Specifications
-
66
-
<II>
(a) Operating conditions: When the outdoor air temperature sensor (Th
O-A) is 22°C or lower continues for 30 seconds while
decision speed is other than 0 rps.
(b) Detail of operation:
1 The lower limit of decision speed is set to B (or D) rps and even if the speed becomes lower than B (or D) rps, the
speed is kept to B (or D) rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
2 The upper limit of decision speed is set to A (or C) rps, the speed is kept to A (or C) rps.
(c) Reset conditions: When the either of the following condition is satisfied
1 When the outdoor air temperature sensor (Th
O-A) becomes 24°C or higher.
2 When the decision speed is 0rps.
(9) Cooling low outdoor temperature protective control
<I>
(a) Operating conditions: When the outdoor air temperature sensor (Th
O-A) is 22°C or lower continues for 30 seconds while
decision speed is other than 0 rps.
(b) Detail of operation: The outdoor fan is controlled in accordance with the outdoor heat exchanger temperature.
(c) Reset conditions: When the either of the following conditions is satisfied
1 When the outdoor air temperature sensor (Th
O-A) becomes 24°C or higher.
2 When the decision speed is 0 rps.
Model
A
B
C
D
80 rps
35 rps
64 rps
60 rps
SCM40ZG-S
70 rps
29 rps
64 rps
54 rps
SCM45ZG-S
69 rps
46 rps
64 rps
54 rps
SCM48ZG-S
60 rps
22 rps
50 rps
30 rps
SCM60ZG-S
60 rps
20 rps
50 rps
30 rps
SCM80ZG-S
Values of A ~ D