Specifications

6
3.8.1 VRLA Battery System Example (EXAMPLE using 225 kVA UPS)
a. The battery system shall include a DC landing box (Wall or floor
mounted) equipped with a 600A/500Vdc breaker. The landing box shall
interface the UPS’ DC input to battery cabinets.
b. The battery shall be capable of operating in an average ambient
temperature of 25 °C, with excursions of 16 °C to 32 °C and shall be sized
as follows:
1. float voltage: 405 VDC
(2.25 to 2.27 V/cell)
2. final voltage: 300 VDC
(1.67V/cell)
4.0 FUNCTIONAL DESCRIPTION
4.1 Converter
4.1.1 General
The Converter shall convert the incoming AC power into regulated DC power to
supply the inverter input and system battery. The Converter shall utilize the
following technologies:
a. Solid state PWM controlled IGBT power transistors switching at 6
kHZ. Switching shall be defined as IGBT turn on and turn off rate.
Doubling of frequency at inverter output shall not be considered as the true
switching frequency.
c. Input Power: Rated kVA at 1:1 ratio.
d. DSP based control logic.
4.1.2 Input Current Limit
i) The Converter logic shall provide input current limiting by limiting the AC
input current. Two (2) line-side current transformers shall be employed as a
means of sensing the current amplitude. The Converter logic shall also be
capable of providing auxiliary current limiting when the logic is signaled to do
so via an external dry contact closure (e.g.; UPS fed from motor generator).
The Converter shall be capable of supplying 1 line cycle of overload current
equal to 125% of its full load rating. It shall also provide sufficient capacity to
provide power to a fully loaded inverter while simultaneously recharging the
system battery to 90% of full capacity within 10 times the discharge time. The
DC output current limit values are as follows: