Installation manual

4
2. Installationlocation
Fig.3-1
2.4. Ventilationandservicespace
2.4.1. Windylocationinstallation
When installing the outdoor unit on a rooftop or other location unprotected from
the wind, situate the air outlet of the unit so that it is not directly exposed to strong
winds. Strong wind entering the air outlet may impede the normal airow and a
malfunction may result.
The following shows three examples of precautions against strong winds.
1
Face the air outlet towards the nearest available wall about 100 cm away from
the wall. (Fig. 2-3)
2
Install an optional air guide if the unit is installed in a location where strong
winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)
A
Air outlet guide
3
Position the unit so that the air outlet blows perpendicularly to the seasonal
wind direction, if possible. (Fig. 2-5)
B
Wind direction
Fig.2-4
Fig.2-3
Fig.2-5
2.4.2. Wheninstallingasingleoutdoorunit(Refertothelastpage)
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
1
Obstacles at rear only (Fig. 2-6)
2
Obstacles at rear and above only (Fig. 2-7)
3
Obstacles at rear and sides only (Fig. 2-8)
4
Obstacles at front only (Fig. 2-9)
* When using an optional air outlet guide, the clearance is 500 mm or more.
5
Obstacles at front and rear only (Fig. 2-10)
* When using an optional air outlet guide, the clearance is 500 mm or more.
6
Obstacles at rear, sides, and above only (Fig. 2-11)
Do not install the optional air outlet guides for upward airow.
2.4.3.
Wheninstallingmultipleoutdoorunits(Refertothelastpage)
Leave 10 mm space or more between the units.
1
Obstacles at rear only (Fig. 2-12)
2
Obstacles at rear and above only (Fig. 2-13)
No more than three units must be installed side by side. In addition, leave space as
shown.
Do not install the optional air outlet guides for upward airow.
3
Obstacles at front only (Fig. 2-14)
* When using an optional air outlet guide, the clearance is 1000 mm or more.
4
Obstacles at front and rear only (Fig. 2-15)
* When using an optional air outlet guide, the clearance is 1000 mm or more.
5
Single parallel unit arrangement (Fig. 2-16)
* When using an optional air outlet guide installed for upward airow, the clearance is 1000
mm or more.
6
Multiple parallel unit arrangement (Fig. 2-17)
* When using an optional air outlet guide installed for upward airow, the clearance is 1500
mm or more.
7
Stacked unit arrangement (Fig. 2-18)
The units can be stacked up to two units high.
No more than two stacked units must be installed side by side. In addition, leave space as
shown.
3. Installingtheoutdoorunit
Be sure to install the unit in a sturdy, level surface to prevent rattling noises dur-
ing operation. (Fig. 3-1)
<Foundation specications>
Foundation bolt M10 (3/8")
Thickness of concrete 120 mm
Length of bolt 70 mm
Weight-bearing capacity 320 kg
Make sure that the length of the foundation bolt is within 30 mm of the bottom
surface of the base.
Secure the base of the unit rmly with four-M10 foundation bolts in sturdy loca
-
tions.
Installingtheoutdoorunit
Do not block the vent. If the vent is blocked, operation will be hindered and
breakdown may result.
In addition to the unit base, use the installation holes it xes top panel on the
back of the unit to attach wires, etc., if necessary to install the unit. Use self-
tapping screws (ø5 × 15 mm or less) and install on site.
Warning:
The unit must be securely installed on a structurethat can sustain its
weight.Iftheunitismountedonanunstablestructure,itmayfalldownand
causedamageorinjuries.
Theunitmustbeinstalled according to the instructions in order tomini-
mizetheriskofdamagefromearthquakes,typhoons,orstrongwinds.An
incorrectlyinstalledunitmayfalldownandcausedamageorinjuries.
A
M10 (3/8") bolt
B
Base
C
As long as possible.
D
Vent
Max. 30
(mm)
Min. 360
Min. 10
BG79U791K01_en.indd 4 9/18/2007 3:43:18 PM