UNINTERRUPTIBLE POWER SUPPLY MODEL 9800AE MULTI MODULE SYSTEM SPECIFICATIONS
TABLE OF CONTENTS 1. GENERAL ...................................................................................................................................................2 1.1. SUMMARY...........................................................................................................................................2 1.2. STANDARD .........................................................................................................................................2 1.3.
SECTION 16610 UNINTERRUPTIBLE POWER SUPPLY MULTI-MODULE SYSTEM (UPS MMS) 1. GENERAL 1.1. SUMMARY A. This specification describes a three-phase, continuous duty, on-line solid-state Uninterruptible Power Supply Multi-Module System, hereafter referred to as the UPS MMS and a Critical Load Cabinet (CLC) that parallel connects individual UPS Module power circuits to offer system capacity or redundancy to support the critical load. B.
B. DC Input and associated Battery System (including battery disconnect circuit breaker). C. Inverter Section: 1. Solid-state Pulse Width Modulation (PWM) inverter utilizing IGBT 2. Inverter input fuses 3. Isolation transformer 4. Inverter output contactor D. Bypass Static Switch Circuit (sized to provide fault clearing): 1. Bypass input 2. Bypass static switch with primary contactor. E.
2. Bypass Circuit Load Sharing Reactors (if required) ACL1, ACL2 up to ACL8 depending on system UPS Module quantity. 3. Parallel bus power circuit. 4. Neutral Bar (if required). 5. Load bank test circuit (Option) 6. System Maintenance Bypass circuit breaker (SMB) and power circuit. 7. System Output circuit breaker (52L). 8. System output power circuit and terminals. 9. SMB, 52L Interlock System. 10. Interface terminal for CLC circuit breaker status. B.
bypass static switch circuit and associated control circuitry (UPS Module Control and UPS MMS Bypass Operation Control). The same bypass source shall be connected to each UPS Module bypass input, with each UPS Module bypass static switch circuit utilized during UPS MMS Bypass Operation. For uninterrupted transfer of the load to the bypass source and to UPS MMS Bypass Operation, the bypass source must be available.
Monitoring System. J. Monitoring System Operation - The Monitoring System will monitor all UPS MMS components and display UPS MMS operational status and information on the Human Machine Interface (HMI). UPS MMS operation sequences shall also be possible from the Monitoring System HMI, and system summary alarm and user selectable system alarm contacts available. 1.5. SUBMITTALS 1.5.1. Proposal Submittals Submittals with the proposal shall include; A. System configuration with single line drawings. B.
7. There should be no inflammable / explosive gas. 8. Dust in the room where the UPS is installed must not exceed normal atmospheric dust levels. In particular, that dust should not include iron particles, oils or fats, or organic materials such as silicone. B.
Grounding Continuity Insulation strength test Control Circuit Operation Measurement of steady state characteristics (Voltage/ current/ efficiencies) Transient characteristics (0-100% step load, without batteries/ voltage fluctuation) 12. Overload Testing 13. Transfer switch operation 7. 8. 9. 10. 11. 2. PRODUCT 2.1. THE UPS SHALL HAVE THE FOLLOWING ELECTRICAL CHARACTERISTICS 2.1.1.
A. B. C. D. E. F. G. H. I. J. K. Configuration: 3-phase, 4-Wire Nominal Output Voltage: 480V, 600V Nominal Dynamic Voltage Regulation: 1% for Unbalanced Load Manually Adjustable Output : 5%, Voltage Range: Voltage Transient Response: 1. 100% Step Load: 2% 2. Loss or Return of AC Input: 1% 3. Inverter Bypass Transfer: 5% [Voltage Transient Response shall not exceed the above and shall recover to within: Nominal Voltage Regulation tolerance within 16.7 msec.] Output Frequency: 60 Hz [0.
150 225 300 375 500 750 93.5 93.0 93.5 93.5 94.0 94.0 93.5 93.0 93.5 93.5 94.0 94.0 2.1.7. CLC Power Section specification The CLC Power Section total kVA capability and associated component ampere ratings will be dependent on the total UPS MMS configuration, kVA capacity and output voltage specification. Refer to Mitsubishi Electric CLC Specification for further details.
2.2.2. Charger/Booster A. The charger/booster utilizes solid state Pulse Width Modulation (PWM) controlled Insulated Gate Bipolar Transistors (IGBT). The charger switching frequency is 10kHz, and the booster switching frequency 2kHz. B. The Battery Charge Current charger logic and control circuit DC battery current limiting function enables controlled battery charging. The battery charge current limit will control the recharge current by reducing the rectifier/charger output when the set limit is reached.
H. Battery Self Test (Diamond-Sense); for a short duration, a small power discharge from the battery is automatically performed. The UPS module, from this small power discharge, evaluates the degradation of the system battery. The following advantages are achieved: 1. The Diamond-Sense Battery Self-Test function can be performed even when load is on inverter. 2. Due to the short duration small power discharge, there is no effect to battery life expectancy. 3.
a. Field Programmable Gate Array (FPGA) Control b. DSP based Control c. DSP Sampling Frequency is 30 kHz, therefore the control samples 500 times in 1 cycle of output voltage. Output voltage is controlled with high precision. B. Voltage Regulation The inverter output voltage shall not deviate by more than +/- 1% RMS with the following steady state conditions: 1. 0 to 100% loading. 2. Inverter DC input varies from maximum to minimum. 3.
b. Inverter DC input varies from maximum to minimum. c. Environmental condition variations within the specifications defined herein. G. Output Harmonic Distortion The inverter output shall limit the amount of harmonic content to 2% maximum at 100% linear load, and 5% maximum at 100% non-linear load. The need for additional filtering to limit the harmonic content shall not be required. Therefore high efficiency, reliability and original equipment footprint are maintained. H.
purpose of this feature is to compensate for varying line drop voltage between the inverter and the critical load M. Inverter Operation Inhibit The external dry contact can inhibit the inverter operation. When UPS condition is load on inverter, load is transferred to bypass. 2.2.4. UPS Module Control and Monitoring. A. UPS Module Control and Monitoring operates and controls the hybrid converter, inverter and independent automatic bypass static switch circuit (working in conjunction with UPS MMS Control). B.
static switch and shall at the same time as the static switch, be energized and upon closure maintain the critical load feed from the bypass source. The static switch shall only be utilized for the time needed to energize the wrap around contactor therefore increasing reliability. The bypass circuit shall be capable of supplying the UPS rated load current and also provide fault clearing current capabilities.
providing load power from bypass source supply. a. For bypass operation details, refer to previous section UPS MMS Bypass Operation. B. UPS MMS Parallel Operation Control 1. UPS MMS Parallel Operation Control in each UPS Module utilizes cross current control signals between the UPS Modules to calculate and perform fast simultaneous inverter reference voltage and phase waveform control. This UPS MMS Parallel Operation Control ensures that at all times: a.
measured values, while also offering operator sequence instructions (start/stop function etc. - Password protection possible). The LCD panel allows the user to verify the status and operation of the UPS Module components by the mimic display. The following information is available on the MAIN MENU Sheet: Display information: a. Bypass Voltage and Frequency b. Input Voltage and Frequency c. Battery Voltage (and charge/discharge current) d. Battery capacity remaining during power failure conditions e.
c. d. e. f. g. h. i. Battery Operation Output Overload Rectifier Operation Inverter Running Synchronously Static Bypass Input Out of Range Minor Fault Data Major Fault Data B. LED indication The Operation/Display Panel contains the following LED indication: a. b. c. d. e. f. Load on Inverter Battery operation Load on Bypass Overload LCD Fault UPS Fault (Green) (Yellow) (Green) (Red) (Red) (Red) C.
Download Alarm and System Event log to PCRS 232 Communication 2.2.11. External signal interface terminal The UPS Module is equipped with a series of input/output terminals for external annunciation of alarms and for remote access of certain UPS functions. A. Terminals OUT 1 to OUT 6 are user programmable, with the default settings: a. b. c. d. e. f. OUT 1: Load on Bypass OUT 2: Load on Inverter OUT 3: Battery Operation OUT 4: Rectifier Operation OUT 5: Battery Low Voltage OUT 6: Overload B.
2.3.2. SMB and 52L circuit breaker and associated power circuits The CLC contains power circuit. The system bypass source is a common feed to the UPS Module bypass inputs and also the CLC System Maintenance Bypass input. An electro-mechanical interlock system will prevent closure of the SMB circuit breaker and subsequent opening of 52L circuit breaker unless UPS MMS Bypass Operation is active. Refer to previous section System Maintenance Bypass Operation.
b. UPS Module component and CLC CB color status indication. c. System input and output measurement data. d. Screen selection icons 2. Individual UPS Module information: a. UPS Module mimic display and power flow. b. UPS Module component color status indication. c. UPS Module input and output measurement data. d. UPS Module Battery Data e. Screen selection icons 3. System Event and Alarm information (History log). a. UPS Module Alarm and event Groups. b. Alarm and event history 4.
NEMA standard for floor mounting. The UPS shall be equipped with standard forklift provisions to allow ease of installation using conventional lifting/moving equipment. The UPS module cabinet shall have hinged and lockable doors on the front only. Operating controls shall be located outside the locked doors. Input, output, and battery cables shall be installed through the top or bottom of the cabinet. 2.4.2.
A. The equipment shall be checked out and started by a customer support representative from the equipment manufacturer. Visual and mechanical inspection of electrical installation, initial UPS startup and operational training shall be performed. A signed service report shall be submitted after equipment is operational. B. The following inspection and test procedures shall be performed by field service personnel during the UPS startup; 1. Visual Inspection a. Ensure that shipping members have been removed.
98AEtypMMSspec_RevB.doc 25 Copyright © 2007, Mitsubishi Electric Power Products Inc. SP-0011 Rev.