Specifications

-
47
-
4.3 Drain motor forced operation functions (STM, SRRM only)
(1) Operation
When the float switch detects drain water, please use the wireless remote control to set the operation mode to "heating",
set the temperature to 30°C, and set the timer to continuous operation.
When the float switch detects drain water, press the TEST switch on wired remote control for 3 seconds.
(2) Detail of operation
Sets the decision speed to 0 rps, stops the indoor fan motor, and only lets the drain motor run for 5 minutes. After this operation
finishes, if the float switch detects drain water, it will display an error and stop operation.
(3) Reset condition
(a) When the drain motor has run for 5 minutes.
(b) Use the remote control to set the operation mode to heating, set the temperature to 30°C, and set the timer to something other
than continuous operation.
EXTERNAL INPUT
WIRED REMOCON
OPE PERMISSION
CUSTOM
AUTO RESTART
LO TEMP
DIRT PREVENT
COOL ONLY
HI CEIL
PANEL
50/60
4.4 Power blackout auto restart function
(1) Power blackout auto restart function is that records the operational status of the air-conditioner immediately prior to it being
switched off by a power cut, and then automatically resumes operations at that point after the power has been restored.
(2) The following settings will be cancelled:
(a) Timer settings
(b) High-power operations
Notes (1) Power blackout auto restart function is set at on when the air-conditioner is shipped from the factory. Consult with your dealer if this function needs to
be switched off.
(2) When power failure ocurrs, the timer setting is cancelled. Once power is resumed, reset the timer.
(3) If the jumper wire (J12) “REMOTE/AUTO RESTART” is cut, auto restart is disabled. (SKM 20 ~ 50 model. See the diagram at above)
(4) If the jumper wire (J7) “AUTO RESTART” is cut, auto restart is disabled. (SKM 60 · 71, STM, SRRM model. See the diagram at above)
S SKM20~50 model S SKM60·71, STM, SRRM model
Jumper wire (J12)
Jumper wire (J7)