Specifications

33
Dec. 2012
Mitsubishi IPM-series Application Note
9-4 Fault Signal of IPM
IPM (Intelligent Power Modules) have sophisticated built-in protection circuits that prevent the power devices
from being damaged should the system malfunction or be over stressed. Control supply under-voltage(UV)
, over
temperature(OT), and short-circuit(SC) protection are all provided by the IPM's internal gate control circuits. A
fault output signal is provided to alert the system controller if any of the protection circuits are activated. Following
Fig.9.7 is a block diagram showing the IPMs internally integrated functions.
Fig.9.7 Timing chart of Control and protection of IPM
Control Supply Under-Voltage (UV)
The IPM’s internal control circuits operate from an isolated 15V DC supply. If, for any reason, the voltage of
this supply drops below the specified under-voltage trip level (UVt), the power devices will be turned off and a
fault signal will be generated. Small glitches less than the specified tdUV(<10us) in length will not affect the
operation of the control circuitry and will be ignored by the under voltage protection circuit. In order for normal
operation to resume, the supply voltage must exceed the under voltage reset level (UVr). Operation of the
under-voltage protection circuit will also occur during power up and power down of the control supply. This
operation is normal and the system controller's program should take the fault output delay (tfo) into account.
Note)
1. Application of the main bus voltage at a rate greater than 20V/ms before the control power supply is on
and stabilized may cause destruction of the power devices.
2. Voltage ripple on the control power supply with dv/dt in excess of 5V/us may cause a false trip of the UV
lock-out.
Over Temperature (OT)
The IPM has a temperature sensor mounted on surface of IGBT chips. If the temperature of the IGBT chips
exceeds the over temperature trip level (OT) the IPMs internal control circuit will protect the power devices by
disabling the gate drive and ignoring the control input signal until the over temperature condition has subsided.
The fault output will remain as long as the over temperature condition exists. When the temperature falls below
the over temperature reset level (OT
r), and the control input is high (offstate) the power device will be enabled
and normal operation will resume at the next low (on) input signal.
Note)
1. Tripping of the over-temperature protection is an indication of stressful operation. Repetitive tripping
should be avoided.
16
OT
r
Tj
VGE
Ic
SC
t
VD
Fo outpu
t
UV
r
UV
t
Fo
Signal inpu
t
Fo
FoFo
UV protection SC protection
OT protection
Using IPM