Specifications
-
14
-
Model FDTVA251HEN1R
Model
Item
FDTVA251HEN1R
FDTA251R FDCVA251HENR
Nominal cooling capacity
(1)
kW
5.6 [2.8~6.3]
Nominal heating capacity
(1)
kW
6.7 [3.1~7.1]
Power source 1 Phase, 220-240V 50Hz/220V 60Hz
Operation data
(3)
Cooling power consumption kW
1.64/1.65
Running current (Cooling) A
7.3/7.6
Power factor (Cooling) %
98/99
Heating power consumption kW
1.78/1.79
Running current (Heating) A
7.9/8.4
Power factor (Heating) %
98/97
Inrush current (L.R.A) A
5
Noise level dB(A)
Powerful mode Hi:38 Me:35 Lo:33
Mild mode Hi:35 Me:33 Lo:31
48
Exterior dimensions
Height × Width × Depth
mm
Unit 270 × 840 × 840
Panel 35 × 950 × 950
595 × 780 (+67) × 290
Net weight kg 31 (Unit:24 Panel:7) 40
Refrigerant equipment
Compressor type & Q’ty
–
5CS102XFD × 1
Starting method – Direct line start
Heat exchanger
Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control – Electronic expansion valve
Refrigerant R410A
Quantity kg –
1.75 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.48 (RB68A)
Defrost control Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan × 1 Propeller fan × 1
Motor W 20 × 134 × 1
Starting method Direct line start Direct line start
Air fl ow CMM
Powerful mode Hi:20 Me:17 Lo:15
Mild mode Hi:17 Me:15 Lo:13
41
Outside air intake
Available –
Air filter, Q’ty Plastic net (washable) × 1 –
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber mount (for compressor)
Electric heater W – 20 (Crank case heater)
Operation control
Operation switch
Wired remote control switch (Optional : RC-E1R)
Wireless kit (Optional : RCN-T-35W-ER)
– (Indoor unit side)
Room temperature control Thermostat by electronics –
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Connecting method Flare piping
Drain hose
Connectable with VP25 (I.D. 25mm, O.D. 32mm) –
Insulation for piping Necessary (both Liquid & Gas lines)
Accessories Mounting kit. Drain hose
Optional parts Decorative Panel (T-PSA-35W-ER)
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO-T1
Heating 20˚C – 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.