data(3) Running current (Cooling) Power factor (Cooling) 3 Phase, 380/415V 50Hz kW 9.1/9.2 A 16.2/15.5 % 85/83 kW 7.1/7.3 Running current (Heating) A 13.6/13.2 Power factor (Heating) % 79/77 Inrush current (L.R.
FDU-H Model FDU1008HES-SA FDU1008HES-SA Model Item FDU1008-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC1008HES3 25000 28000 Power source Operation data(3) Cooling input Running current (Cooling) Power factor (Cooling) 3 Phase, 380/415V 50Hz kW 12.8/12.9 A 22.7/21.7 % 86/83 kW 10.6/10.8 Running current (Heating) A 19.2/18.7 Power factor (Heating) % 84/80 Inrush current (L.R.
FDU-H Model FDU308HEN-A FDU308HEN-A Model Item FDU308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC306HEN3 7100 7300 Power source Cooling input Operation data(3) Running current (Cooling) Power factor (Cooling) 1 Phase, 220/240V, 50Hz kW 3.29/3.33 A 16.5/17.3 % 91/80 kW 3.04/3.08 Running current (Heating) A 15.4/16.2 Power factor (Heating) % 90/79 Inrush current (L.R.
FDU-H Model FDU308HES-A FDU308HES-A Model Item FDU308-A Nominal cooling capacity(1) (1) FDC306HES3 7100/7700 6000 7300/7900 3 Phase, 380-415V 50Hz, 380V 60Hz 3.05/3.06/3.64 5.9/6.0/7.1 79/71/78 2.72/2.74/3.19 5.5/5.7/6.7 75/67/72 3.87 7.
FDU-H Model FDU408HES-A FDU408HES-A Model Item FDU408-A Nominal cooling capacity(1) (1) FDC406HES3 10200/11300 9900 10500/11600 3 Phase, 380-415V 50Hz, 380V 60Hz 3.96/3.96/4.88 7.8/7.8/9.4 77/71/79 3.66/3.66/4.51 7.5/7.5/9.1 74/68/75 5.38 10.
FDU-H Model FDU508HES-A FDU508HES-A Model Item FDU508-A Nominal cooling capacity(1) (1) FDC506HES3 12500/14000 11900 12800/14400 3 Phase, 380-415V 50Hz, 380V 60Hz 5.01/5.03/6.03 10.3/10.3/11.5 74/68/80 4.63/4.67/5.61 9.5/9.6/10.7 74/68/80 6.63 12.
FDU-H Model FDU508HEM-A FDU508HEM-A Model Item FDU508-A Nominal cooling capacity(1) (1) ISO-T1 ISO-T3 Operation data(3) Nominal heating capacity Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Cooling input Running current (Cooling) Power factor (Cooling) Inrush current (L.R.
FDU-H 15.2.2 Range of usage & limitations Models FDU308~1008, (FDC308~1008 type) Models Item FDU308~1008(FDC308~1008 type) Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Indoor unit atmosphere (behind ceiling) temperature and humidity Dew point temperature: 28˚C or less, relative humidity: 80% or less Max. 50m Refrigerant line (one way) length Max.
FDU-H 15.2.3 Exterior dimensions (1) Indoor unit Models FDU308-A, 408-A Unit : mm 138 138 Return air duct (M5 × 12 pcs.) 60 250 13 Holes for screws 65 820 13 400 188 750 (Duct for dimension) 35 VIEW A 95 92 106 25 60 35 13 200 188 Control box Liquid piping Gas piping ø9.52 (3/8") 308 type : ø15.88 (5/8") 408 type : ø19.05 (3/4") Suspension bolts (M10 × 4 pcs.) Hole for wiring Supply air (M5 × 12 pcs.
FDU-H Model FDU508-A Unit : mm Holes for screws Return air duct 138 (M5 × 16 pcs.) 138 13 13 13 200 163 4 × 200 = 800 163 50 1100 (Duct for dimension) 50 110 94 65 1200 250 13 18 (Duct for dimension) 60 794 (Suspension bolts pitch) 18 1270 (Suspension bolts pitch) 1320 25 830 ø9.52 (3/8") ø19.05 (3/4") 250 (Duct for dimension) Control box Gas piping 60 Liquid piping 95 25 VIEW A Suspension bolts (M10 × 4 pcs.) 510 Supply air Hole for screws 25 (M5 × 12 pcs.
FDU-H Models FDU808-A, 1008-A Unit : mm 60 138 Holes for screw (M5 × 20 pcs.) 163 35 60 35 95 13 200 6 × 200 = 1200 1500 (Duct for dimension) 163 25 Return air duct 13 138 13 13 65 80 100 1570 250 (Duct for dimension) 18 1640 (Suspension bolts pitch) 1690 25 830 794 (Suspension bolts pitch) 18 Liquid piping Gas piping 808: ø12.7 (1/2") 1008: ø15.88 (5/8") 808: ø25.4 (1") 1008: ø28.
FDU-H (2) Remote controller (Optional parts) Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 120 60 46 47 17 7 120 89 83.
FDU-H (3) Outdoor unit Models FDC308HEN3, 308HES3 Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) 110 195 50 50 10 195 460 110 845 Gas piping: ø15.
FDU-H Models FDC408HES3, 508HES3 Unit: mm Liquid piping: ø 9.52 (3/8") (Flare connecting) 46 100 48 50 Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 (1050) Gas piping: ø 19.
FDU-H Unit: mm Models FDC808HES3, 1008HES3 600 50 1350 1450 Opening for exit wiring (ø50) ( ) Power supply connecting terminal block 170 105 119 105 20 291.5 Opening for exit piping (ø88) 80 A Connect of liquid piping 808: ø12.7 (1/2") 1008: ø15.58 (5/8") 80 Connect of gas piping 170 ø25.4 (1") ( 1008:808:ø28.
FDU-H Models FDC306HEN3, 306HES3 580 380 Unit: mm Anchor bolts (M10 × 4 pcs) Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type 1 2 L1 Open Open 500 L2 300 0 Open L3 100 150 100 Mark 3 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space over the unit must be larger than 1 m. (4) The unit should not be surrounded by obstructions in all direction.
FDU-H Models FDC406HES3, 506HES3, 506HEM3 Unit: mm 380 580 Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type 1 2 3 L1 Open Open 500 L2 300 0 Open L3 150 300 150 Mark 602 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space over the unit must be larger than 1 m. (4) The unit should not be surrounded by obstructions in all direction.
FDU-H 15.2.4 Exterior appearance (1) Indoor unit ......
FDU-H 15.2.5 Piping system Models FDU308HEN-SA, 308HES-SA, 408HES-SA Cooling cycle Heating cycle Indoor unit Outdoor unit High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Gas line Strainer Service valve (Flare connecting) 308:ø15.88 ( 408:ø19.
FDU-H Models FDU808HES-SA, 1008HES-SA Cooling cycle Indoor unit Outdoor unit Heating cycle Service valve High pressure switch(63H2) (Brazing) (For fan motor control) Thermistor (ThO-A) Brazing Strainer Gsa line 808 : ø25.4 1008 : ø28.58 ( ) 4way valve High pressure switch(63H1) Thermistor (ThI-A) Lower Heat exchanger Upper (For protection) Muffler Heat exchanger Thermistor (ThI-R) Muffler Compressor Accumlator Capillary tube Liquid line 808 : ø12.7 1008 : ø15.
FDU-H Models FDU408HES-A, 508HES-A, 508HEM-A Cooling cycle Heating cycle Service valve (Flare connecting) Indoor unit Check joint Strainer Gas line (ø19.05) Outdoor unit High pressure switch (For fan motor control) Strainer 4way valve Check joint Thermistor (ThI-A) Heat exchanger Accumlator Heat exchanger Check joint Thermistor (ThI-R) Defrost Thermostat (23DH) Compressor High Pressure regulator valve Capillary tube Liquid line (ø9.
FDU-H 15.2.6 Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling and heating capacity in relation to temperatures Only case of ISO-T1 models (Only case of FDC308~1008 type) Cooling operation Outdoor air D.B. temperature (˚CD.B.) Heating operation Indoor air D.B.
FDU-H Cooling operation Heating operation Indoor air D.B. temperature (˚CD.B.) Outdoor air D.B. temperature (˚CD.B.) Coefficient of cooling and heating capacity in relation to temperatures (C) Only case of ISO-T3 and SASO models Indoor air W.B. temperature (˚CW.B.) ISO-T1 Standard condition ISO-T1 Standard condition Outdoor air W.B. temperature (˚CW.B.
FDU-H (3) Correction of cooling and heating capacity in relation to one way length of refrigerant piping It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor and outdoor units.
FDU-H 15.2.7 Characteristics of fan How to interpret the blower characteristics table Example ¡What is the Fan Controller’s Volume Number setting if, at the high operation speed of FDU308-A (60Hz), it is required to have 140Pa (14mmAq) outside static pressure at 24m3/min airflow volume as the operation point? Move the 140Pa (14mmAq) outside static pressure point to the right as shown in the diagram below. The “ a -point”, i.e.
FDU-H Model FDU408-A (50Hz) High Low 200 (20) Model FDU408-A (60Hz) • Condition of standard rating (Air flow : 100 (10) Pa (mmAq) 200 (20) High Low • Condition of standard rating (Air flow : 100 (10) Pa (mmAq) 8 8 7 5 Example of duct 4 6 150 (15) Outside static pressure Pa (mmAq) 150 (15) Outside static pressure Pa (mmAq) 7 6 3 2 100 (10) 5 8 100 (10) 7 6 5 50 (5) 50 (5) 2 3 4 5 8 6 7 0 (0) 0 (0) 20 27 25 30 Standard Lower limit 34 24 Upper limit Lower limit High Low
FDU-H Model FDU808-A High Low • Condition of standard rating (Rated air volume : 100 (10) Pa (mmAq) 200(20) 8 7 Example of duct 6 5 4 Static pressure Pa(mmAq) 150(15) 100(10) 8 3 7 2 2 6 3 50(5) 5 4 0(0) 38 40 45 55 56 50 Lower limit 60 65 Upper limit Standard Air flow (m3/min) Model FDU1008-A High Low • Condition of standard rating (Rated air volume : 100 (10) Pa (mmAq) 200(20) 8 7 6 8 7 5 4 3 6 2 Example of duct 5 150(15) 4 Static pressure Pa(mmAq) 3 100(10) 2 50(5) 0
FDU-H 15.2.8 Noise level Notes (1) The data are based on the following conditions. Ambient air temperature: Indoor unit 27°C DB, 19°C WB Outdoor unit 35°C DB, Indoor unit Measured based on JIS B 8616 Mike position as below Outdoor unit Only case of FDC 308~508 and FDC 306~506 type. Measured based on JIS B 8616 Mike position: at highest noise level in position as below Distance from front side 1m Height 1m Only case of FDC 808, 1008 type. Mike position: Front height is 1 meter. Unit 1.
FDU-H (2) Outdoor unit Models FDC308HEN3, 308HES3 Noise level 52 dB (A) 70 70 50 N50 40 40 N40 30 30 500 50 N50 40 40 N40 30 30 1000 2000 4000 20 63 125 Mid octave band frequency (Hz) Noise level 54 dB (A) 50 50 N50 40 40 N40 30 30 2000 4000 50 40 40 N40 30 30 63 60 50 50 N50 40 40 N40 30 30 N30 1000 2000 4000 614 2000 125 250 500 60 N60 50 50 N50 40 40 N40 30 30 N30 1000 2000 4000 N30 N2 0 20 20 8000 63 125 250 500 1000 2000 20 8000 Nois
BL Y/GN S WH X05 X08 X04 X07 X06 X03 CT1 R WH WH 3 28 2 H L UH X02 X03 X04 Mark CC CFI CFO CH CM CN CnA ~ W CT1 F FC FMI FMO NF NR PC SV1,2 SW1 SW3 TB FS Thc ThI-A 17 X01 19 X06 20 A2 18 A1 52C Parts name Capacitor for CM Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Current sensor Fuse Fan controler Fan motor (Indoor unit) Fan motor (Outdoor unit) Noise filter Surge suppressor Photo coupler Solenoid coil (for control) Switch (Ad
CT1 Y/GN 4 V X08 X07 X06 X03 BL 2 1 3 28 RD/WH Mark CFI CFO1 CH CM CN CnA ~ Z CT1,2 F FC FMI FMO1 FS NF NR PC SV1,2 SW1 SW3 TB Thc ThI-A (49FO1) FMO1 H L UH X02 X03 X04 CF01 X05 16 12 13 20S 17 BK X01 Parts name Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Current sensor Fuse Fan controler Fan motor (Indoor unit) Fan motor (Outdoor unit) Float switch Noise fulter Surge suppressor Photo coupler Solenoid coil (for control) Switch (
CT1 Y/GN RD X05 X08 X04 X07 BL X06 X03 CT2 W BL 2 1 3 28 RD/WH H L UH (49FO1) FMO1 X02 X03 X04 Mark CFI CFO1,2 CH CM CN CnA ~ Z CT1,2 F FC FMI FMO1,2 FS NF NR PC SV1,2 SW1 SW3 TB Thc ThI-A CF01 12 13 H L UH (49FO2) FMO2 BK CF02 X05 17 16 20S 14 15 Parts name Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Current sensor Fuse Fan controler Fan motor (Indoor unit) Fan motor (Outdoor unit) Float switch Noise filter Surge suppre
RD V X03 BL BK/WH 1 2 3 28 H L (49FO1) FMO1 X02 X03 X04 CF01 12 13 Mark CFI1,2 CFO1,2 CH CM CnA ~ Z CT1,2 F FMI1,2 FMO1,2 FC FS NF PC SW1 SW3 TB Thc ThI-A ThI-R H (49FO2) FMO2 CF02 X05 17 16 14 15 20S Parts name Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Connector ( mark) Corrent sensor Fuse Fan motor (Indoor unit) Fan motor (Outdoor unit) Fan controller Float switch Noise filter Photo coupler Switch (Address set) Changeover switch Terminal block ( mark) The
WH (49C) CM S 6 5 R BK 52C OR CnM FM0 (49F0) OR CnM OR OR CnM Mark CC CFI CFO CH CM CN CnA ~ W F Fc FMI FMO FS NF NR PC SW1 SW3 TB Thc CFO CnP CH CnP 52C BK BK 3 BK 63H2 RD Parts name Capacitor for CM Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Fuse Fan controller Fan motor (Indoor unit) Fan motor (Outdoor unit) Float switch Noise filter Surge suppressor Photo coupler Switch (Address set) Changeover switch Terminal block ( mar
N L3 WH BL RD BK 52C NR T1 CM T3 (49C) T2 6 5 4 3 2 1 BL RD L2 WH BL RD OR OR CnM OR OR CnM (49FO) FMO CnM BK WH Mark CFI CFO CH CM CN CnA ~ W F Fc FMI FMO FS NF NR PC SW1 SW3 TB Thc CFO CnP CH CnP 52C BK BK 63H2 3 BK Parts name Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Fuse Fan controller Fan motor (Indoor unit) Fan motor (Outdoor unit) Float switch Noise filter Surge suppressor Photo coupler Switch (Address s
N L3 WH BL RD 52C NR T2 T1 CM T3 (49C) 6 5 4 3 2 1 BL RD OR Mark CFI CFO1, 2 CH CM CN CnA ~ W F Fc FMI FMO1, 2 FS NF NR PC SW1 SW3 TB Thc CFOI BK CnP OR OR CnM2 OR OR CnM2 (49FO2) FMO2 CnM2 CH CnP 52C BK CFO2 63H2 3 BK 5 Parts name Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Fuse Fan controller Fan motor (Indoor unit) Fan motor (Outdoor unit) Float switch Noise filter Surge suppressor Photo coupler Switch (Address set
T T2 T1 CM T3 (49C) 6 5 4 3 2 1 RD 52C NR FMO1 OR CnM1 (49FO1) Mark CFI CFO1, 2 CH CM CN CnA ~ W F Fc FMI FMO1, 2 FS NF NR PC SW1 SW3 TB Thc BK BK BK CFOI OR CnM2 FMO2 (49FO2) OR CnM2 OR OR CnM2 CnP CH CnP 52C RD BK CFO2 3 BK 63H2 Parts name Capacitor for FMI Capacitor for FMO Crankcase heater Compressor motor Capaciter Connector ( mark) Fuse Fan controller Fan motor (Indoor unit) Fan motor (Outdoor unit) Float switch Noise filter Surge suppressor Photo coupler Switch (A
FDU-H 15.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER Same as the cooling/heating equipment for FDT(N) heat pump type. Refer to page 317. 15.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings.
FDU-H NOTICE All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATION. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to Mitsubishi Heavy Industries, Ltd. through your local distributor. WARNING BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION.
FDU-H (3) Duct work 1 Air filter is not installed in the main unit of air conditioner. Air filter should be installed in the suction grill 3A 3 Canvas coupling 3 Canvas coupling which allows an ample access for cleaning. 2 Silencer chamber(s) may be necessary depending on the OA noise level allowed in the room where the air conditioner is installed. Ceiling surface Air conditioner main unit. Additional silencer may be necessary where a particu5 Blow outlet Suction hole larly low noise is required.
FDU-H (d) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30 (11/4˝) or thicker pipe this purpose. (e) Be sure to provide heat insulation to hard PVC pipes of indoor placement. (f) Do not ever provide an air vent. (g) Avoid postitioning the drain piping outlet at a place where generation of odor may be stimulated. Do not lead the drain piping direct into a sewer from where sulfur gas may generate.