Installation manual

5
4. Installingtherefrigerantpiping
4.1.
PrecautionsfordevicesthatuseR410Arefrigerant
• Refertopage3forprecautionsnotincludedbelowonusingaircondition-
erswithR410Arefrigerant.
• Useesteroil,etheroil,alkylbenzeneoil(smallamount)astherefrigeration
oilappliedtothearedsections.
• Use C1220copper phosphorus, for copper and copper alloy seamless
pipes,toconnecttherefrigerantpipes.Userefrigerantpipeswiththethick
-
nesses specied in the table to the below.Make sure the insides of the
pipesarecleananddonotcontainanyharmfulcontaminantssuchassul
-
furiccompounds,oxidants,debris,ordust.
Alwaysapplyno-oxidationbrazingwhenbrazingthepipes,otherwise,the
compressorwillthedamaged.
Warning:
Wheninstallingormovingtheairconditioner,useonlythespeciedrefriger
-
ant(R410A)tochargethe refrigerantlines.Donotmixitwithanyotherre
-
frigerantanddonotallowairtoremaininthelines.Airenclosedinthelines
cancausepressurepeaksresultinginaruptureandotherhazards.
Pipe size (mm) ø6.35 ø9.52 ø12.7 ø15.88 ø19.05 ø22.2 ø25.4 ø28.58
Thickness (mm)
0.8 0.8 0.8 1.0 1.0 1.0 1.0 1.0
Donotusepipesthinnerthanthosespeciedabove.
Use1/2HorHpipesifthediameteris22.2mmorlarger.
FortheRP250,use1/2HorHpipesifthediameteris19.05mmorlarger.
4.2. Connectingpipes
When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100°C or more,
thickness of 12 mm or more).
The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specic gravity of 0.03, thickness of 9 mm or more).
Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten
-
ing are nut.
A
(Fig. 4-1)
Use two wrenches to tighten piping connections.
B
(Fig. 4-1)
Use leak detector or soapy water to check for gas leaks after connections are
completed.
Apply refrigerating machine oil over the entire are seat surface.
C
(Fig. 4-1)
Use the are nuts for the following pipe size.
D
(Fig. 4-1)
INDOOR UNIT RP50 RP60, 71 RP100-140
Gas side Pipe size (mm)
ø12.7 ø15.88 ø15.88
Liquid side Pipe size (mm)
ø6.35 ø9.52 ø9.52
When bending the pipes, be careful not to break them. Bend radii of 100 mm to
150 mm are sufcient.
Make sure the pipes do not contact the compressor. Abnormal noise or vibration
may result.
1
Pipes must be connected starting from the indoor unit.
Flare nuts must be tightened with a torque wrench.
2
Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil
(Applied on site).
When usual pipe sealing is used, refer to Table 1 for aring of R410A refrigerant
pipes.
The size adjustment gauge can be used to conrm B measurements.
Table 1 (Fig. 4-2)
Copper pipe O.D.
(mm)
B (mm)
Flare tool for R410A Flare tool for R22·R407C
Clutch type
ø6.35 (1/4") 0 - 0.5 1.0 - 1.5
ø9.52 (3/8") 0 - 0.5 1.0 - 1.5
ø12.7 (1/2") 0 - 0.5 1.0 - 1.5
ø15.88 (5/8") 0 - 0.5 1.0 - 1.5
ø19.05 (3/4") 0 - 0.5 1.0 - 1.5
3
Use the following procedure for connecting the gas-side piping. (Fig. 4-3)
1 Braze the
E
Joint pipe provided to the outdoor unit using locally procured braz
-
ing materials and
C
Local piping without oxygen.
2 Connect the
E
Joint pipe to the gas-side Stop valve.
Use two wrenches to tighten the are nut.
* If order is reversed, refrigerant leak occurs because of the part damaging by brazing re.
For PEA-RP200, 250, 400, 500GA
The method of pipe connection is brazing connection.
PEA-200 PEA-250 PEA-400 PEA-500
Gas side Pipe size (mm)
ø25.4 ø25.4 ø25.4 ø25.4
Liquid side Pipe size (mm)
ø9.52 ø12.7 ø9.52 ø12.7
A
(Fig. 4-1)
Copper pipe O.D.
(mm)
Flare dimensions
øA dimensions (mm)
ø6.35 8.7 - 9.1
ø9.52 12.8 - 13.2
ø12.7 16.2 - 16.6
ø15.88 19.3 - 19.7
ø19.05 23.6 - 24.0
B
(Fig. 4-1)
Copper pipe O.D.
(mm)
Flare nut O.D.
(mm)
Tightening torque
(N·m)
ø6.35 17 14 - 18
ø6.35 22 34 - 42
ø9.52 22 34 - 42
ø12.7 26 49 - 61
ø12.7 29 68 - 82
ø15.88 29 68 - 82
ø15.88 36 100 - 120
ø19.05 36 100 - 120
A
Flare cutting dimensions
B
Flare nut tightening torque
A
Die
B
Copper pipe
A
Stop valve (gas-side)
B
Seal section
C
Local piping
D
Double spanner section
E
Joint pipe
F
Pipe cover
Fig.4-1
Fig.4-2
Fig.4-3
45° ± 2°
90° ± 0.5°
R0.4 ~ R0.8