* Set the refrigerant address using the DIP switch of the outdoor unit.
1
Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
2
When a Different Refrigerant System Grouping is Used.
Up to 16 refrigerant systems can be controlled as one group using the slim MA re
-
mote controller.
Note:
Insinglerefrigerantsystem(twin/triple),thereisnoneedofwiring
2
.
9. Systemcontrol(Fig.9-1)
SW1
Function table
<SW1>
Function
Operation according to switch setting
ON OFF
SW1
function
settings
1 Compulsory
defrosting
Start Normal
2 Error history
clear
Clear Normal
3
4
5
6
Refrigerant
system ad
-
dress setting
Settings for outdoor unit addresses
0 to 15
ON
OFF
A
Outdoor unit
B
Indoor unit
C
Master remote controller
D
Subordinate remote controller
E
Standard 1:1 (Refrigerant address = 00)
F
Simultaneous twin (Refrigerant address = 01)
G
Simultaneous triple (Refrigerant address = 02)
E
SW 1 - 3 ~ 6
F
SW 1 - 3 ~ 6
G
SW 1 - 3 ~ 6
Fig.9-1
TB1
A GFA
A
E
B B B B B
B
DC
TB1 TB1
TB4
TB5
TB4
TB5
TB4 TB4
TB5
TB4 TB4
1
1
2
ON
OFF
ON
OFF
ON
OFF
3 4 5 6
3 4 5 6
3 4 5 6
2
8. SpecialFunctions
8.3. Refrigerantcollecting(pumpdown)
Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.
1
Supply power (circuit breaker).
* When power is supplied, make sure that “CENTRALLY CONTROLLED” is not
displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis
-
played, the refrigerant collecting (pump down) cannot be completed normally.
2
After the gas stop valve is closed, set the SWP switch on the control board of
the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor
and outdoor units) start operating and refrigerant collecting operation begins.
LED1 and LED2 on the control board of the outdoor unit are lit.
* Only set the SWP switch (push-button type) to ON if the unit is stopped. How
-
ever, even if the unit is stopped and the SWP switch is set to ON less than
three minutes after the compressor stops, the refrigerant collecting operation
cannot be performed. Wait until compressor has been stopped for three min
-
utes and then set the SWP switch to ON again.
3
Because the unit automatically stops in about two to three minutes after the
refrigerant collecting operation (LED1 and LED2 are lit), be sure to quickly
close the gas stop valve. When LED1 and LED2 are lit and the outdoor unit is
stopped, open the liquid stop valve completely, and then repeat step
2
after
three minutes have passed.
* If the refrigerant collecting operation has been completed normally (LED1
and LED2 are lit), the unit will remain stopped until the power supply is turned
off.
4
Turn off the power supply (circuit breaker).
* Note that when the length of the extension piping is long, it may not be pos
-
sible to perform a pump-down operation. When performing the pump-down
operation, make sure that the low pressure is lowered to near 0 MPa (gauge).