Specifications
-
21
-
Model FDTVA602HES2R
Model
Item
FDTVA602HES2R
FDTA601R FDCVA602HESAR
Nominal cooling capacity
(1)
kW
14.0 [6.7~14.8]
Nominal heating capacity
(1)
kW
16.0 [6.3~16.8]
Power source 3 Phase, 380-415V 50Hz/380V 60Hz
Operation data
(3)
Cooling power consumption kW
4.65/4.65
Running current (Cooling) A
6.8/7.3
Power factor (Cooling) %
99/97
Heating power consumption kW
4.54/4.54
Running current (Heating) A
6.7/7.4
Power factor (Heating) %
98/93
Inrush current (L.R.A) A
5
Noise level dB(A)
Powerful mode Hi:48 Me:45 Lo:43
Mild mode Hi:45 Me:43 Lo:40
53
Exterior dimensions
Height × Width × Depth
mm
Unit 365 × 840 × 840
Panel 35 × 950 × 950
845 × 970 × 370
Net weight kg 38 (Unit:31 Panel:7) 74
Refrigerant equipment
Compressor type & Q’ty
–
RM-B5125MDE31 × 1
Starting method – Direct line start
Heat exchanger
Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control – Electronic expansion valve
Refrigerant R410A
Quantity kg –
3.8 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.7 (M-MA68)
Defrost control Microcomputer controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan × 1 Propeller fan × 1
Motor W 120 × 1 120 × 1
Starting method Direct line start Direct line start
Air fl ow CMM
Powerful mode Hi:34 Me:30 Lo:26
Mild mode Hi:30 Me:26 Lo:23
Cooling: 75, Heating: 73
Outside air intake
Available –
Air filter, Q’ty Plastic net (washable) × 1 –
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber mount (for compressor)
Electric heater W – 20 (Crank case heater)
Operation control
Operation switch
Wired remote control switch (Optional : RC-E1R)
Wireless kit (Optional : RCN-T-35W-ER)
– (Indoor unit side)
Room temperature control Thermostat by electronics –
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Installation data
Refrigerant piping size
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Connecting method Flare piping
Drain hose
Connectable with VP25 (I.D. 25mm, O.D. 32mm) –
Insulation for piping Necessary (both Liquid & Gas lines)
Accessories Mounting kit. Drain hose
Optional parts Decorative Panel (T-PSA-35W-ER)
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
ISO-T1
Heating 20˚C – 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.