Specifications

-
89
-
(2) Indication of self diagnosis
Indoor unit
indicator
Outdoor unit
indicator
(LED E)
Wired remote
control display
(optional parts)
Description of
trouble
Cause Conditions of flashing
On for 4 sec-
onds and off
for 4 seconds
Outdoor heat exchang-
er sensor error
Indoor heat exchanger
sensor (1) error
Room temperature
sensor error
Outdoor air tempera-
ture sensor error
Power transistor sensor
error
Discharge pipe sensor
error
Comp. suction sensor
error
Indoor heat exchange
sensor (2) error
Closed service valve
Indoor heat exchanger
sensor (1) error
Indoor fan motor error
Broken discharge pipe sensor wire
Connector poor connection
Broken power transistor sensor wire
Connector poor connection
When heat exchanger sensor (1) temperature of
–20°C or under continued for more than 15
seconds while operation is stopped.
(This is not displayed during operation.)
When room temperature sensor temperature of
–20°C or under continued for more than 15
seconds while operation is stopped.
(This is not displayed during operation.)
When air conditioner is operating and indoor fan
motor is turned ON, indoor fan motor speed of
300 rpm or under continued for more than 30
seconds. (Air conditioner stops.)
After cooling starts, when the temperature
difference at the indoor heat exchanger sensor (1)
after 13 minutes and after 16 minutes is greater
than –2ºC, operation is stopped.
When outdoor air temperature sensor temperature
of –20°C or under continued for more than 10
seconds while operation is stopped.
(This is not displayed during operation.)
When heat exchanger sensor temperature of –20
°C or under continued for more than 10 seconds
while operation is stopped.
(This is not displayed during operation.)
When heat exchanger sensor (2) temperature of
–20°C or under continued for more than 15
seconds while operation is stopped.
(This is not displayed during operation.)
After the decision speed has been 0 rps or more for
9 continuous minutes and the discharge pipe sensor
has sent a 10 second or more broken wire signal.
(Compressor is stopped.)
After the decision speed has been 0 rps or more for
9 continuous minutes and the
power transistor
sensor has sent a 10 second or more broken wire
signal. (Compressor is stopped.)
Broken heat exchanger sensor (2)
wire
Connector poor connection
Disconnected sensor
Drain abnormality
(STM, SRRM only)
Float switch motion
Drain at reverse gradient
Float switch defective
Closed service valve
Heat exchanger sensor (1) is
disconnected.
Broken comp. suction sensor wire
Poor connector connection
When comp. suction sensor temperature of
–20°C or under continued for more than 10
seconds while operation is stopped.
Broken heat exchanger sensor (1)
wire
Connector poor connection
Disconnected sensor
Broken room temperature sensor
wire
Connector poor connection
Broken heat exchanger sensor
wire
Poor connector connection
Broken outdoor air temperature
sensor wire
Poor connector connection
Defective fan motor
Connector poor connection
RUN
light
1 time
flash
2 time
flash
4 time
flash
5 time
flash
6 time
flash
7 time
flash
Keeps
flashing
Keeps
flashing
Keep
flashing
Keep
flashing
Keep
flashing
Keeps
flashing
Keeps
flashing
Keeps
flashing
Keeps
flashing
TIMER
light
Comes
on
Comes
on
Comes
on
Comes
on
Comes
on
Comes
on
1 time
flash
2 time
flash
4 time
flash
5 time
flash
6 time
flash
E6
E7
E9
E6
E16
E6
E38
E37
E39
E53
E41
Stays off
Stays off
Stays off
Stays off
Stays off
Stays off